GOT-F900 SERIES (CONNECTION)
Connection of Printer 21
21-4
21.4
Cautions on Use of Printer
When using the GOT-F900 connected to the printer, observe the following cautions on use.
21.4.1
Caution on printer setting
When "PRINTER" is set to "USE" in "SERIAL PORT(RS-232C)" in the GOT-F900, the RS-232C port of
the GOT-F900 is occupied for the printer.
In this status, even if a personal computer is connected and screen data transfer or sequence program
(two-port interface function) transfer/monitoring is executed, the GOT-F900 does not automatically
change to the transfer screen. (And a communication error occurs in the application software installed in
the personal computer.)
1) Avoidance Method
When "PRINTER" is set to "USE", communication error can be avoided by executing an either
operation.
2) Priority of the RS-232C Port Functions
From the functions having the highest priority, the system checks whether the setting is provided. If a
certain function is set, functions having lower priority are disabled.
For example, when the PLC connection destination is set to RS-232C or when the bar code reader is
set valid, functions having lower priority (such as screen data transfer and sequence program
transfer/monitoring) are disabled.
*1 This function is valid only in CPU direct connection in the FX/A/QnA/Q Series. (This function is valid
also in serial communication connection in the QnA/Q Series.)
When all communications should be valid, set "PRINTER" to "DON'T USE".
However, when the alarm history should be printed in real time at occurrence of alarms, "PRINTER"
should be set to "USE".
21.4.2
Concurrent use of microcomputer and printer
When the microcomputer and the printer are used at the same time, the transmission specifications
(such as the communication speed, the parity and the data length) are shared.
Accordingly, the transmission specifications should be equivalent between the microcomputer and the
printer.
Screen data transfer
Read and display the "SELECT MODE" screen, then select "OTHER
MODE"-"DATA TRANSFER".
Sequence program transfer/monitoring Set "PRINTER" to "DON'T USE", turn off the power, then turn it on again.
Priority
RS-232C function
1
Connected equipment (PLC, general-purpose equipment)
2
Bar code reader
3
Printer
4
Two-port interface function
*1
5
Screen data transfer mode
Exchange the connection.
Printer
Personal computer
Communication
error
Содержание F920GOT-BBD-K-E
Страница 4: ...GOT F900 SERIES CONNECTION ii ...
Страница 6: ...GOT F900 SERIES CONNECTION iv ...
Страница 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Страница 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Страница 102: ...GOT F900 SERIES CONNECTION Installation and Wiring of F920GOT K F930GOT K F940 W GOT 4 4 32 MEMO ...
Страница 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Страница 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Страница 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Страница 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Страница 338: ...GOT F900 SERIES CONNECTION Connection of FX Series Positioning Unit FX 2N 10 20GM 12 12 16 MEMO ...
Страница 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Страница 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Страница 460: ...GOT F900 SERIES CONNECTION Connection of FLEX PC N Series PLC Manufactured by Fuji Electric 16 16 18 MEMO ...
Страница 478: ...GOT F900 SERIES CONNECTION Connection of Machine Controller CP9200SH PLC Manufactured by Yaskawa Electric 17 17 18 MEMO ...
Страница 500: ...GOT F900 SERIES CONNECTION Connection of FP Series PLC Manufactured by Matsushita Electric Works 18 18 22 MEMO ...
Страница 522: ...GOT F900 SERIES CONNECTION Connection of SLC500 MicroLogix Series PLC Manufactured by Allen Bradley 19 19 22 MEMO ...
Страница 546: ...GOT F900 SERIES CONNECTION Connection of SIMATIC S7 200 300 400 Series PLC Manufactured by Siemens AG 20 20 24 MEMO ...
Страница 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Страница 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Страница 591: ......