8 TROUBLESHOOTING
8.2.3 When an analog output value is not output
Check item
Action to be taken
Is 24VDC external power supply being supplied?
Verify that 24VDC voltage is being supplied to the external power
supply terminals
(Q62DAN, Q64DAN, Q62DA, Q64DA: terminal numbers 16, 17
Q68DAVN, Q68DAIN, Q68DAV, Q68DAI: terminal numbers 17, 18).
Is there any fault with the analog signal lines
such as broken or disconnected line?
Check for any abnormality on the signal lines by doing a visual check
and performing a continuity check.
Is the CPU module in the STOP status?
Set the CPU module to the RUN status.
Are the offset/gain settings correct?
Verify that the offset/gain settings are correct (Refer to sections 4.6,
5.6.2 and 5.6.3).
If the user range setting is being used, switch to a different default
output range and check if D/A conversion is correctly performed. If it
is correctly performed, redo the offset/gain settings.
Is the output setting range correct?
Verify setting range (buffer memory addresses 20, 21 (Un\G20,
Un\G21) in GX Developer monitor. If the output range setting is
incorrect, redo GX Developer intelligent function module switch
settings (Refer to Section 4.5).
Is the resolution mode setting correct?
Check the on/off status of High resolution mode status flag (X8) in GX
Developer system monitor.
If the resolution mode setting is incorrect, redo the GX Developer
intelligent function module switch setting. (Refer to Section 4.5.)
Is D/A conversion enable/disable setting for the
channel to be output set to Disable?
Check the setting of D/A conversion enable/disable (buffer memory
address 0: Un\G0) in GX Developer monitor and set it to Enable using
the sequence program or utility package (Refer to Section 3.4).
Is the D/A output enable/disable setting for the
channel to be output set to Disable?
Verify on/off for CH Output enable/disable flag (Y1 to Y8) in GX
Developer monitor.
If the output enable/disable flags are off, review the initial setting for
the sequence program or utility package (Refer to Section 3.3).
Is the digital value being written to the channel to
be output?
Verify CH Digital value (buffer memory address 1 to 8 (Un\G1 to 8)
in GX Developer monitor (Refer to Section 3.4).
Has Operating condition setting request (Y9)
been executed?
Set Operating condition setting request (Y9) from on to off from GX
Developer and check to see if the analog output is normal.
If normal analog output is obtained, review the initial setting for the
sequence program or utility package (Refer to Section 3.3).
POINT
If the analog output value is not output after the proper corrective action is taken in
accordance with the above check item, the possible cause is a module failure.
Consult the nearest sales representative or branch.
Содержание GX Configurator-DA
Страница 2: ......
Страница 17: ...A 15 A 15 MEMO ...
Страница 116: ...6 3 6 3 MELSEC Q 6 PROGRAMMING 2 Programming example ...
Страница 118: ...6 5 6 5 MELSEC Q 6 PROGRAMMING 2 Programming example using the intelligent function module device U G ...
Страница 184: ...App 19 App 19 MELSEC Q APPENDICES Appendix 3 External Dimensions 1 Q62DAN Q64DAN Unit mm 2 Q68DAVN Q68DAIN Unit mm ...
Страница 185: ...App 20 App 20 MELSEC Q APPENDICES 3 Q62DA Q64DA Unit mm 4 Q68DAV Q68DAI Unit mm ...
Страница 186: ...App 21 App 21 MELSEC Q APPENDICES MEMO ...
Страница 189: ...WARRANTY ...
Страница 191: ......