7.9. Supplementary information
Back-up operation of boiler
Heating operation is backed up by boiler.
For more details, refer to the installation manual of PAC-TH012HT-E.
<Installation & System set up>
1. Set DIP-SW 1-1 (FTC) to ON "With boiler" and SW2-6 (FTC) to ON “With Mixing tank”.
2. Install the thermistors THWB1
*1
on the boiler circuit.
3. Connect the output wire (OUT10: Boiler operation) to the input (room thermostat input) on the boiler.
*2
4. Install one of the following room temperature thermostats.
*3
Wireless remote controller (option)
Room temp. thermostat (local supply)
Main remote controller (remote position)
*1 The boiler temperature thermistor is an optional part.
*2 OUT10 has no voltage across it.
*3 Boiler heating is controlled on/off by the Room temp. thermostat.
<Main remote controller settings>
1. Go to Service menu > Heat source setting and choose “Boiler” or “Hybrid”.
*4
2. Go to Service menu > Operation settings > Boiler settings to make detailed settings for “Hybrid” above .
*4 The “Hybrid” automatically switches heat sources between Heat pump (and Electric heater) and boiler.
Product fiche of temperature control
(a) Supplier's name: MITSUBISHI ELECTRIC CORPORATION
(b) Supplier's model identifier: PAR-WT50R-E and PAR-WR51R-E
(c) The class of the temperature control:
(d) The contribution of the temperature control to seasonal space heating energy efficiency: 4%
B-267