D How to check miswiring and serial signal error
Turn OFF the power supply.
Is there rated voltage AC in
the power supply?
Yes
No
Turn ON the power supply.
Check the power supply.
Is there rated voltage between
outdoor terminal block S1 and
S2?
No
Check the wiring.
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR
lamp light up? <Con
fi
rmation of the power to
the indoor unit>
Yes
No
Is serial signal error indicated 6 minutes later?
Yes
No
Is there any miswiring, poor
contact, or wire disconnec-
tion of the indoor/outdoor
connecting wire?
Is fuse (F65) broken?
Yes
Correct them.
No
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not miswiring.
Short-circuit outdoor terminal block S2
and S3. 1
B
1. Miswiring may damage indoor electronic control
P.C. board during the operation.
Be sure to con
fi
rm the wiring is correct before
the operation starts.
Turn ON the power supply.
Does the LED on the inverter P.C. board or
the outdoor electronic control P.C. board
repeat "3.6-second-OFF and 0.8-second-
ON quick blinking"?
Yes
No
(Lighted
or not
lighted)
Replace the inverter P.C. board or the
outdoor electronic control P.C. board.
2
2. Be careful of the residual
voltage of smoothing capacitor.
Turn OFF the power supply.
Remove the short-circuit between out-
door terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20 VDC
between outdoor terminal block S2 and
S3? <Con
fi
rmation of serial signal>
Yes
No
Is there any error of the in-
door/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Yes
Replace the indoor/out-
door connecting wire.
Is there rated voltage between
indoor terminal block S1 and S2?
<Con
fi
rmation of power voltage>
No
No
Is there any error of the in-
door/outdoor connecting wire,
such as the damage of the wire,
intermediate connection, poor
contact to the terminal block?
Yes
Replace the indoor/out-
door connecting wire.
No
Replace the indoor electronic control P.C. board.
Yes
Be sure to release the failure-mode recall function
after checking.
Yes
Turn OFF inverter-controlled lighting
equipment.
Turn OFF the power supply and then
turn ON again.
Press EMERGENCY OPERATION
switch.
•
•
•
A
Is serial signal
error indicated 6
minutes later?
B
Yes
Reinstall
either the unit
or the light
away from
each other.
Attach a
fi
lter
on remote
control receiv-
ing section
of the indoor
unit.
•
•
No
Содержание Mr.Slim MSY-D30NA
Страница 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Страница 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Страница 43: ...9 MUY D30NA MUY D36NA ...
Страница 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Страница 131: ...5 MUZ GE24NA MUY GE24NA Piping Air outlet Drain outlet Air inlet back and side Drain hose OBH549G ...
Страница 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Страница 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Страница 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Страница 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Страница 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Страница 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Страница 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Страница 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Страница 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Страница 148: ...22 MUY GE18NA 1 OBH549G ...
Страница 149: ...23 MUZ GE24NA OBH549G ...
Страница 150: ...24 MUY GE24NA OBH549G ...
Страница 199: ...73 OBH549G ...