Measurement of main circuit voltages, currents and powers
106
PRECAUTIONS FOR MAINTENANCE AND INSPECTION
Measuring points and instruments
Item
Measuring point
Measuring instrument
Remarks (reference measured value)
Converter unit (F
R
-CC
2)
Power supply
voltage
V1
Across R/L1 and S/L2,
S/L2 and T/L3,
T/L3 and R/L1
Digital power meter (for inverter)
Commercial power supply
Within permissible AC voltage fluctuation (Refer
to
Power supply side
current
I1
R/L1, S/L2, T/L3 line
current
Power supply side
power
P1
R/L1, S/L2, T/L3 and
Across R/L1 and S/L2,
S/L2 and T/L3,
T/L3 and R/L1
P1 = W11 + W12 + W13 (3-wattmeter method)
Power supply side
power factor
Pf1
Calculate after measuring power supply voltage, power supply side current and power supply side power.
Converter output
Across P/+ and N/-
Digital multimeter or other tester
Inverter LED is lit. 1.35
×
V1
Operation enable
signal
External thermal
relay signal
Reset signal
Across RDI, OH,
RES(+) and SD (for
sink logic)
Digital multimeter or other tester,
or moving-coil type instrument
(internal resistance 50 kΩ or more)
When open
20 to 30 VDC
ON voltage: 1 V or less
"SD" is
common
Alarm signal
Across A1 and C1
Across B1 and C1
Digital multimeter or other tester
Continuity check
[Normal]
[Fault]
Across A1 and C1 Discontinuity
Continuity
Across B1 and C1 Continuity
Discontinuity
Inverte
r
Output side
voltage
V2
Across U and V, V and
W, and W and U
Digital power meter (designed for
inverter)
Difference between the phases is within 1% of
the maximum output voltage.
Output side
current
I2
U, V and W line
currents
Digital power meter (designed for
inverter)
Difference between the phases is 10% or lower
of the inverter rated current.
Output side power
P2
U, V, W and
across U and V, V and
W
P2 = W21 + W22
2-wattmeter method (or 3-wattmeter method)
Output side power
factor
Pf2
Calculate in similar manner to power supply side power factor.
Frequency setting
signal
Across 2, 4(+) and 5
Digital multimeter or other tester,
or moving-coil type instrument
(internal resistance 50 k
Ω
or more)
0 to 10 VDC, 4 to 20 mA
"5" is .
common
Across 1(+) and 5
0 to
±
5 VDC and 0 to
±
10 VDC
Frequency setting
power supply
Across 10(+) and 5
5.2 VDC
Across 10E(+) and 5
10 VDC
Frequency meter
signal
Across AM(+) and 5
Approximately 10 VDC at maximum
frequency
(without frequency meter)
Across CA(+) and 5
Approximately 20 mADC at
maximum frequency
Across FM(+) and SD
Approximately 5 VDC at maximum
frequency
(without frequency meter)
Pulse width T1: Adjust with
C0
(Pr.900)
.
Pulse cycle T2: Set with
Pr.55
.
(frequency monitor only)
"SD" is
common
Start signal
Select signal
Reset signal
Output stop signal
Across STF, STR, RH,
RM, RL, JOG, RT, AU,
STOP, CS, RES,
MRS(+) and SD (for
sink logic)
When open
20 to 30 VDC
ON voltage: 1 V or less
Fault signal
Across A1 and C1
Across B1 and C1
Digital multimeter or other tester
Continuity check
[Normal]
[Fault]
Across A1 and C1 Discontinuity
Continuity
Across B1 and C1 Continuity
Discontinuity
Pf
1
P
1
3V
1
I
×
1
------------------------ 100
×
=
%
Pf
2
P
2
3V
2
I
2
×
------------------------ 100
×
=
%
8VDC
T1