5 NETWORK CONFIGURATION OF RD77GF
5.2 Precautions for System Configuration
53
5
5.2
Precautions for System Configuration
Connecting devices to the same network
Do not connect the Ethernet devices compatible with other than the CC-Link IE Field Network (such as personal computers)
to the switching hub used in the CC-Link IE Field Network. A timeout may occur in the master station and all the stations may
be disconnected.
Connecting devices to the CPU module (built-in Ethernet port part)
When connecting devices to the CPU module (built-in Ethernet port part), power off the CPU module before connection.