![Mitsubishi Electric GX Configurator-DA Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/mitsubishi-electric/gx-configurator-da/gx-configurator-da_user-manual_239042028.webp)
3 - 1 3 - 1
MELSEC-Q
3 SPECIFICATIONS
3 SPECIFICATIONS
3.1 Performance Specifications
3.1.1 Performance specifications list
(1) Q62DAN, Q64DAN, Q68DAVN, Q68DAIN
Table 3.1 Performance specifications list
Model name
Item
Q62DAN Q64DAN Q68DAVN Q68DAIN
Number of analog input channels
2 channels
4 channels
8 channels
Digital input
16-bit signed binary (normal resolution mode: -4096 to 4095,
high resolution mode: -12288 to 12287, -16384 to 16383)
Analog output
Voltage
–10 to 10 V DC (External load resistance value: 1 k to 1M )
—
Current
0 to 20 mA DC
(External load resistance value: 0 to 600 )
—
0 to 20 mA DC
(External load resistance
value: 0 to 600 )
I/O characteristics,
Maximum resolution
Analog output range
Normal resolution mode
High resolution mode
Digital input value
Maximum
resolution
Digital input value
Maximum
resolution
Voltage
0 to 5V
0 to 4000
1.25 mV
0 to 12000
0.416 mV
1 to 5V
1.0 mV
0.333 mV
-10 to 10V
-4000 to 4000
2.5 mV
-16000 to 16000
0.625 mV
User range
setting
0.75 mV
-12000 to 12000
0.333 mV
Current
0 to 20 mA
0 to 4000
5 A
0 to 12000
1.66 A
4 to 20 mA
4
A
1.33
A
User range
setting
-4000 to 4000
1.5
A
-12000 to 12000
0.83
A
Accuracy
(Accuracy in
respect to
maximum analog
output value)
1
Ambient temperature
25 ± 5 °C
Within ± 0.1 % (Voltage: ±10 mV, Current: ± 20
A)
Ambient temperature
0 to 55 °C
Within ± 0.3 % (Voltage: ± 30 mV, Current: ± 60
A)
Conversion speed
80 s/channel
Absolute
maximum output
Voltage
± 12 V
—
Current
21 mA
—
21 mA
E
2
PROM write count
Max. 100 thousand times
Output short circuit protection
Available
Insulation method
Between the I/O terminal and programmable controller power supply :
Between output channels :
Between external supply power and analog output :
Photo coupler insulation
No insulation
Transformer insulation
Dielectric withstand voltage
Between the I/O terminal and programmable controller power supply: 500VAC for 1 minute
Between external supply power and analog output: 500VAC for 1 minute
Insulation resistance
Between the I/O terminal and programmable controller power supply: 500VDC 20M or more
Between external supply power and analog output: 500VDC 20M or more
I/O occupied points
16 points (I/O assignment: Intelligent 16 points)
External interface
18-points terminal block
Applicable wire size
0.3 to 0.75 mm
2
Applicable solderless terminal
R 1.25-3
(A solderless terminal with sleeve cannot be used)
FG terminal: R1.25-3, 1.25-YS3, RAV1.25-3, V1.25-YS3A
Other terminals than FG: R1.25-3 (A solderless terminal
with sleeve cannot be used)
External supply power
24 V DC + 20 %, – 15 %
Ripple, spike 500 mV P-P or less
Inrush current: 4.7 A,
within 280
s
Inrush current: 4.7 A,
within 280
s
Inrush current: 4.7 A,
within 280
s
Inrush current: 4.7 A,
within 280
s
0.15 A
0.24 A
0.20 A
0.27 A
Internal current consumption (5 V DC)
0.33 A
0.34 A
0.38 A
0.38 A
Weight
0.19 kg
0.20 kg
0.20 kg
0.20 kg
1: D/A converter modules need to be powered on 30 minutes prior to operation for compliance to the
specification (accuracy).
3
Содержание GX Configurator-DA
Страница 2: ......
Страница 17: ...A 15 A 15 MEMO ...
Страница 116: ...6 3 6 3 MELSEC Q 6 PROGRAMMING 2 Programming example ...
Страница 118: ...6 5 6 5 MELSEC Q 6 PROGRAMMING 2 Programming example using the intelligent function module device U G ...
Страница 184: ...App 19 App 19 MELSEC Q APPENDICES Appendix 3 External Dimensions 1 Q62DAN Q64DAN Unit mm 2 Q68DAVN Q68DAIN Unit mm ...
Страница 185: ...App 20 App 20 MELSEC Q APPENDICES 3 Q62DA Q64DA Unit mm 4 Q68DAV Q68DAI Unit mm ...
Страница 186: ...App 21 App 21 MELSEC Q APPENDICES MEMO ...
Страница 189: ...WARRANTY ...
Страница 191: ......