GOT-F900 SERIES (CONNECTION)
Connection of Two or More GOT Units 7
7-24
7.8
Troubleshooting
For reference, this section summarizes frequently asked questions about connection of two or more
GOT units.
1) GOT-F900
Classification
Contents of trouble
Check points and countermeasures
GOT-F900
"COMMUNICATION ERROR
OCCURS" is displayed when a screen
changeover or numeric data input is
performed on the GOT-F900 screen.
Nothing is displayed on the screen of some GOT units.
• Causes
Communication is disabled because the power of the
connected equipment is turned off.
• Countermeasures
Turn on the power.
Some of the connected GOT units do not display.
• Causes
The power has been turned on before or at the same
instant as connected equipment was turned on.
• Countermeasures
Turn on the connected equipment first.
Set the opening screen display period longer.
The first GOT unit (closest from connected equipment)
displays an user screen, but the second and later
(further) GOT units do not.
• Causes
The second and later GOT units has not been ready to
communicate before display of the opening screen of
the first GOT finished.
The power of the second and later GOT is turned off.
• Countermeasures
Set the opening screen display period longer.
Turn on the second and later GOT.
GT Designer
DU/WIN
When the screen data is transferred by
the screen creation software, "No
response from terminal", etc. is
displayed.
The RS-232C port of the GOT-F900 is allocated to
another connected equipment (bar code reader or
printer).
• Causes
1)"RS-232C" is specified for PLC connection.
2)The bar code reader is set valid.
3)The printer is set valid.
Confirm the settings above in the screen creation
software.
• Countermeasures
Select by hand the data transfer mode in the GOT-F900.
Start up the system screen, display the "SELECT
MODE" screen, select "OTHER MODE" - "DATA
TRANSFER" on the menu, then transfer the screen data.
GOT-F900
When the screen data is transferred by
the screen creation software, the
"DATA TRANSFER" screen does not
appear in the GOT-F900.
Содержание F920GOT-BBD-K-E
Страница 4: ...GOT F900 SERIES CONNECTION ii ...
Страница 6: ...GOT F900 SERIES CONNECTION iv ...
Страница 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Страница 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Страница 102: ...GOT F900 SERIES CONNECTION Installation and Wiring of F920GOT K F930GOT K F940 W GOT 4 4 32 MEMO ...
Страница 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Страница 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Страница 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Страница 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Страница 338: ...GOT F900 SERIES CONNECTION Connection of FX Series Positioning Unit FX 2N 10 20GM 12 12 16 MEMO ...
Страница 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Страница 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Страница 460: ...GOT F900 SERIES CONNECTION Connection of FLEX PC N Series PLC Manufactured by Fuji Electric 16 16 18 MEMO ...
Страница 478: ...GOT F900 SERIES CONNECTION Connection of Machine Controller CP9200SH PLC Manufactured by Yaskawa Electric 17 17 18 MEMO ...
Страница 500: ...GOT F900 SERIES CONNECTION Connection of FP Series PLC Manufactured by Matsushita Electric Works 18 18 22 MEMO ...
Страница 522: ...GOT F900 SERIES CONNECTION Connection of SLC500 MicroLogix Series PLC Manufactured by Allen Bradley 19 19 22 MEMO ...
Страница 546: ...GOT F900 SERIES CONNECTION Connection of SIMATIC S7 200 300 400 Series PLC Manufactured by Siemens AG 20 20 24 MEMO ...
Страница 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Страница 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Страница 591: ......