GOT-F900 SERIES (CONNECTION)
Connection of MELSEC-QnA Series PLC 10
10-12
10.4
Caution on Use of MELSEC-QnA Series PLC
When using the GOT-F900 connected to the QnA Series PLC, observe the following caution on use.
10.4.1
Caution when the GOT is connected to the serial communication unit
1) Simultaneous use of 2 ports
When the GOT is connected, the CH1 and the CH2 of the serial communication unit cannot be used
at the same time.
Accordingly, have in mind that connecting both of GOT unit and peripheral equipment for the GPP
function or two GOT units to one serial communication unit is not allowed.
However, a GOT unit or a personal computer can be connected to the RS-422 port of the QnACPU
while the computer link unit has one GOT unit.
2) Compatible OS version of QnACPU
When connecting a GOT unit to a serial communication unit or A Series computer link unit, the OS
version of QnACPU needs to be later than the version indicated below. (Programming port of CPU is
compatible with any version.)
10.4.2
Caution when the GOT is connected to the computer link for the A Series PLC
•
When connecting the GOT-F900 to the A computer link attached to the QnACPU, select A SERIES
for PLC TYPE.
•
For setting method for the A computer link or screen creation software, refer to Chapter 9.
QnACPU
H/W version
S/W version
Production date
Q2A,Q3A,Q4A
D
A
Earlier than March, 1997
Q2AS
A
L
Earlier than March, 1997
GOT-F900
GOT-F900
GOT-F900
CPU
Serial communication unit
Personal computer
GOT-F900
Personal computer
CPU
Serial communication unit
Either
one
Содержание F920GOT-BBD-K-E
Страница 4: ...GOT F900 SERIES CONNECTION ii ...
Страница 6: ...GOT F900 SERIES CONNECTION iv ...
Страница 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Страница 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Страница 102: ...GOT F900 SERIES CONNECTION Installation and Wiring of F920GOT K F930GOT K F940 W GOT 4 4 32 MEMO ...
Страница 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Страница 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Страница 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Страница 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Страница 338: ...GOT F900 SERIES CONNECTION Connection of FX Series Positioning Unit FX 2N 10 20GM 12 12 16 MEMO ...
Страница 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Страница 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Страница 460: ...GOT F900 SERIES CONNECTION Connection of FLEX PC N Series PLC Manufactured by Fuji Electric 16 16 18 MEMO ...
Страница 478: ...GOT F900 SERIES CONNECTION Connection of Machine Controller CP9200SH PLC Manufactured by Yaskawa Electric 17 17 18 MEMO ...
Страница 500: ...GOT F900 SERIES CONNECTION Connection of FP Series PLC Manufactured by Matsushita Electric Works 18 18 22 MEMO ...
Страница 522: ...GOT F900 SERIES CONNECTION Connection of SLC500 MicroLogix Series PLC Manufactured by Allen Bradley 19 19 22 MEMO ...
Страница 546: ...GOT F900 SERIES CONNECTION Connection of SIMATIC S7 200 300 400 Series PLC Manufactured by Siemens AG 20 20 24 MEMO ...
Страница 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Страница 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Страница 591: ......