3 - 30 3 - 30
MELSEC-Q
3 SPECIFICATIONS
3.4.9 Setting range (buffer memory address 20, 21: Un\G20, Un\G21)
(1) This area is used to confirm the setting range of the D/A converter module.
Settings for channels 1 to 4 are stored in Un\G20.
Settings for channels 5 to 8 are stored in Un\G21.
(2) For the Q62DAN and Q62DA, b8 to b15 (CH3 and 4 information) for Un\G20 and
Un\G21 (information of CH5 to CH8) are invalid.
For the Q64DAN and Q64DA, Un\G21 (CH5 to CH8 information) is invalid.
Output range
Setting value
4 to 20 (mA)
0
H
0 to 20 (mA)
1
H
1 to 5 (V)
2
H
0 to 5 (V)
3
H
–10 to 10 (V)
4
H
User range setting
F
H
(3) The default is 0
H
. The Q68DAVN and Q68DAV are operated in 2
H
(1 to 5 V)
setting even when 0
H
(default) is set for the output range setting so that 2
H
will be
stored.
POINT
Setting ranges cannot be changed by using Setting range (buffer memory
addresses 20, 21: Un\G20, Un\G21).
Change the setting range in the Switch setting for I/O and intelligent function
module dialog box. (Refer to Section 4.5.)
3.4.10 Offset/gain setting mode Offset/gain specification
(buffer memory address 22, 23: Un\G22, Un\G23)
(1) Specifies the channel to be adjusted for the offset/gain settings.
(2) Specification can be made for 1 channel only.
An offset/gain setting mode error (Error code 500) will occur if more than one
channel is specified at the same time.
(3) For the Q62DAN and Q62DA, b2 to b7 (CH3 to CH8) are invalid.
For the Q64DAN and Q64DA, b4 to b7 (CH5 to CH8) are invalid.
(4) Refer to Section 4.6 for the details of the offset/gain settings.
b15
b12 b11
b8
b7
b4
b3
b0
CH4
CH3
CH2
CH1
to
to
to
to
CH8
CH7
CH6
CH5
Un\G20 (setting range CH1 to CH4)
Un\G21 (setting range CH5 to CH8)
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
0
CH4 CH3 CH2 CH1
Un\G22 (Offset specification)
0
0
0
0
0
0
0
0
CH4 CH3 CH2 CH1
Un\G23 (Gain specification)
0
0
0
0
0
0
0
1: Channel to be set
0: Invalid
For Q62DAN, Q62DA, b2 to b15 information is fixed at 0.
CH8 CH7 CH6 CH5
CH8 CH7 CH6 CH5
For Q64DAN, Q64DA, b4 to b15 information is fixed at 0.
Содержание GX Configurator-DA
Страница 2: ......
Страница 17: ...A 15 A 15 MEMO ...
Страница 116: ...6 3 6 3 MELSEC Q 6 PROGRAMMING 2 Programming example ...
Страница 118: ...6 5 6 5 MELSEC Q 6 PROGRAMMING 2 Programming example using the intelligent function module device U G ...
Страница 184: ...App 19 App 19 MELSEC Q APPENDICES Appendix 3 External Dimensions 1 Q62DAN Q64DAN Unit mm 2 Q68DAVN Q68DAIN Unit mm ...
Страница 185: ...App 20 App 20 MELSEC Q APPENDICES 3 Q62DA Q64DA Unit mm 4 Q68DAV Q68DAI Unit mm ...
Страница 186: ...App 21 App 21 MELSEC Q APPENDICES MEMO ...
Страница 189: ...WARRANTY ...
Страница 191: ......