1.Installation
The unit can be installed in both horizontal as well as vertical pipelines.
The flow sensor is only suitable for use in fully filled piping.
<Note>
▪
The length of the inlet section should be at least 190 mm and the length of the outlet section should be at least 95 mm.
2. Electrical work
Model
Signal name
Terminal block
Connector
Item
PAC-IF07*B-E
INA1
TBI.4 1-3
CN1A
Flow sensor
PAC-IF033****-E
─
─
CN1A
Flow sensor
3. Dip switch setting
Model
Dip switch
Function
OFF
ON
PAC-IF07*B-E
SW2-8
Flow sensor
WITHOUT Flow sensor WITH Flow sensor
PAC-IF033****-E
SW4-2
Flow sensor
WITHOUT Flow sensor WITH Flow sensor
4. Specifications
Ambient temperature range
0 to 70 °C
Fluid temperature range
5 to 90 °C
1
2
3
4
BK
WH
BU
BN
SENSOR
5 V DC
Vout
MICRO
PROCESSOR
FTC CONTROLLER BOARD
4
-
3
: 5 V (DC)
2
-
3
: Output Vout (DC)
WITHOUT SIGNAL
CN1A WH
Flow signal
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
0
20
40
60
80
100
Flow [L/min]
Flow output signal
[V]
0.35V
・
Possibility of bubble formation
・
Possibility of drain
-
off (measuring pipe partly
filled)
・
Possibility of bubble formation
・
Possibility of drain
-
off
Min. 190 mm
Min. 95 mm
Optional parts
D-56
FLOW SENSOR
9
Optional parts