Main circuit terminals
37
2
2.5.3
Terminal layout of the main circuit terminals,
wiring of power supply and the motor
NOTE
• Make sure the power cables are connected to the R/L1, S/L2, and T/L3 of the converter unit. (Phase need not be matched.)
Never connect the power cable to the U, V, and W of the inverter. Doing so will damage the inverter.
• Connect the motor to the U, V, and W of the inverter. (The phases must be matched.)
• When wiring the main circuit conductor, tighten a nut from the right side of the conductor.
When wiring two wires, place wires on both sides of the conductor. (Refer to the diagram below.)
For wiring, use bolts (nuts) provided with the inverter.
• When wiring the main circuit conductor (R/L1, S/L2, T/L3) of the converter unit (FR-CC2), use the bolts (nuts) for main circuit
wiring, which are provided on the front side of the conductor.
FR-CC2-H315K to FR-CC2-H500K
FR-A842-07700(315K) to FR-A842-12120(500K)
Jumper
Charge lamp
P/+
N/-
To inverter
R1/L11 S1/L21
R/L1
S/L2
T/L3
Power supply
Charge lamp
Jumper
M
Motor
N/-
P/+
To converter
unit
R1/L11 S1/L21
FR-CC2-H315K, H355K
FR-CC2-H400K to H500K
Connect the cables here.
Connect the cables here.