Engineers Forms
Should settings be changed from default, please enter and record new setting in ‘Field Setting’ column. This will ease resetting in
the future should the system use change or the circuit board need to be replaced.
Commissioning/Field settings record sheet
Main remote controller screen
Parameters
Default
setting
Field
setting Notes
Main
Zone1 heating room temp.
10°C to 30°C
20°C
Zone2 heating room temp. *8 10°C to 30°C
20°C
Zone1 heating flow temp.
20°C to 60°C
45°C
Zone2 heating flow temp. *1
20°C to 60°C
35°C
Zone1 heating compensation
curve
−9°C to +9°C
0°C
Zone2 heating compensation
curve *1
−9°C to +9°C
0°C
Holiday mode
Active/Non active/Set time
—
Option
Forced DHW operation
On/Off
—
DHW
On/Off/Timer
On
Heating
On/Off/Timer
On
Energy monitor
Consumed electrical energy/Deliv-
ered energy
—
Setting
DHW
Operation mode
Normal/Eco
Eco
DHW max. temp.
40°C to 60°C
50°C
DHW ma. temp. drop
5°C to 30°C
10°C
DHW max. operation time
30 to 120 min
60 min
DHW mode restriction
30 to 120 min
30 min
DHW recharge
Standard/Large
Standard
Legionella prevention
Active
Yes/No
Yes
Hot water temp.
60°C to 70°C
65°C
Frequency
1 to 30 days
15 days
Start time
00:00 to 23:00
03:00
Max. operation time
1 to 5 hours
3 hours
Duration of maximum temp.
1 to 120 min
30 min
Heating
Zone1 operation mode
Heating room temp./ Heating flow
temp./ Heating compensation curve
Room temp.
Zone2 operation mode *1
Heating room temp./ Heating flow
temp./ Heating compensation curve
Compensa-
tion curve
Compensa-
tion curve
Hi flow temp.
set point
Zone1 outdoor ambient temp.
−30°C to +33°C
−15°C
Zone1 flow temp.
20°C to 60°C
50°C
Zone2 outdoor ambient temp.
*1
−30°C to +33°C
−15°C
Zone2 flow temp. *1
20°C to 60°C
40°C
Lo flow temp.
set point
Zone1 outdoor ambient temp.
−28°C to +35°C
35°C
Zone1 flow temp.
20°C to 60°C
25°C
Zone2 outdoor ambient temp.
*1
−28°C to +35°C
35°C
Zone2 flow temp.*1
20°C to 60°C
25°C
Adjust
Zone1 outdoor ambient temp.
−29°C to +34°C
—
Zone1 flow temp.
20°C to 60°C
—
Zone2 outdoor ambient temp.
*1
−29°C to +34°C
—
Zone2 flow temp. *1
20°C to 60°C
—
Holiday
DHW
Active/Non active
Non active
Heating
Active/Non active
Active
Zone1 heating room temp.
10°C to 30°C
15°C
Zone2 heating room temp. *8 10°C to 30°C
15°C
Zone1 heating flow temp.
20°C to 60°C
35°C
Zone2 heating flow temp. *1
20°C to 60°C
25°C
Initial settings
Language
EN/FR/DE/SV/ES/IT/DA/NL/FI/NO/
PT/BG/PL/CZ/RU/TR/SL
EN
°C/°F
°C/°F
°C
Summer time
On/Off
Off
Temp. display
Room/DHW tank/Room&DHW tank /
Off
Off
Time display
hh:mm/hh:mm AM/AM hh:mm
hh:mm
Room sensor settings for
Zone1
TH1/Main RC/Room RC1-8/“Time/
Zone”
TH1
Room sensor settings for
Zone2 *1
TH1/Main RC/Room RC1-8/“Time/
Zone”
TH1
Room RC zone select *1
Zone1/Zone2
Zone1
B-264
Water to Water Heat Pump (WTW)
7
Cylinder
unit/
Hydrobox/GSHP/WTW