Self-diagnostics list (continued)
*1
Can be changed by the parameter settings of the peripheral devices.
*2
Displayed as a three-digit trouble code only for errors with the "CHK" instruction.
Diagnostic Item
Diagnostic Timing
CPU Module
Status
Status of
RUN LED
Error Message
Error Code
(D9008)
CPU
er
ro
r
RAM check
• When switching on or resetting
• When M9084 is on during STOP
• When END instruction is executed
Stop
Flickering
RAM ERROR
20
Operation circuit check
• When switching on or resetting
OPE.CIRCUIT ERR.
21
Watchdog error supervision
• When END instruction is executed
WDT ERROR
22
END instruction not executed
• When END instruction is executed
END NOT EXECUTE
24
Main CPU check
Always
MAIN CPU DOWN
26, 60, 61
Memory card error
• When END instruction is executed
• When power is on
MEMORY CARD ERR.
16
I/O
er
ror
Module verify error
*1 (Default: stop)
When END instruction is executed
(However, not checked when M9084 is on.)
Stop/Run
Flickering/
On
UNIT VERIFY ERR.
31
Fuse blown
*1 (Default: stop)
When END instruction is executed
(However, not checked when M9084 is on.)
FUSE BREAK OFF
32
S
pe
ci
al
fu
ncti
o
n m
od
ul
e e
rr
or
Control bus check
When FROM/TO instruction are executed
and bus error occurs
Stop
Flickering
CONTROL-BUS ERR.
40
Special function module error
When FROM/TO instruction are executed
SP.UNIT DOWN
41
Link module error
• When switching on or resetting
•
LINK UNIT ERROR
42
I/O interrupt error
When interruption occurs
I/O INT.ERROR
43
Special function module
assignment error
• When switching on or resetting
•
SP.UNIT LAY.ERR.
44
Special module access error
*1 (Default: STOP)
When FROM/TO instruction are executed
Stop/Run
Flickering/
On
SP.UNIT ERROR
46
Link parameter error
• When switching on or resetting
•
Run
On
LINK PARA.ERROR
47
Ba
tt
er
y
Low battery
Always
(However, not checked when M9084 is on.)
Run
On
BATTERY ERROR
70
Operation error *1 (Default: RUN)
When each instruction is executed
Stop/Run
Flickering/
On
OPERATION ERROR
*2
[<CHK> ERROR
]
50
When switching from (STOP, PAUSE) to
(RUN, STEP RUN)
When switching from (STOP, PAUSE) to
(RUN, STEP RUN)
When switching from (STOP, PAUSE) to
(RUN, STEP RUN)
Содержание MELCEC Q Series
Страница 1: ...QCPU A A Mode User s Manual Q02CPU A Q02HCPU A Q06HCPU A ...
Страница 2: ......
Страница 249: ...App 55 APPENDICES Appendix5 2 A1S61PN A1S62PN and A1S63P power supply module Unit mm ...
Страница 261: ......