8-8. EMERGENCY-TEST OPERATION
In case of test run operation or emergency operation, use the EMERGENCY OPERATION switch on the front of the
indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote
controller run down. The unit will start and the OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at
High speed and the system is in continuous operation. (The thermostat is ON.)
After 30 minutes of test run operation the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of
75˚F.
The fan speed shifts to Med. speed.
The coil frost prevention works even in emergency operation, and defrosting cycle as well.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO (
) mode.
Emergency operation continues until the EMERGENCY OPERATION switch is pressed once or twice or the unit receives
any signal from the remote controller. In case of latter normal operation will start.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
MSZ09UN
MSZ12UN
8-9. Main power supply circuit
POWER
SUPPLY
L63
L62
CT61
DS62
X64
R64
DS61
L61
C61
C63
R61
IPM
+
–
(–)
(~)
(~)
(+)
(–) (~)
(+)
(~)
W
V
U
P
N
U
V
W
+
–
COMPRESSORE
MICROPROCESSOR
ELECTRONIC CONTROL P.C. BOARD
NOISE FILTER P.C. BOARD
1. Outline of main power supply circuit
(1) When the electricity is turned on to the outdoor unit
Rush current generates in the main power supply circuit.
To prevent the rush current from running into the main power supply circuit, R64(Current-limiting resistor) absorbs
the rush current.
After the rush current is absorbed, X64(Relay) is ON and the circuit to R64 is short-circuited, then the electricity to
R64 is bypassed.
Following the indoor unit’s operation, X64 is switched to ON or OFF.
Outline drawing of main power supply