5. PARAMETERS
5 - 19
No.
Symbol
Name and function
Initial
value
[unit]
Setting
range
PSD18 **SDIDT1 Mismatch permissible time DI1
Set a threshold of mismatch time of DI1A (CN10A-4) and DI1B (CN10B-4). When the
mismatch time of DI1A and DI1B reaches the setting value, [AL. 79.7 Mismatched input
signal error] will occur. Setting "0" disables alarm detections.
20
[ms]
0
to
60000
PSD19 **SDIDT2 Mismatch permissible time DI2
Set a threshold of mismatch time of DI2A (CN10A-13) and DI2B (CN10B-13). When the
mismatch time of DI2A and DI2B reaches the setting value, [AL. 79.7 Mismatched input
signal error] will occur. Setting "0" disables alarm detections.
20
[ms]
0
to
60000
PSD20 **SDIDT3 Mismatch permissible time DI3
Set a threshold of mismatch time of DI3A (CN10A-5) and DI3B (CN10B-5). When the
mismatch time of DI3A and DI3B reaches the setting value, [AL. 79.7 Mismatched input
signal error] will occur. Setting "0" disables alarm detections.
20
[ms]
0
to
60000
PSD21 **SDIDT4 Mismatch permissible time DI4
Set a threshold of mismatch time of DI4A (CN10A-14) and DI4B (CN10B-14). When the
mismatch time of DI4A and DI4B reaches the setting value, [AL. 79.7 Mismatched input
signal error] will occur. Setting "0" disables alarm detections.
20
[ms]
0
to
60000
PSD22 **SDIDT5 Mismatch permissible time DI5
Set a threshold of mismatch time of DI5A (CN10A-6) and DI5B (CN10B-6). When the
mismatch time of DI5A and DI5B reaches the setting value, [AL. 79.7 Mismatched input
signal error] will occur. Setting "0" disables alarm detections.
20
[ms]
0
to
60000
PSD23 **SDIDT6 Mismatch permissible time DI6
Set a threshold of mismatch time of DI6A (CN10A-15) and DI6B (CN10B-15). When the
mismatch time of DI6A and DI6B reaches the setting value, [AL. 79.7 Mismatched input
signal error] will occur. Setting "0" disables alarm detections.
20
[ms]
0
to
60000
PSD24
**SDIP1
Input device - Test pulse diagnosis execution selection 1
Select whether or not to diagnose DI1_ to DI4_ by test pulses outputted from PLSA and PLSB.
When executing the test pulse diagnosis with an external device, etc., set "0 (Not diagnose)".
Setting
digit
Explanation
Initial
value
Setting
range
_ _ _ x Test pulse diagnosis execution selection DI1
Select whether diagnose DI1_ or not.
0: Not diagnose
1: Diagnose
1h 0h
to
1h
_ _ x _ Test pulse diagnosis execution selection DI2
Select whether diagnose DI2_ or not.
0: Not diagnose
1: Diagnose
1h 0h
to
1h
_ x _ _ Test pulse diagnosis execution selection DI3
Select whether diagnose DI3_ or not.
0: Not diagnose
1: Diagnose
1h 0h
to
1h
x _ _ _ Test pulse diagnosis execution selection DI4
Select whether diagnose DI4_ or not.
0: Not diagnose
1: Diagnose
1h 0h
to
1h