: Configurable
×
: No settings required
-
: No setting items
Item
Details
Parent terminal
Child
terminal
Without
child
terminals
With
child
terminals
Unit configuration
Register the model and name of the terminal units that constitute the system.
Model name
Only when an extension unit is used, set this item.
Select the extension unit model from the pull-down menu.
・
Blank (no extension unit)
・
EMU4-A2
・
EMU4-AX4
・
EMU4-VA2
・
EMU4-PX4
When the extension unit, EMU4-A2, is selected, EMU4-
VA2 must be set to an extension unit field above EMU4-A2.
⭘
⭘
-
Unit name
Enter a name of the unit.
A maximum of 30 characters are allowed in the input field.
○
⭘
○
Network information
for Ethernet
Register the settings for the network connecting to a computer.
This setting is for the parent terminal only.
IP address
Enter an IP address.
Setting range: 1.0.0.0 to 126.255.255.255
128.0.0.0 to 191.255.255.255
192.0.0.0 to 223.255.255.255
*0.0.0.0 and xxx.xxx.xxx.255 (xxx is an arbitrary number
available.) are not available.
Default: 192.168.3.11
○
○
×
Subnet mask
Enter a subnet mask.
When it is expressed in binary numbers, set the numbers
fulfilling the following conditions:
・
The most significant bit is 1.
・
Do not enter 0 between 1 and 1.
・
The least significant bit is 0.
・
255.255.255.254 is not available.
Default: 255.255.255.0
○
○
×
Default gateway
Enter a default gateway.
*0.0.0.0 and xxx.xxx.xxx.255 (xxx is an arbitrary number
available.) are not available.
Default: Blank
○
○
×
Network information
for MODBUS RTU
Register the settings for MODBUS RTU communication.
For the parent terminal without any child terminal in the system, it is set to communicate with
the superior monitoring systems.
For any child terminals, it is set to communicate with the parent terminal.
Slave address
Set the Slave address.
The same address as other terminals cannot be set
repeatedly.
Setting range: 1 to 247 (Default: 1)
*For the parent terminal without any child terminal in the
system, set a different address from other terminals in
the same MODBUS RTU communication network.
○
-
○
Baud rate *1
Select a baud rate from the pull-down menu.
・
2400
・
19200 (Default)
・
4800
・
38400
・
9600
○
-
-
Parity
Select a parity bit from the pull-down menu.
・
NONE
・
ODD
・
EVEN (Default)
○
-
-
Stop bit
Select a stop bit from the pull-down menu.
・
1 (Default)
・
2
○
-
-
*1: For the parent terminal with some child terminals in the system or for any child terminals, the baud rate is set to 19200.
(2) Click the
Register
button to save the settings.
Содержание EMU4-CNT-MB
Страница 91: ...90 3 Click the Register button to save the settings ...
Страница 131: ...130 CC Link Communication Unit for Energy Measuring Unit EMU4 CM C ...
Страница 133: ...132 Small Type Display Unit for Energy Measuring Unit EMU4 D65 ...
Страница 134: ...133 15 External Dimensions of the Control Unit Note The unit of numbers mm Model EMU4 CNT MB Model EMU4 BT ...