21
Types of units in error and the units that will stop when errors are reset
Types of units in error and the units that will stop
Units in error
Units that will stop
EB-50
None
Outdoor unit
All indoor units that are connected to the outdoor unit in error
Indoor unit
Indoor unit in error and all other indoor units in the same group
ME (MA) remote controller
All indoor units that are connected to the remote controller in error
System controller
All indoor units that are connected to the system controller in error
Advanced HVAC CONTROLLER
None
Interlocked LOSSNAY unit
Indoor units with which the LOSSNAY unit in error is interlocked
Air To Water (PWFY) unit
Air To Water (PWFY) unit in error and all other Air To Water (PWFY) units in the same
group
DIDO controller (PAC-YG66DCA)
None
Example of units in error and the units that will stop
Indoor unit
[2]
AHC
[202]
Indoor unit
[1]
Indoor unit
[3]
Indoor unit
[4]
Indoor unit
[5]
Air To Water (PWFY) unit
[7]
DIDO controller (PAC-YG66DCA)
[8]
Outdoor unit
[51]
Outdoor unit
[53]
Outdoor unit
[55]
Outdoor unit
[57]
EB-50
[0]
ME remote controller
[101]
System controller
[201]
LOSSNAY unit
[6]
Group 1
Group 2
Units in error
Units that will stop
EB-50 [0]
None
Outdoor unit [51]
Indoor unit [1], Indoor unit [2]
Outdoor unit [53]
Indoor unit [3], Indoor unit [4], Indoor unit [5]
Outdoor unit [57]
Air To Water (PWFY) unit [7]
Indoor unit [1]
Indoor unit [1], Indoor unit [2]
Indoor unit [3]
Indoor unit [3]
Indoor unit [5]
Indoor unit [4], Indoor unit [5]
LOSSNAY unit [6]
Indoor unit [5]
Air To Water (PWFY) unit [7]
Air To Water (PWFY) unit [7]
ME remote controller [101]
Indoor unit [1]
System controller [201]
Indoor unit [1], Indoor unit [3], Indoor unit [4]
Advanced HVAC CONTROLLER [202]
None
DIDO controller (PAC-YG66DCA) [8]
None