![Mitsubishi Electric MELCEC Q Series Скачать руководство пользователя страница 243](http://html.mh-extra.com/html/mitsubishi-electric/melcec-q-series/melcec-q-series_user-manual_239056243.webp)
App -
49
APPENDICES
Appendix4.1 Instructions with different specifications
This section explains how to modify the sequence program when the instructions with
different specifications are used.
Basically, the instructions which are not listed in this section do not require modifications.
• When M9053 is turned on, the Enable/Disable setting of the link refresh instruction
(EI, DI) can be performed.
• As the QCPU-A performs the link refresh in the END processing, enabling/
disabling the link refresh during the sequence program execution is not allowed.
Therefore, modify the sequence program.
(3) LEDA/LEDB instruction
(4) SUB, SUBP instruction.......... Unusable
• As the QCPU-A cannot store the microcomputer program, the SUB instruction is
cannot be used.
• To use in the QCPU-A, all the data processed in the microcomputer program area
has to be changed into those of the dedicated instructions.
(1) CHK instruction............ Modifications are required when the A1SHCPU or the
A2SHCPU is used in the refresh mode.
(2) DI/EI instruction............Modifications are required when the special relay M9053 is
on.
Output reverse instruction
X005
X5
ON
OFF
Y10
ON
OFF
CHK
X005
LEDB
FF
LEDC Y010
LEDR
Y010
M1
K4
Содержание MELCEC Q Series
Страница 1: ...QCPU A A Mode User s Manual Q02CPU A Q02HCPU A Q06HCPU A ...
Страница 2: ......
Страница 249: ...App 55 APPENDICES Appendix5 2 A1S61PN A1S62PN and A1S63P power supply module Unit mm ...