3 - 9 3 - 9
MELSEC-Q
3 SPECIFICATIONS
POINT
(1) Set within the digital input range and analog output range for each output
range.
If these ranges are exceeded, the maximum resolution and accuracy may not
fall within the performance specifications. (Avoid using the dotted line area
shown in Figures 3.3 and 3.4.)
(2) Set the offset/gain values for the user setting range 1 within a range in
which the following conditions are satisfied.
(a) Setting range is from 0 to 20 mA
(b) Normal resolution mode setting:
{ (Gain value) - (Offset value) } > 6.0mA
High resolution mode setting:
{ (Gain value) - (Offset value) } > 10.0mA