19
4-2. Measurement List
This section explains how to check the measurement data of the temperature sensors, humidity sensors, and
metering devices.
Click [Monitor/Operation] in the menu bar, and then click [Measurement List] to access the Measurement List
screen.
Note: An AI controller (PAC-YG63MCA), a commercially available temperature sensor, and a humidity sensor are
required to measure the temperature and humidity.
Note: A PI controller (PAC-YG60MCA) and a commercially available metering devices are required to measure the
electric, water, heat, and gas consumptions.
Measurement item
Update
Click to show the most
recent measurement data.
Measurement value
Number of units whose
filter sign is turned on
Number of units in error
Item
Description
Update
Click to show the most recent measurement data.
When [Auto] is selected, the measurement data is updated automatically every minute.
Measurement value
The current measurement values will appear.
Note: The following icons are used to indicate the measuring devices. Icons will appear in orange
when the measurement value reaches the upper or lower alarm threshold value that has
been set on the Measurement screen, accessible via the Web Browser for Initial Settings.
Normal
Upper/lower alarm
threshold value is
reached.
Communication
error
Temperature sensor
*1
Humidity sensor
*1
Metering device
*2
*1 When there is a communication error, the measurement value of the temperature or humidity
sensor will be "--."
*2 When there is a communication error, the measurement value of the metering device will be
the measured value immediately before the error detection.
Number of units whose filter
sign is turned on
*1
The number of units under the control of EB-50 whose filter sign is currently turned on will
appear. Clicking " " will bring up the Filter Sign List screen. (See section 4-4.)
Note: This item will not appear if the [Filter Sign Display] is set to [OFF] on the Basic System
settings screen, accessible via the Web Browser for Initial Settings.
Number of units in error
*1
The number of units under the control of EB-50 that are currently in error will appear.
Clicking " " will bring up the Malfunction List screen. (See section 4-3.)
*1 The item will not appear if the number of units is "0."