46
2. Flow chart of the detailed outdoor unit failure mode recall function
2.Blinking pattern when outdoor unit is abnormal:
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Does the upper lamp of OPERATION INDICATOR
lamp on the indoor unit blink at the interval of 0.5
seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the upper
lamp of OPERATION INDICATOR lamp. 2
Yes
(Blinks
)
No
(OFF)
The outdoor unit might be abnormal.
Check if outdoor unit is abnormal according to the following procedures.
Operational procedure
Make sure that the remote controller is set to the failure mode recall func-
tion.
With the remote controller headed towards the indoor unit, press TOO
COOL or TOO WARM button to adjust the set temperature to 77°F (25°C).
1
1. Regardless of normal or abnormal condition, 2 short
beeps are emitted as the signal is received.
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to
outdoor unit failure mode table (10-2.3.).
Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
The outdoor unit is normal.
Release the failure mode recall function accord-
ing to the left mentioned procedure.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (10-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE
: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
OBH549G
Содержание Mr.Slim MSY-D30NA
Страница 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Страница 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Страница 43: ...9 MUY D30NA MUY D36NA ...
Страница 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Страница 131: ...5 MUZ GE24NA MUY GE24NA Piping Air outlet Drain outlet Air inlet back and side Drain hose OBH549G ...
Страница 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Страница 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Страница 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Страница 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Страница 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Страница 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Страница 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Страница 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Страница 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Страница 148: ...22 MUY GE18NA 1 OBH549G ...
Страница 149: ...23 MUZ GE24NA OBH549G ...
Страница 150: ...24 MUY GE24NA OBH549G ...
Страница 199: ...73 OBH549G ...