Control circuit
43
2
∗1
Terminal FM is provided in the FM-type inverter.
∗2
Terminal CA is provided in the CA-type inverter.
Open collector
RUN
Inverter running
Switched to LOW when the inverter output frequency is equal to or
higher than the starting frequency (initial value 0.5 Hz). Switched to
HIGH during stop or DC injection brake operation.
Permissible load 24
VDC (maximum 27
VDC) 0.1 A
(The voltage drop is
2.8 V at maximum
while the signal is
ON.)
LOW is when the
open collector output
transistor is ON
(conducted).
HIGH is when the
transistor is OFF (not
conducted).
SU
Up to frequency
Switched to LOW when the output frequency
is within the set frequency range
±
10% (initial
value). Switched to HIGH during acceleration/
deceleration and at a stop.
Fault code (4 bits)
output.
OL
Overload alarm
Switched to LOW when stall prevention is
activated by the stall prevention function.
Switched to HIGH when stall prevention is
canceled.
IPF
Open collector output
No function is assigned in the initial setting.
The function can be assigned setting
Pr.192
.
FU
Frequency detection
Switched to LOW when the inverter output
frequency is equal to or higher than the preset
detection frequency, and to HIGH when it is
less than the preset detection frequency.
SE
Open collector output
common
Common terminal for terminals RUN, SU, OL, IPF, FU
———
Pul
se FM
For meter
Outputs a selected monitored item (such as
output frequency) among several monitored
items. The signal is not output during an
inverter reset.
The output signal is proportional to the
magnitude of the corresponding monitoring
item.
Use
Pr.55
,
Pr.56
, and
Pr.866
to set full scales
for the monitored output frequency, output
current, and torque.
Output item:
Output frequency (initial
setting)
Permissible load
current 2 mA
For full scale
1440 pulses/s
NPN open
collector output
This terminal can be
used for open collector
outputs by setting
Pr.291
.
Maximum output
pulse: 50k pulses/s
Permissible load
current: 80 mA
Analog
AM
Analog voltage output
Output item:
Output frequency (initial
setting)
Output signal 0 to 10
VDC, Permissible
load current 1 mA
(load impedance 10
k
Ω
or more)
resolution 8 bits
CA
Analog current output
Load impedance 200
Ω
to 450
Ω
Output signal 0 to 20
mADC
Ty
p
e Terminal
Symbol
Terminal name
Terminal function description
Rated
specification