9-4. TROUBLESHOOTING CHECK TABLE
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the
power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes.
OPERATION INDICATOR
Lighted
Blinking
Not lighted
No. Abnormal
point
Operation indicator lamp
Symptom
Condition
Remedy
1
Miswiring
or serial
signal
Upper lamp
fl
ashes.
0.5-second ON
0.5-second OFF
Indoor unit and
outdoor unit do
not operate.
The serial signal from the outdoor unit is not
received for 6 minutes.
• Refer to 9-6. "How to check
miswiring and serial signal er-
ror".
2
Indoor coil
thermistor
Upper lamp
fl
ashes.
2-time
fl
ash
2.5-second OFF
The indoor coil or the room temperature ther-
mistor is short or open circuit.
• Refer to the characteristics of
indoor coil thermistor, and the
room temperature thermistor
(9-7.).
Room tem-
perature
thermistor
3
Indoor fan
motor
Upper lamp
fl
ashes.
3-time
fl
ash
2.5-second OFF
The rotational frequency feedback signal is
not emitted during the indoor fan operation.
• Refer to 9-6. "Check of in-
door fan motor".
4
Indoor con-
trol system
Upper lamp
fl
ashes.
4-time
fl
ash
2.5-second OFF
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
• Replace the indoor electronic
control P.C. board.
5
Outdoor
power sys-
tem
Upper lamp
fl
ashes.
5-time
fl
ash
2.5-second OFF
It consecutively occurs 3 times that the com-
pressor stops for overcurrent protection or
start-up failure protection within 1 minute after
start-up.
• Refer to "How to check of in-
verter/compressor".
Refer to outdoor unit service
manual
• Check the stop valve.
6
Outdoor
thermistors
Upper lamp
fl
ashes.
6-time
fl
ash
2.5-second OFF
The outdoor thermistors short or open circuit
during the compressor operation.
• Refer to "Check of outdoor
thermistor".
Refer to outdoor unit service
manual.
7
Outdoor
control sys-
tem
Upper lamp
fl
ashes.
7-time
fl
ash
2.5-second OFF
It cannot properly read data in the nonvolatile
memory of the inverter P.C. board or the out-
door electronic control P.C. board.
• Replace the inverter P.C. board
or the outdoor electronic control
P.C. board.
Refer to outdoor unit service
manual.
8
Other ab-
normality
Upper lamp
fl
ashes.
14-time
fl
ash
2.5-second OFF
An abnormality other than above mentioned
is detected.
• Check the stop valve.
• Con
fi
rm the abnormality in de-
tail using the failure mode recall
function for outdoor unit.
9
Outdoor
control sys-
tem
Upper lamp lights up.
Outdoor unit
does not oper-
ate
It cannot properly read data in the nonvolatile
memory of the inverter P.C. board or the out-
door electronic control P.C. board.
• Check the blinking pattern of
the LED on the inverter P.C.
board or the outdoor electronic
control P.C. board.
OBH548D
Содержание Mr.Slim MSY-D30NA
Страница 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Страница 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Страница 43: ...9 MUY D30NA MUY D36NA ...
Страница 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Страница 131: ...5 MUZ GE24NA MUY GE24NA Piping Air outlet Drain outlet Air inlet back and side Drain hose OBH549G ...
Страница 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Страница 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Страница 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Страница 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Страница 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Страница 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Страница 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Страница 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Страница 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Страница 148: ...22 MUY GE18NA 1 OBH549G ...
Страница 149: ...23 MUZ GE24NA OBH549G ...
Страница 150: ...24 MUY GE24NA OBH549G ...
Страница 199: ...73 OBH549G ...