PPO TYPE SUPPORT SPECIFICATION
51
7
ESW
(Extended format)
SU signal
0
0: OFF, 1: ON (up to frequency)
OL signal
1
0: OFF, 1: ON (overload alarm)
IPF signal
2
0: OFF, 1: ON (an instantaneous power failure or undervoltage occurs)
Terminal RUN function
3
Inverter running
The function assigned to the terminal
RUN is activated.
—
4
Not used (0 is set)
Alarm 1
5
0: REF1 command execution normal, 1: REF1 command execution error (outside
setting range)
Alarm 2
6
0: REF2 command execution normal, 1: REF2 command execution error (outside
setting range)
Alarm 3
7
0: REF3 command execution normal, 1: REF3 command execution error (outside
setting range)
Alarm 4
8
0: REF4 command execution normal, 1: REF4 command execution error (outside
setting range)
Alarm 5
9
0: REF5 command execution normal, 1: REF5 command execution error (outside
setting range)
Alarm 6
10
0: REF6 command execution normal, 1: REF6 command execution error (outside
setting range)
Alarm 7
11
0: REF7 command execution normal, 1: REF7 command execution error (outside
setting range)
Command count
12 to 15
Echo back of the command request.
Name
Bit
Definition