![Mitsubishi Electric MELCEC Q Series Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/mitsubishi-electric/melcec-q-series/melcec-q-series_user-manual_239056028.webp)
2 -
7
2.
SYSTEM CONFIGURATION
2.2.3
Precautions when using GPP function software packages and A8PUE peripheral devices which are
not compatible with AnU
When starting with GPP function software packages not compatible with the AnU, QCPU-
A (starting with the programmable controller model name "A3A" or "A3H") or a A8PUE
peripheral device (including A7PUS), the usable device ranges are limited as follows.
(1) List of usable device range
(1) The device range other than listed above is the same as that of QCPU-A.
(2) Refer to Operating Manual for peripheral devices to be used for available functions.
Item
AnACPU-compatible Module
A3HCPU-compatible Module
Programmable controller Model
"A3A"
at System FD Start-up
A8PUE
Programmable controller Model
"A3H"
at System FD Start-up
A7PUS
Instruction (sequence/basic/
application/dedicated)
All instructions can be used.
Program capacity
Max. 14k steps can be used for the main program.
I/O device points (X/Y)
X/Y0 to X/Y7FF can be used.
(X/Y800 to X/Y1FFF cannot be used.)
X/Y0 to X/Y7FF can be used.
(X/Y800 to X/Y1FFF cannot be used.)
M, L, S relay
M/L/S0 to M/L/S8191 can be used.
M/L/S0 to M/L/S2047 can be used.
(M/L/S2048 to M/L/S8191 cannot be used.)
Link relay (B)
B0 to BFFF can be used.
(B1000 to B1FFF cannot be used.)
B0 to B3FF can be used.
(B400 to B1FFF cannot be used.)
Timer (T)
T0 to T2047 can be used.
T0 to T255 can be used.
(T256 to T2047 cannot be used.)
Counter (C)
C0 to C1023 can be used.
C0 to C255 can be used.
(C256 to C1023 cannot be used.)
Data register (D)
D0 to D6143 can be used.
(D6144 to D8191 cannot be used.)
D0 to D1023 can be used.
(D1024 to D8191 cannot be used.)
Link register (W)
W0 to WFFF can be used.
(W1000 to W1FFF cannot be used.)
W0 to W3FF can be used.
(W400 to W1FFF cannot be used.)
Annunciator (F)
F0 to F2047 can be used.
F0 to F255 can be used.
(F256 to F2047 cannot be used.)
Index register (V, Z)
V, V1 to V6, Z, Z1 to Z6can be used.
V and Z can be used.
(V1 to V6, Z1 to Z6 cannot be used.)
Expanded comment
Max. 3968 points
–
Unusable
–
Latch (power failure compensation)
range
The device range shown above can be latched. The device range shown above can be latched.
I/O assignment
Possible to register occupied I/O
points and module model names.
–
Number of I/O occupied points can
be registered.
–
Содержание MELCEC Q Series