7 - 26 7 - 26
MELSEC-Q
7 ONLINE MODULE CHANGE
(2) Dismounting of module
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to
enter the "Online module change" mode, double-click the module to be
changed online to display the "Online module change" dialog box.
(b) Click the "Execution" button to enable a module change.
If the following error dialog box appears, the user range cannot be saved.
Click the [OK] button, and perform the operation in Section 7.3.6 (2)(c) and
later.
(c) After confirming that the "RUN" LED of the module has turned off, remove
the terminal block and dismount the module.
POINT
Always dismount the module. If mounting confirmation is made without the module
being dismounted, the module will not start properly and the "RUN" LED will not be
lit.
Содержание GX Configurator-DA
Страница 2: ......
Страница 17: ...A 15 A 15 MEMO ...
Страница 116: ...6 3 6 3 MELSEC Q 6 PROGRAMMING 2 Programming example ...
Страница 118: ...6 5 6 5 MELSEC Q 6 PROGRAMMING 2 Programming example using the intelligent function module device U G ...
Страница 184: ...App 19 App 19 MELSEC Q APPENDICES Appendix 3 External Dimensions 1 Q62DAN Q64DAN Unit mm 2 Q68DAVN Q68DAIN Unit mm ...
Страница 185: ...App 20 App 20 MELSEC Q APPENDICES 3 Q62DA Q64DA Unit mm 4 Q68DAV Q68DAI Unit mm ...
Страница 186: ...App 21 App 21 MELSEC Q APPENDICES MEMO ...
Страница 189: ...WARRANTY ...
Страница 191: ......