29
Time chart of defrosting in HEAT mode (reverse type)
set position
set position
set speed
Indoor fan
Compressor normal
Outdoor fan
R.V. coil
(21S4)
OFF
ON
OFF
MAX. 79Hz (MSZ12UN)
MAX. 80Hz (MSZ09UN)
horizontal
Horizontal vane
Very Low (temperature of indoor coil thermistor > 64
°
F)
30
seconds
30
seconds
30
seconds
1second
5 seconds
1second
OFF
OFF
OFF
5
seconds
MAX. Hz
MAX. Hz
ON
ON
ON
<outdoor unit>
<indoor unit>
5. R.V. coil control
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Compressor
R.V. coil
(COOL / DRY)
(HEAT)
5 sec.
5 sec.
ON
OFF
ON
OFF
OB297--1.qxp 04.2.4 4:20 PM Page 29