27
A Check of indoor fan motor
9-6. TROUBLESHOOTING FLOW
The indoor fan motor error has occurred, and the indoor fan does not operate.
Turn OFF the power supply.
Is there any foreign matter that interferes
the rotation of the line
fl
ow fan?
Yes
No
Remove the foreign matter and
adjust the line
fl
ow fan.
Pay enough attention to the high voltage on the fan motor connector.
Turn ON the power supply, wait 5 seconds or more, and then press
EMERGENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds after EMER-
GENCY OPERATION switch is pressed.
If more than 12 seconds passes, turn OFF the power supply and turn it
ON again, then measure the voltage.
<Indoor power P.C. board>
1. Measure the voltage between CN211 (+) and (–).
2. Measure the voltage between CN211 (+) and (–).
<Indoor electronic control P.C. board>
3. Measure the voltage between CN10A (+) and JPG(GND)(–).
If more than 12 seconds passes after EMERGENCY OPERATION switch
is pressed, the voltage measured at 2. above goes 0 VDC although the
indoor P.C. board is normal.
Does the voltage between CN211
(+) and (–) on the power P.C. board
rise to the range of 2 to 6 VDC within
12 seconds after EMERGENCY
OPERATION switch is pressed?
Replace the indoor fan motor.
Yes
No
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211
(+) and (–) while the fan motor is
rotating.
Replace the indoor power
P.C. board and the indoor
terminal P.C. board.
Is it unchanged holding
0 or 15 VDC?
No
(Changed)
Yes
(Unchanged)
Measure the voltage CN10A (+)
and JPG (GND)(–) on the indoor
electronic control P.C board when
the fan motor is rotaring.
Replace the indoor fan motor.
Is there 294/325 VDC
between CN211 (+)
and (–) ?
Yes
Does the voltage between CN10A
(+) and JPG (GND)(–) on the indoor
electronic control P.C. board fall to
2 V or less within 12 seconds after
EMERGENCY OPERATION switch is
pressed?
Replace the indoor electronic
control P.C. board.
No
Yes
Replace the indoor power P.C.
board and the indoor terminal P.C.
board.
Is it unchanged holding
0 or 15 VDC?
No
(Changed)
Yes
(Unchanged)
Replace the indoor
electronic control P.C.
board.
No
MSZ-GE06/09/12/15/18NA
MSY-GE09/12/15/18NA
OBH548D
Содержание Mr.Slim MSY-D30NA
Страница 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Страница 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Страница 43: ...9 MUY D30NA MUY D36NA ...
Страница 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Страница 131: ...5 MUZ GE24NA MUY GE24NA Piping Air outlet Drain outlet Air inlet back and side Drain hose OBH549G ...
Страница 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Страница 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Страница 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Страница 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Страница 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Страница 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Страница 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Страница 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Страница 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Страница 148: ...22 MUY GE18NA 1 OBH549G ...
Страница 149: ...23 MUZ GE24NA OBH549G ...
Страница 150: ...24 MUY GE24NA OBH549G ...
Страница 199: ...73 OBH549G ...