GOT-F900 SERIES (CONNECTION)
Connection of MELSEC-F FX Series PLC 8
8-24
"CAN NOT WRITE."
is displayed on the
GOT-F900 screen.
Programs and device set values of the FX Series PLC
cannot be changed.
• Causes
The write-protect switch of the memory cassette is set
to ON. PLC Password protection is on.
• Countermeasures
Set the write-protect switch to OFF.
Enter the keywords by "SELECT MODE"-"OTHER
MODE"-"ENTRY CODE".
1.10 or
later
6.10 or
later
4.10 or
later
From
first
product
"CAN NOT USE THE
FUNCTION WHILE
PROTECTED." is
displayed on the
GOT-F900 screen.
Programs and device set values of the FX Series PLC
cannot be changed.
• Causes
PLC Password protection is on.
• Countermeasures
Enter the keywords by "SELECT MODE"-"OTHER
MODE"-"ENTRY CODE".
From
first
product
From
first
product
From
first
product
From
first
product
"PLC IS RUNNING."
is displayed on the
GOT-F900 screen.
An attempt was made to edit the set value of the timer
or counter, or the current value of the file registers of
the FX Series PLC.
• Cause
Such changes are disabled while the FX Series PLC
equipped with the EEPROM memory cassette is
running. (Data saved in the built-in EEPROM can be
changed.)
Such changes are also disabled when the PLC is
equipped with EPROM memory cassette.
• Countermeasures
Run the FX Series PLC using the built-in memory.
Specify the set value of the timer (T) and the counter
(C) indirectly through the data register (D).
From
first
product
From
first
product
From
first
product
From
first
product
Contents of trouble
Check points and countermeasures
OS version
F940W
F940
F930
F920
Содержание F920GOT-BBD-K-E
Страница 4: ...GOT F900 SERIES CONNECTION ii ...
Страница 6: ...GOT F900 SERIES CONNECTION iv ...
Страница 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Страница 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Страница 102: ...GOT F900 SERIES CONNECTION Installation and Wiring of F920GOT K F930GOT K F940 W GOT 4 4 32 MEMO ...
Страница 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Страница 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Страница 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Страница 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Страница 338: ...GOT F900 SERIES CONNECTION Connection of FX Series Positioning Unit FX 2N 10 20GM 12 12 16 MEMO ...
Страница 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Страница 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Страница 460: ...GOT F900 SERIES CONNECTION Connection of FLEX PC N Series PLC Manufactured by Fuji Electric 16 16 18 MEMO ...
Страница 478: ...GOT F900 SERIES CONNECTION Connection of Machine Controller CP9200SH PLC Manufactured by Yaskawa Electric 17 17 18 MEMO ...
Страница 500: ...GOT F900 SERIES CONNECTION Connection of FP Series PLC Manufactured by Matsushita Electric Works 18 18 22 MEMO ...
Страница 522: ...GOT F900 SERIES CONNECTION Connection of SLC500 MicroLogix Series PLC Manufactured by Allen Bradley 19 19 22 MEMO ...
Страница 546: ...GOT F900 SERIES CONNECTION Connection of SIMATIC S7 200 300 400 Series PLC Manufactured by Siemens AG 20 20 24 MEMO ...
Страница 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Страница 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Страница 591: ......