<Room sensor settings>
For room sensor settings it is important to choose the correct
room sensor depending on the heating mode the system will
operate in.
1. From the Initial settings menu select Room sensor settings.
Time/Zone schedule setting screen
2. When 2-zone temperature control is active and wireless re-
mote controllers are available, from Room RC zone select
screen, select zone No. to assign to each remote controller.
3. From Sensor setting screen, select a room sensor to be
used for monitoring the room temperature from Zone1 and
Zone2 separately.
Control option
("Remote Control-
ler Options"
Corresponding initial settings room sensor
Zone1
Zone2
A
Room RC1-8 (one each
for Zone1 and Zone2)
*
B
TH1
*
C
Main remote controller
*
D
*
*
* Not specified ( if a field-supplied room thermostat is used)
Room RC1-8 (one each for Zone1 and Zone2) (if a wireless remote controller
is used as a room thermostat)
4. From Sensor setting screen, select Time/Zone to make it
possible to use different room sensors according to the time
schedule set in the Select Time/Zone menu. The room sen-
sors can be switched up to 4 times within 24 hours.
B-240
Water to Water Heat Pump (WTW)
7
Cylinder
unit/
Hydrobox/GSHP/WTW