23
9-4. TROUBLESHOOTING CHECK TABLE
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the
power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes.
OPERATION INDICATOR
Lighted
Blinking
Not lighted
No. Abnormal
point
Operation indicator lamp
Symptom
Condition
Remedy
1 Miswiring or
serial signal
Left lamp
fl
ashes.
0.5-second ON
0.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
The serial signal from the outdoor unit is not
received for a maximum of 6 minutes.
Refer to 9-6. "How to check miswiring
and serial signal error".
•
2
Indoor coil
thermistor
Left lamp
fl
ashes.
2-time
fl
ash
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
The indoor coil or the room temperature
thermistor is short or open circuit.
Refer to 9-7.the characteristics of indoor
coil thermistor, and the room tempera-
ture thermistor.
•
Room
temperature
thermistor
3 Indoor fan
motor
Left lamp
fl
ashes.
3-time
fl
ash
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
The rotational frequency feedback signal is not
emitted during the indoor fan operation.
Refer to 9-6. "Check of indoor fan mo-
tor".
•
4 Indoor con-
trol system
Left lamp
fl
ashes.
4-time
fl
ash
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
Replace the indoor electronic control
P.C. board.
•
5
Outdoor
power sys-
tem
Left lamp
fl
ashes.
5-time
fl
ash
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
It consecutively occurs 3 times that the
compressor stops for overcurrent protection or
start-up failure protection within 1 minute after
start-up.
Refer to "How to check of inverter/com-
pressor".
Refer to outdoor unit service manual.
Check the stop valve.
•
•
6 Outdoor
thermistors
Left lamp
fl
ashes.
6-time
fl
ash
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
The outdoor thermistors short or open circuit
during the compressor operation.
Refer to "Check of outdoor thermistor".
Refer to outdoor unit service manual.
•
7 Outdoor con-
trol system
Left lamp
fl
ashes.
7-time
fl
ash
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
It cannot properly read data in the nonvola-
tile memory of the inverter P.C. board or the
outdoor electronic control P.C. board.
Replace the inverter P.C. board or the
outdoor electronic control P.C. board.
Refer to outdoor unit service manual.
•
8 Other abnor-
mality
Left lamp
fl
ashes.
14-time
fl
ash
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
An abnormality other than above mentioned is
detected.
Con
fi
rm the abnormality in detail using
the failure mode recall function for
outdoor unit.
•
Содержание Mr.Slim MSY-D30NA
Страница 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Страница 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Страница 43: ...9 MUY D30NA MUY D36NA ...
Страница 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Страница 131: ...5 MUZ GE24NA MUY GE24NA Piping Air outlet Drain outlet Air inlet back and side Drain hose OBH549G ...
Страница 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Страница 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Страница 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Страница 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Страница 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Страница 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Страница 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Страница 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Страница 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Страница 148: ...22 MUY GE18NA 1 OBH549G ...
Страница 149: ...23 MUZ GE24NA OBH549G ...
Страница 150: ...24 MUY GE24NA OBH549G ...
Страница 199: ...73 OBH549G ...