![Mitsubishi Electric -MR-CV Скачать руководство пользователя страница 102](http://html.mh-extra.com/html/mitsubishi-electric/mr-cv/mr-cv_user-manual_20704102.webp)
100
10 OPTIONS AND PERIPHERAL EQUIPMENT
10.6 Earth-leakage current breaker
10.6
Earth-leakage current breaker
Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits. Leakage currents
containing harmonic contents are larger than those of the motor, which runs on AC power.
Select an earth-leakage current breaker according to the following formula, and ground the converter unit, drive unit, servo
amplifier, servo motor, etc. securely.
To minimize leakage currents, make the input and output wires as short as possible, and keep a distance of 30 cm or longer
between the wires and ground.
Rated sensitivity current
≥
10 • {Ig1 + Ign + Iga + K • (Ig2 + Igm)} [mA] . . . (10.1)
Ig1: Leakage current on the electric channel from the earth-leakage current breaker to the input terminals of the converter unit
Page 101 Example of leakage current (Ig1, Ig2) per km of CV cable run in metal conduit
Ig2: Leakage current on the electric channel from the output terminals of the drive unit to the servo motor
Page 101 Example of leakage current (Ig1, Ig2) per km of CV cable run in metal conduit
Ign: Leakage current when a filter is connected to the input side (4.4 mA per one FR-BIF(-H))
Iga: Leakage current of the converter unit and drive unit
The leakage current of the MR-CV_ power regeneration converter unit is 5 mA for all series. For the leakage current of the
drive units, refer to the manual and instruction manual of each drive unit.
Igm: Servo motor leakage current
Refer to the manual and instruction manual for each drive unit.
Earth-leakage current breaker
K
Type
Mitsubishi Electric products
Models provided with harmonic and surge
reduction techniques
NV-SV
NV-SVF
NV-SW
NV-CV
NV-CVF
NV-CW
NV-HV
1
General models
BV-C1
3
Ign
Ig1
NV
Iga
Ig2
Igm
M
Noise filter
Wire
Converter
unit
Drive unit
Wire