56
PPO TYPE SUPPORT SPECIFICATION
7.6.2
Parameter clear
Parameter clear can be performed from the master.
The communication parameters are not cleared. For details of the communication parameters, refer to the Instruction Manual (Detailed)
of the inverter.
7.6.3
Operation mode read/write
Read/write of the operation mode can be performed from the master.
7.6.4
Set frequency read
The frequency set to the inverter can be read from the master.
PNU
Item
Data definition
Data type
P2.2
Parameter clear
H965A
AUs16
P2.3
All parameter clear
H99AA
AUs16
P2.5
Parameter clear
H5A96
AUs16
P2.6
All parameter clear
HAA99
AUs16
P2.8
Faults history clear
H0000
AUs16
PNU
Item
Data definition
Data type
P3
Operation mode read/write
External operation mode: H10
PU operation mode: H11 (For writing, when "6" is set in
Pr.79
)
Network operation mode: H14
Us16
PNU
Item
Data definition
Data type
P4.1
Set frequency (RAM) read
Set frequency (RAM) is read.
AUs16
P4.2
Set frequency (EEPROM) read
Set frequency (EEPROM) is read.
AUs16