EMC AND LOW VOLTAGE DIRECTIVES
8.
8.1.1
EMC Directive related standards
(1) Regulations regarding emission
*1
QP: Quasi-peak value, Mean: Average value
*2
Programmable controllers are open-type devices (devices designed to be housed inside other
equipment) and must be installed inside a conductive control panel. The corresponding tests
were conducted with the programmable controller installed inside a control panel.
(2) Regulations regarding immunity
*1
Programmable controllers are open-type devices (devices designed to be housed inside other
equipment) and must be installed inside a conductive control panel. The corresponding tests
were conducted with the programmable controller installed inside a control panel.
*2
The accuracy of an analog-digital converter module may temporary vary within 10%.
Standard
Test item
Test description
Value specified in standard
EN61131-2:2007
CISPR16-2-3
Radiated emission
*2
Radio waves from the product are
measured.
• 30M-230MHz
QP: 40dB V/m (10m in
measurement range)
*1
• 230M-1000MHz
QP: 47dB V/m (10m in
measurement range)
CISPR16-2-1, CISPR16-1-2
Conducted emission
*2
Noise from the product to the power
line is measured.
• 150k-500kHz
QP: 79dB, Mean: 66dB
*1
• 500k-30MHz
QP: 73dB, Mean: 60dB
Standard
Test item
Test description
Value specified in standard
EN61131-2:2007
EN61000-4-2
Electrostatic discharge immunity
*1
Immunity test in which electrostatic
is applied to the cabinet of the
equipment.
• 8kV Air discharge
• 4kV Contact discharge
EN61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity
*1
Immunity test in which electric fields
are irradiated to the product.
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
EN61000-4-4
Electrical fast transient/burst
immunity
*1
Immunity test in which burst noise is
applied to the power line and signal
line.
• AC/DC main power, I/O power, AC
I/O (unshielded): 2kV
• DC I/O, analog, communication:
1kV
EN61000-4-5
Surge immunity
*1
Immunity test in which lightning
surge is applied to the power line
and signal line.
• AC power line, AC I/O power, AC I/
O (unshielded): 2kV CM, 1kV DM
• DC power line, DC I/O power: 0.5kV
CM, DM
• DC I/O, AC I/O (shielded), analog
*2
,
communication: 1kV CM
EN61000-4-6
Immunity to conducted
disturbances, induced by radio-
frequency fields
*1
Immunity test in which high
frequency noise is applied to the
power line and signal line.
0.15M-80MHz, 80% AM
modulation@1kHz, 10Vrms
EN61000-4-8
Power-frequency magnetic field
immunity
*1
Immunity test in which the product
is installed in inductive magnetic
field.
50Hz/60Hz, 30A/m
EN61000-4-11
Voltage dips and interruption
immunity
*1
Immunity test in which power supply
voltage is momentarily interrupted.
• Apply at 0%, 0.5 cycles and zero-
cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)