9 -
29
9.
LOADING AND INSTALLATION
9.5.2
Wiring to module terminals
This section explains the wiring of power cables and ground wires to the main and
extension bases.
*1
Ground the LG and FG terminals by using a ground wire as thick and short as possible (2mm
in diameter).
POINT
(1) Use the thickest possible (max. 2mm
2
(14 AWG)) wires for the 100/200VAC
and 24VDC power cables. Be sure to twist these wires starting at the connec-
tion terminals. For wiring a terminal block, be sure to use a solderless termi-
nal. To prevent short-circuit due to loosening screws, use the solderless
terminals with insulation sleeves of 0.8mm or less thick. The number of the
solderless terminals to be connected for one terminal block are limited to 2.
(2) Be sure to ground the LG and FG terminals. Failure to do so may cause the
programmable controller to be susceptible to noise.
(3) A1S61PN and A1S62PN do not need to be switched as the are 100 to
240VAC wide-range.
AC
100/110VAC
200/220VAC
Fuse
DC24V
DC24V
AC
DC
Extension cable
Ground cable
Grounding
Main base unit
(QA1S38B)
A1S62PN
CPU
Extension base unit
(QA1S68B)
A1S62PN
I/O
100/240VAC
+24V
24G
INPUT
100-240VAC
+24V
24G
INPUT
100-240VAC
Connected to the 24VDC
terminal of the module that
requires 24VDC inside the
I/O module.
(LG)
*1
(FG)
*1
(LG)
*1
(FG)
*1
Terminal block
Solderless terminals
with insulation sleeves