FIELD WIRING
7
Breaker abbreviation
Meaning
ECB
Earth leakage circuit breaker for booster heater
TB1
Terminal block 1
TB2
Terminal block 2
Description
Power supply
Capacity
Breaker
Wiring
Booster heater (Primary circuit)
230V N~ 50 Hz
2 kW
16 A *2 *3
3 × 2.5 mm²
Tightening torque
TB1
2.0 ~
2.5 Nm
TB2
2.0 ~
2.5 Nm
ECB
1.3 ~
1.7 Nm
earth
2.0 ~
2.5 Nm
*2. A breaker with at least 3.0 mm contact separation in each pole shall be provided.
The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*3. Use a breaker with an over-current protection function.
*4. Max. 15 m
*5. The values given in the table above are not always measured against the ground value.
Cylinder unit power supply
Cylinder unit input capacity
Main switch (Breaker)
Wiring
Wiring No. × size (mm²)
Cylinder unit power supply (including earth cable)
Cylinder unit - Outdoor unit (including earth cable)
Circuit rating
Cylinder unit L - N
Cylinder unit - Outdoor unit S1 - S2
Cylinder unit - Outdoor unit S2 - S3
*2
*5
*5
*5
*4
~/N 230 V 50 Hz
16 A
3 × Min. 2.5
4 × Min. 2.5
230 V AC
230 V AC
24 V DC
Note: 1. Wiring size MUST comply with the applicable local and national codes.
2. Cylinder unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable. (Design 60245 IEC 57)
Cylinder unit power supply cables shall not be lighter than polychloroprene sheathed flexible cable. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
4. Please keep enough output capacity of power supply for each heater. The lack of the power supply capacity may possibly cause chattering.
Outdoor unit powered via cylinder unit
<1 phase>
TB1
L
N
TB2
S1
S2
S3
Earth
leakage
circuit
breaker
*1
Cylinder unit
Outdoor unit
*1. Current sensitivity 10 mA, operating time 0.1 s.
If the installed earth leakage circuit breaker does not have an over-current protection function, install a breaker with that function along the same power line.
Power
supply
~/N
230 V
50 Hz
Wiring
circuit
breaker
or
Isolating
switch
ECB
L
N
Power
supply
~/N
230 V
50 Hz
Wiring
circuit
breaker
or
Isolating
switch
S1
S2
S3
For
booster
heater
(Primary circuit)
Electrical connections 1 phase
Isolating switch