background image

-

 

 

-

 '11 • SRK-T-118

Necessary tools for the installation work

1

2

3

4

5

6

7

8

9

10

11

12

13

1

1

1

1

1

1

Q’ty

Option parts

Sealing plate

Sleeve

Inclination plate

Putty

Drain hose (extension hose)

Piping cover

(for insulation of connection piping)

Plus  headed  driver

Knife

Saw

Tape  measure

Hammer

Spanner wrench

Torque wrench

Hole core drill (65mm  in diameter)

Wrench key (Hexagon) [4m/m]

Flaring tool set

Gas leak detector

Pipe bender

Gauge for projection adjustment

  Used when flare is made by using

  conventional flare tool

(

)

(                                                  )

14.0 ~ 61.0N·m

(1.4 ~ 6.1kgf·m)

(

Designed specifically

for R410A

)

Piping in the left direction

Piping in the right rear direction

Piping in the left rear direction

Piping in the right direction

INSTALLATION SPACE (INDOOR UNIT)

(FRONT VIEW)

Piping is possible in the rear, left, left rear, left downward, right or downward direction.

Right

Rear

Downward

Left 

rear

Left downward

Left

Wireless remote control

Remote control holder

Wood screws

BEFORE INSTALLATION

    Before installation check that the power supply matches the air conditioner.

SELECTION OF INSTALLATION LOCATION

INSTALLATION OF INDOOR UNIT

Indoor unit

Relation between setting plate and indoor unit

Installing the support of piping

(Install at location that meets the following conditions, after getting approval from the customer)

    Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed.

    A solid place where the unit or the wall will not vibrate.

    A place where there will be enough space for servicing. (Where space mentioned below can be secured)

    Where wiring and the piping work will be easy to conduct.

    The place where receiving part is not exposed to the direct rays of the sun or the strong rays of the street lighting.

    A place where it can be easily drained.

    A place separated at least 1m away from the television or the radio. (To prevent interference to images and sounds.)

    Places where this unit is not affected by the high frequency equipment or electric equipment.

    Avoid installing this unit in place where there is much oil mist.

    Places where there is no electric equipment or household under the installing unit.

Wireless remote control

In case of piping in the right rear direction

    A place where the air conditioner can be received the signal surely during operating the wireless remote control.

    Places where there is no affected by the TV and radio etc.

    Do not place where exposed to direct sunlight or near heat devices such as a stove.

Sufficient care must be taken not to damage 
the panel when connecting pipes.

[Top view]

When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.

• Matters of special notice when piping from left or central/rear of the unit.

Left-hand-side piping

Right-hand-side piping

Installation of Installation board

Drilling of holes and fixture of sleeve (Option parts)

Level position (2 locations)

Mating mark for 
level surface

Fixing on concrete wall

Use of nut anchor

Use of bolt anchor

Shaping of pipings

Taping of the exterior

Pipings

Drain hose

Top

Nut
(M6)

Mounting

board

Mounting

board

Max.10

Thickness of the wall + 1.5cm

5

ø65

Indoor side

Outdoor side

Indoor side

Outdoor side

Installed state

Turn to
tighten

b

b

c

a

Bolt
(M6   12)

5 cm minimum

from the wal

l

10 cm minimum

from the wal

l

Installation board

Sleeve

(sold separately)

6.5 cm minimum from the ceiling

R410A REFRIGERANT USED

WALL TYPE AIR CONDITIONER

INSTALLATION MANUAL FOR INDOOR UNIT

RLA012A012B

     In case of rear piping draw out, cut off the lower 

and the right side portions of the sleeve collar.

Drill a hole with whole core drill.

Hold the bottom of the 
piping and fix direction 
before stretching it and 
shaping it.

Tape only the portion 
that goes through the 
wall.

     Always tape the wiring 

with the piping.

[Drain hose changing procedures]

1. Remove the drain hose

2. Remove the drain cap.

    Remove it with hand or pliers.

     Remove the screw and drain hose, 

making it rotate.

3. Insert the drain cap.

4. Connect the drain hose.

     Insert the drain cap which was removed 

at procedure “2” securely using a 

hexagonal wrench etc.

Note: Be careful that If it is not Inserted 

securely, water leakage may occur.

     Insert the drain hose securely, making 

rotate. And install the screw.

Note: Be careful that If it is not Inserted 

securely, water leakage may 

occur.

Adjustment of the installation board in the horizontal direction is to 

be conducted with four screws in a temporary tightened state.

     Adjust so the board will be 

level by turning the board 
with the standard hole as 
the center.

450

Look for the inside wall structures (Intermediats support or pillar 
and firmly install the unit after level surface has been checked.)

Standard
hole

Piping for Liquid (09 to 18 type) :  ø6.35
Piping for Gas    (09 to 12 type) :  ø9.52

(18 type)          :  ø12.7

CAUTION

Completely seal the hole on 
the wall with putty. Otherwise, 
furniture, or other, may be 
wetted by leaked water or 
dewing.

putty

putty

1

1

1

5

2

2

2

2

1

Q’ty

Standard accessories (Installation kit)

Accessories for indoor unit

Installation board

(Attached to the rear of the indoor unit)

Wireless remote control

Remote control holder

Battery [R03 (AAA, Micro) 1.5V]

Air-cleaning filters

Filter holders

(Attached to the front panel of indoor unit)

Insulation (#486 50 x 100 t3)

Tapping screws 

(for installation board ø4 X 25mm)
Wood screws

(for remote control switch holder ø3.5 X 16mm)

1

2

3

4

5

6

7

8

9

(

)

Designed specifically

for R410A

Space for service

Space for service

Indoor unit

Installation board

Piping hole (ø65)

Drain hose (ø16)

Piping for Liquid

Piping for Gas

Piping hole (ø65)

Space for service

48.9

47

65

139

450

209

106.5

585

106.5

50

100

7.2

7.7

279.1

47

15 Space for service

55

531.8

471.6

403.6

55

Indoor side

Outdoor side

WARNING

• Installation must be carried out by the qualified installer.
 

If you install the system by yourself, it may cause serious trouble such as 
water leaks, electric shocks, fire and personal injury, as a result of a system 
malfunction. Do not carry out the installation and maintenance work except 
the by qualified installer.

• Install the system in full accordance with the installation manual.

  Incorrect installation may cause bursts, personal injury, water leaks, electric 

shocks and fire.

• Be sure to use only for household and residence. 

  If this appliance is installed in inferior environment such as machine shop 

and etc., it can cause malfunction. 

• Use the original accessories and the specified components for 

installation.

  If parts other than those prescribed by us are used, It may cause water 

leaks, electric shocks, fire and personal injury.

• Install the unit in a location with good support.

  Unsuitable installation locations can cause the unit to fall and cause 

material damage and personal injury.

• Ventilate the working area well in the event of refrigerant leakage 

during installation.

  If the refrigerant comes into contact with naked flames, poisonous gas is 

produced.

• When installing in small rooms, take prevention measures not to 

exceed the density limit of refrigerant in the event of leakage, 
referred by the formula (accordance with ISO5149). 

  If the density of refrigerant exceeds the limit, please consult the dealer and 

install the ventilation system, otherwise lack of oxygen can occur, which 
can cause serious accident. 

• After completed installation, check that no refrigerant leaks from 

the system.

  If refrigerant leaks into the room and comes into contact with an oven or 

other hot surface, poisonous gas is produced.

• Use the prescribed pipes, flare nuts and tools for R410A.

  Using existing parts (for R22 or R407C) can cause the unit failure and 

serious accidents due to burst of the refrigerant circuit.

• Tighten the flare nut by torque wrench with specified method.

  If the flare nut were tightened with excess torque, this may cause burst and 

refrigerant leakage after a long period.

• The electrical installation must be carried out by the qualified 

electrician in accordance with “the norm for electrical work” and 
“national wiring regulation”, and the system must be connected to 
the dedicated circuit.

  Power supply with insufficient capacity and incorrect function done by 

improper work can cause electric shocks and fire.

• Be sure to shut off the power before starting electrical work.

  Failure to shut off the power can cause electric shocks, unit failure or 

incorrect function of equipment.

• Be sure to use the cables conformed to safety standard and cable 

ampacity for power distribution work. 

  Unconformable cables can cause electric leak, anomalous heat production 

or fire.  

• This appliance must be connected to main power supply by means 

of a circuit breaker or switch (fuse:16A) with a contact separation of 
at least 3mm. 

• When plugging this appliance, a plug conforming to the norm 

IEC60884-1 must be used.

• Use the prescribed cables for electrical connection, tighten the 

cables securely in terminal block and relieve the cables correctly to 
prevent overloading the terminal blocks.

  Loose connections or cable mountings can cause anomalous heat 

production or fire.

• Arrange the wiring in the control box so that it cannot be pushed up 

further into the box. Install the service panel correctly.

  Incorrect installation may result in overheating and fire.

• Be sure to switch off the power supply in the event of installation, 

inspection or servicing.

  If the power supply is not shut off, there is a risk of electric shocks, unit 

failure or personal injury due to the unexpected start of fan.

• Be sure to wear protective goggles and gloves while at work.
• Earth leakage breaker must be installed.

  If the earth leakage breaker is not installed, it can cause electric shocks.

CAUTION

• Use the circuit breaker of correct capacity. Circuit breaker should 

be the one that disconnect all poles under over current.

  Using the incorrect one could cause the system failure and fire.

• Install isolator or disconnect switch on the power supply wiring in 

accordance with the local codes and regulations.

  The isolator should be locked in OFF state in accordance with EN60204-1.

• Be sure to install indoor unit properly according to the installation 

manual in order to run off the drainage smoothly.

  Improper installation of indoor unit can cause dropping water into the room 

and damaging personal property.

• Install the drainage pipe to run off drainage securely according to 

the installation manual.

  Incorrect installation of the drainage pipe can cause dropping water into the 

room and damaging personal property.

• Be sure to install the drainage pipe with descending slope of 1/100 

or more, and not to make traps and air-bleedings.

  Check if the drainage runs off securely during commissioning and ensure 

the space for inspection and maintenance. 

• Secure a space for installation, inspection and maintenance 

specified in the manual.

  Insufficient space can result in accident such as personal injury due to 

falling from the installation place.

• For installation work, be careful not to get injured with the heat 

exchanger, piping flare portion or screws etc.

• Be sure to insulate the refrigerant pipes so as not to condense the 

ambient air moisture on them.

  Insufficient insulation can cause condensation, which can lead to moisture 

damage on the ceiling, floor, furniture and any other valuables.

• When perform the air conditioner operation (cooling or drying opera-

tion) in which ventilator is installed in the room. In this case, using the 
air conditioner in parallel with the ventilator, there is the possibility 
that drain water may backflow in accordance with the room lapse into 
the negative pressure status. Therefore, set up the opening port such 
as incorporate the air into the room that may appropriate to ventila-
tion (For example; Open the door a little). In addition, just as above, so 
set up the opening port if the room lapse into negative pressure status 
due to register of the wind for the high rise apartment etc.

• Be sure to perform air tightness test by pressurizing with nitrogen 

gas after completed refrigerant piping work.

  If the density of refrigerant exceeds the limit in the event of refrigerant 

leakage in the small room, lack of oxygen can occur,  which can cause 
serious accidents.

• Do not install the unit in the locations listed below.

  • Locations where carbon fiber, metal powder or any powder is floating.
  • Locations where any substances that can affect the unit such as sulphide 

gas, chloride gas, acid and alkaline can occur. 

  • Vehicles and ships.
  • Locations where cosmetic or special sprays are often used.
  • Locations with direct exposure of oil mist and steam such as kitchen and 

machine plant.

  • Locations where any machines which generate high frequency harmonics 

are used.

  • Locations with salty atmospheres such as coastlines. 
  • Locations with heavy snow (If installed, be sure to provide base flame and 

snow hood mentioned in the manual).

  • Locations where the unit is exposed to chimney smoke.
  • Locations at high altitude (more than 1000m high).
  • Locations with ammonic atmospheres.
  • Locations where heat radiation from other heat source can affect the unit.
  • Locations without good air circulation.
  • Locations with any obstacles which can prevent inlet and outlet air of the unit.
  • Locations where short circuit of air can occur (in case of multiple units 

installation).

  • Locations where strong air blows against the air outlet of outdoor unit.
  • Locations where something located above the unit could fall.
  It can cause remarkable decrease in performance, corrosion and damage 

of components, malfunction and fire.

• Do not install the indoor unit in the locations listed below (Be sure 

to install the indoor unit according to the installation manual for 
each model because each indoor unit has each limitation).

  • Locations with any obstacles which can prevent inlet and outlet air of the 

unit.

  • Locations where vibration can be amplified due to insufficient strength of 

structure.

  • Locations where the infrared receiver is exposed to the direct sunlight or 

the strong light beam (in case of the infrared specification unit).

  • Locations where an equipment affected by high harmonics is placed (TV 

set or radio receiver is placed within 1m).

  • Locations where drainage cannot run off safely.
  It can affect performance or function and etc. 

• Do not install the unit near the location where leakage of 

combustible gases can occur.

  If leaked gases accumulate around the unit, it can cause fire.

• Do not install the unit where corrosive gas (such as sulfurous acid 

gas etc.) or combustible gas (such as thinner and petroleum gases) 
can accumulate or collect, or where volatile combustible 
substances are handled.

  Corrosive gas can cause corrosion of heat exchanger, breakage of plastic 

parts and etc. And combustible gas can cause fire.

• Do not use the indoor unit at the place where water splashes may 

occur such as in laundries.

  Since the indoor unit is not waterproof, it can cause electric shocks and fire. 

• Do not install nor use the system close to the equipment that 

generates electromagnetic fields or high frequency harmonics.

  Equipment such as inverters, standby generators, medical high frequency 

equipments and telecommunication equipments can affect the system, and 
cause malfunctions and breakdowns. The system can also affect medical 
equipment and telecommunication equipment, and obstruct its function or 
cause jamming.

• Do not place any variables which will be damaged by getting wet 

under the indoor unit.

  When the relative humidity is higher than 80% or drainage pipe is clogged, 

condensation or drainage water can drop and it can cause the damage of 
valuables.

• Do not install the remote control at the direct sunlight.

  It can cause malfunction or deformation of the remote control.

• Do not use the unit for special purposes such as storing foods, 

cooling precision instruments and preservation of animals, plants or 
art.

  It can cause the damage of the items.

• Do not use any materials other than a fuse with the correct rating in 

the location where fuses are to be used.

  Connecting the circuit with copper wire or other metal thread can cause 

unit failure and fire.

• Do not touch any buttons with wet hands.

  It can cause electric shocks.

• Do not touch any refrigerant pipes with your hands when the 

system is in operation.

  During operation the refrigerant pipes become extremely hot or extremely 

cold depending the operating condition, and it can cause burn injury or 
frost injury.

• Carry out the electrical work for ground lead with care.

  Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults 

such as electric shocks due to short-circuiting.

• Do not put the drainage pipe directly into drainage channels where 

poisonous gases such as sulphide gas can occur.

  Poisonous gases will flow into the room through drainage pipe and 

seriously affect the user’s health and safety. This can also cause the 
corrosion of the indoor unit and a resultant unit failure or refrigerant leak.

• Ensure that no air enters in the refrigerant circuit when the unit is 

installed and removed.

  If air enters in the refrigerant circuit, the pressure in the refrigerant circuit 

becomes too high, which can cause burst and personal injury.

• Do not processing, splice the power cord, or share a socket with 

other power plugs.

  This may cause fire or electric shock due to defecting contact, defecting 

insulation and over-current etc.

• Do not bundling, winding or processing for the power cord. Or, do 

not deforming the power plug due to tread it.

  This may cause fire or heating.

• Do not vent R410A into the atmosphere : R410A is a fluorinated 

greenhouse gas, covered by the Kyoto Protocol with Groval 
Warming Potential (GWP)=1975.

• Do not run the unit with removed panels or protections.

  Touching rotating equipments, hot surfaces or high voltage parts can cause 

personal injury due to entrapment, burn or electric shocks.

• Do not perform any change of protective device itself or its setup 

condition.

  The forced operation by short-circuiting protective device of pressure 

switch and temperature controller or the use of non specified component 
can cause fire or burst.

WARNING

SAFETY PRECAUTIONS

• Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it 

during the installation work in order to protect yourself.

• The precautionary items mentioned below are distinguished into two levels,
                           and                        .
                           : Wrong installation would cause serious consequences such 

as injuries or death.

                           : Wrong installation might cause serious consequences 

depending on circumstances.

  Both mentions the important items to protect your health and safety so strictly 

follow them by any means.

• Be sure to confirm no anomaly on the equipment by commissioning after com-

pleted installation and explain the operating methods as well as the maintenance 
methods of this equipment to the user according to the owner’s manual. 

• Keep the installation manual together with owner’s manual at a place where 

any user can read at any time. Moreover if necessary, ask to hand them to a 
new user.

• For installing qualified personnel, take precautions in respect to themselves by 

using suitable protective clothing, groves, etc., and then perform the 
installation works.

• Please pay attention not to fall down the tools, etc. when installing the unit at 

the high position.

• If unusual noise can be heard during operation, consult the dealer.
• The meanings of “Marks” used here are shown as follows:

Never do it under any 
circumstances.

Always do it according to the 
instruction.

CAUTION

WARNING

CAUTION

WARNING

• This installation manual illustrates the method of installing an indoor 

unit.

• For electrical wiring work, please see instructions set out on the 

backside.

• For outdoor unit installation and refrigerant piping, please refer to the 

installation manual that comes with your outdoor unit.

• A wired remote control unit is supplied separately as an optional part.
• When install the unit, be sure to check whether the selection of 

installation place, power supply specifications, usage limitation (piping 
length, height differences between indoor and outdoor units, power 
supply voltage and etc.) and installation spaces. 

a

8. APPLICATION DATA

       (1)   Installation of indoor unit
              Models DXK09ZJ-S, 12ZJ-S, 18ZJ-S

Содержание DXK09ZJ-S

Страница 1: ...ESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONER Split system air to air heat pump type DXK09ZJ S DXK12ZJ S DXK18ZJ S Manual No 11 SRK T 118 ...

Страница 2: ......

Страница 3: ...TECHNICAL MANUAL ...

Страница 4: ... operation 43 40 1 Operation control function by remote controller 5 Flap and louver control 41 4 Custom cord switching procedure 40 3 Auto restart function 2 Unit ON OFF button 40 39 8 Installation location setting 43 9 Outline of heating operation 44 11 Outline of automatic operation 45 10 Outline of cooling operation 45 12 Protective control function 46 53 10 MAINTENANCE DATA 54 4 Troubleshooti...

Страница 5: ...tion procedures corresponding to detail of trouble 64 9 Checking the indoor electrical equipment 69 11 1 Instullation of wired remote controller RC E4 74 11 OPTION PARTS 74 11 2 Interface kit SC BIKN E 80 11 3 Super link E board SC ADNA E 84 How to read the model name Example DXK 09 Z Series code Inveter type Product capacity Model name DXK Wall mounted type DXC Outdoor unit J S ...

Страница 6: ...RFRPSXWHU WKHUPRVWDW ዙ 2SHUDWLRQ LVSOD 581 UHHQ 7 0 5 HOORZ 32 5 UHHQ 872 UHHQ 6DIHW GHYLFHV RPSUHVVRU RYHUKHDW SURWHFWLRQ 2YHUFXUUHQW SURWHFWLRQ URVW SURWHFWLRQ 6HULDO VLJQDO HUURU SURWHFWLRQ QGRRU IDQ PRWRU HUURU SURWHFWLRQ HDWLQJ RYHUORDG SURWHFWLRQ LJK SUHVVXUH FRQWURO RROLQJ RYHUORDG SURWHFWLRQ QVWDOODWLRQ 5HIULJHUDQW SLSLQJ VL H 2 PP LTXLG OLQH Ǿ DV OLQH Ǿ FRQQHFWLQJ PHWKRG P ODUH FRQQHFWLQJ...

Страница 7: ...5 HOORZ 32 5 UHHQ 872 UHHQ 6DIHW GHYLFHV RPSUHVVRU RYHUKHDW SURWHFWLRQ 2YHUFXUUHQW SURWHFWLRQ URVW SURWHFWLRQ 6HULDO VLJQDO HUURU SURWHFWLRQ QGRRU IDQ PRWRU HUURU SURWHFWLRQ HDWLQJ RYHUORDG SURWHFWLRQ LJK SUHVVXUH FRQWURO RROLQJ RYHUORDG SURWHFWLRQ QVWDOODWLRQ 5HIULJHUDQW SLSLQJ VL H 2 PP LTXLG OLQH Ǿ DV OLQH Ǿ FRQQHFWLQJ PHWKRG P ODUH FRQQHFWLQJ ዙ LTXLG OLQH DV LQH QVXODWLRQ IRU SLSLQJ P 1HFHVVDU...

Страница 8: ...tric heater Operation control Operation switch Wireless Remote control Room temperature control Microcomputer thermostat Operation Display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green Safety devices Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload protection High pressure control Cooling ...

Страница 9: ... piping 㧔Refer to the above view㧕 Hole on wall for right rear piping Hole on wall for left rear piping Gas piping Outlet for wiring Drain hose Liquid piping F E C D B Symbol A 㧔Ǿ65㧕 VP16 Ǿ6 35㧔1㧛4 㧕㧔Flare㧕 Content 㧔Ǿ65㧕 09 12 Ǿ9 52㧔3㧛8 㧕㧔Flare㧕 Outlet for piping㧔on both side㧕 G 18 Ǿ12 7㧔1㧛2 㧕㧔Flare㧕 Model Unit mm غ 120 19 60 150 17 3 G 790 60 14 5 45 31 60 45 798 294 229 3 45 60 9 100 106 5 585 10...

Страница 10: ...ounded by walls on the four sides 2 The unit must be fixed with anchor bolts An anchor bolt must not protrude more than 15mm 3 Where the unit is subject to strong winds lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction 4 Leave 1m or more space above the unit 5 A wall in front of the blower outlet must not exceed the units height 6 The model name...

Страница 11: ...Flare Notes 1 It must not be surrounded by walls on the four sides 2 The unit must be fixed with anchor bolts An anchor bolt must not protrude more the 15mm 3 Where the unit is subject to strong winds lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction 4 Leave 1m or more space above the unit 5 A wall in front of the blower outlet must not exceed t...

Страница 12: ... 11 SRK T 118 3 Remote controller a Wireless remote controller Unit mm 60 17 3 150 ...

Страница 13: ...kness 100 to 200m 0 5mm2 2 cores 0 75mm2 2 cores 1 25mm2 2 cores 2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y Sheath Upper cace Board Wiring Upper Lower Y X Tighten the screws after cutting off the thin part of screw mounting part Embedded mounting The peeling off length of sheath The peeling off length of sheath In...

Страница 14: ... 2 t o R AMP 2 HEAT EXCHANGER 5 FMI SMI LM1 LM2 F Va ThI Th2 Th3 T DS 㨪 㨪 Blue Black BK Red BL RD White WH Yellow㧛Green Y㧛G Color Mark Heat exch sensor Fan motor Room temp sensor Flap motor Diode stack DS Fuse F Connector CNE CNY FMI Terminal block T Description Item Varistor Va LM1 2 SMI Louver motor ThI Th2 3 Yellow Y Humidity sensor HD Power Source 1 Phase 220㧛230㧛240V 50Hz 3 ELECTRICAL WIRING ...

Страница 15: ... The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please follow the internal cabling regulations Adapt it to the regulation in effect in each country 9 2 0 32 1 5mm2 x 3 1 5mm2 12 09 MAX running current Power cable size 㧔m...

Страница 16: ... in each country The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please follow the internal cabling regulations Adapt it to the regulation in effect in each country 14 2 0 18 1 5mm2 x 3 1 5mm2 3 1 2 N 18 M T2 T1 S BK WH R...

Страница 17: ...ressure Level dB standard 2 10 5 P a Mid Octave Band frequency Hz 1000 2000 4000 8000 63 125 250 500 Mid Octave Band frequency Hz Indoor Unit Model DXK09ZJ S Noise Level Cooling 34 dB A Heating 39 dB A Cooling Heating Condition ISO T1 JIS C9612 N70 N60 N50 N40 N30 N20 N70 N60 N50 N40 N30 N20 Outdoor Unit Model DXC09ZJ S Noise Level Cooling 48 dB A Heating 47 dB A Cooling Heating ISC10016 4 NOISE L...

Страница 18: ...Sound Pressure Level dB standard 2 10 5 P a Mid Octave Band frequency Hz 1000 2000 4000 8000 63 125 250 500 Mid Octave Band frequency Hz Indoor Unit Model DXK12ZJ S Noise Level Cooling 45 dB A Heating 42 dB A Cooling Heating Condition ISO T1 JIS C9612 N70 N60 N50 N40 N30 N20 Outdoor Unit Model DXC12ZJ S Noise Level Cooling 50 dB A Heating 50 dB A Cooling Heating N70 N60 N50 N40 N30 N20 ISC10016 ...

Страница 19: ...N50 N30 N40 N60 N70 N20 Sound Pressure Level dB standard 2 10 5 P a Mid Octave Band frequency Hz 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Indoor Unit Model DXK18ZJ S Noise Level Cooling 46 dB A Heating 45 dB A Cooling Heating Model DXK18ZJ S Outdoor Unit Model DXC18ZJ S Noise Level Cooling 51 dB A Heating 53 dB A Cooling Heating Condition ISO T1 JIS C9612 ...

Страница 20: ...sensor Th1 Th2 Gas TH2 Heat exchanger sensor TH1 EEV Capillary tube Heat exchanger Humidity sensor HD Model DXK18ZJ S Models DXK09ZJ S 12ZJ S Indoor unit Outdoor unit Flare connection Flare connection Liquid pipe φ Gas pipie φ Service valve Heat exchanger Heat exchanger sensor Electronic expansion valve Liquid Strainer Muffler Capillary tube Outdoor air temp sensor Muffler Muffler Compressor Accum...

Страница 21: ...rt Cooling operation Approximately 15 to 46 D B Heating operation Approximately 15 to 24 D B Refer to the selection chart Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows The net cooling and heating capacity can be obtained in the following way Net capacity Capacity shown on specication Correction factors as follows 1 Coefcient of cooling and he...

Страница 22: ...ing on outdoor heat exchanger during heating How to obtain the cooling and heating capacity Piping length m Cooling Heating 7 1 0 1 0 10 0 99 1 0 15 0 975 1 0 20 0 965 1 0 25 0 95 1 0 Air inlet temperature of DXK12ZJ S outdoor unit in CWB Adjustment coefficient 15 0 95 0 95 0 94 0 93 0 91 0 88 0 86 0 87 0 92 1 00 10 9 7 5 3 1 1 3 5 or more DXK12ZJ S 3300 3217 ...

Страница 23: ... 01 4 18 2 94 m3 min 6 WB 4 09 4 04 4 00 3 95 3 90 Hi 22 3 29 2 80 3 47 2 77 3 66 2 92 3 75 2 90 3 83 2 87 3 99 3 00 4 13 2 93 10 WB 4 35 4 31 4 28 4 22 4 18 10 1 24 3 21 2 76 3 39 2 73 3 59 2 90 3 69 2 87 3 77 2 85 3 93 2 98 4 07 2 91 15 WB 4 73 4 69 4 66 4 61 4 56 m3 min 26 3 13 2 72 3 31 2 70 3 52 2 86 3 62 2 85 3 70 2 82 3 87 2 96 4 02 2 89 20 WB 5 09 5 05 5 02 4 96 4 92 28 3 04 2 69 3 23 2 66...

Страница 24: ...re damage on the ceiling floor furniture and any other valuables When perform the air conditioner operation cooling or drying opera tion in which ventilator is installed in the room In this case using the air conditioner in parallel with the ventilator there is the possibility that drain water may backflow in accordance with the room lapse into the negative pressure status Therefore set up the ope...

Страница 25: ...st of the refrigerant circuit Tighten the flare nut by torque wrench with specified method If the flare nut were tightened with excess torque this may cause burst and refrigerant leakage after a long period The electrical installation must be carried out by the qualified electrician in accordance with the norm for electrical work and national wiring regulation and the system must be connected to t...

Страница 26: ...Please note that measurement B protrusion from the flaring block will vary depending on the type of a flare tool in use If a conventional flare tool is used please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value Clutch type flare tool for R410A Conventional R22 flare tool ø6 35 ø9 52 ø12 7 0 0 0 5 0 0 0 5 0 0 0 5 1 0 1 5 1 0...

Страница 27: ...ventional flare tool Please note that measurement B protrusion from the flaring block will vary depending on the type of a flare tool in use If a conventional flare tool is used please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value Clutch type flare tool for R410A Conventional R22 flare tool ø6 35 ø9 52 ø12 7 0 0 0 5 0 0 0 ...

Страница 28: ...g If the power supply is not shut off there is a risk of electric shocks unit failure or personal injury due to the unexpected start of fan Stop the compressor before removing the pipe after shutting the service valve on pump down work If the pipe is removed when the compressor is in operation with the service valve open air would be mixed in the refrigeration circuit and it could cause explosion ...

Страница 29: ...processing for the power cord Or do not deforming the power plug due to tread it This may cause fire or heating Do not run the unit with removed panels or protections Touching rotating equipments hot surfaces or high voltage parts can cause personal injury due to entrapment burn or electric shocks Do not perform any change of protective device itself or its setup condition The forced operation by ...

Страница 30: ...e and hot air will not bother neighboring residents 〇 Where snow will not accumulate 〇 Where strong winds will not blow against the outlet pipe 〇 A place where no TV set or radio receiver is placed within 5m If electrical interference is caused seek a place less likely to cause the problem 〇 If a operation is conducted when the outdoor air temperature is 5 lower the outdoor unit should be installe...

Страница 31: ... hold connec This cl diamet Please Please ground It has Groundi Cable cla 4 ELECTRICAL WIRING Take care so that installed pipes may not touch components within a unit If touching with an internal component it will generate abnormal sounds and or vibrations 4 On site piping work IMPORTANT How to remove the side cover Carry out the on site piping work with the operation valve fully closed Give suffi...

Страница 32: ...d for air tightness at the factory check the connecting pipes after the installation work for air tightness from the operation valve s check joint equipped on the outdoor unit side While conducting a test keep the operation valve shut all the time a Raise the pressure to 0 5 MPa and then stop Leave it for five minutes to see if the pressure drops b Then raise the pressure to 1 5 MPa and stop Leave...

Страница 33: ...ol box Grounding terminal Cable clamp Indoor Outdoor connecting wire Power cable Please connect the earthed line of indoor and outdoor connecting wire to a bracket part of the illustration power cable indoor outdoor connecting wire circuit diagram 4 ELECTRICAL WIRING WORK For details of electrical cabling refer to the indoor unit installation manual CAUTION CAUTION Power cable indoor outdoor conne...

Страница 34: ...de for cables Required field cables H 05 R N R 4or5 G 1 5 Harmonized cable type 300 500 volts Natural and or synth rubber wire insulation Polychloroprene rubber conductors insulation Stranded core Number of conductors One conductor of the cable is the earth conductor yellow green Section of copper wire mm2 Power cables and connecting wires are securely fixed to the terminal block The power supply ...

Страница 35: ...ompressor before removing the pipe after shutting the service valve on pump down work If the pipe is removed when the compressor is in operation with the service valve open air would be mixed in the refrigeration circuit and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle Only use prescribed optional parts The installation must be carried out by the qualifi...

Страница 36: ... Any remaining packing materials can cause personal injury as it contains nails and wood And to avoid danger of suffocation be sure to keep the plastic wrapper away from children and to dispose after tear it up Be sure to insulate the refrigerant pipes so as not to condense the ambient air moisture on them Insufficient insulation can cause condensation which can lead to moisture damage on the ceil...

Страница 37: ...erence between indoor and outdoor units Plug the end of the pipe with tape or other material and fill the pipe with nitrogen gas Only use nitrogen gas N2 Taping N2 Nitrogen Brazing Station valve Primary side Secondary side 0 5MPa Hand Relief valve Nitrogen gas Brazing must be performed under a nitrogen gas flow About brazing When pipe is brazing 4 Caution about selection of installation location W...

Страница 38: ... tool handle mm Operation valve size mm 5 Air tightness test Gas side operation valve Check joint Pressurize Close Outdoor unit Indoor unit Work flow 6 Evacuation Air tightness test completed Vacuuming completed Vacuuming begins Do not hold the valve cap area with a spanner 3 Refrigerant pipe wall thickness and material NOTE Phosphorus deoxidized seamless copper pipe ICS 23 040 15 ICS 77 150 30 ø6...

Страница 39: ...ness larger than the specified minimum pipe thickness 14 18 34 42 49 61 45 60 30 45 30 45 150 200 250 Use a torque wrench If a torque wrench is not available fasten the flare nut manually first and then tighten it further using the left table as a guide 1 2 Run the vacuum pump for at least one hour after the vacuum gauge shows 0 1MPa or lower 76cmHg or lower When the system has remaining moisture ...

Страница 40: ...external force may work on terminal connections Grounding terminals are provided in the control box Switchgear or Circuit Breaker CAUTION CAUTION CAUTION Wires for connecting indoor and outdoor units Exterior tape Gas piping Insulation Liquid piping Band accessory Pipe cover accessory 8 Heating and condensation prevention Pay attention to the following points in addition to the above for the R410A...

Страница 41: ... IEC57 for supply cords of parts of appliances for outdoor use Ground the unit Do not connect the grounding wire to a gas pipe water pipe lightning rod or telephone grounding wire If improperly grounded an electric shock or malfunction may result A grounding wire must be connected before connecting the power cable Provide a grounding wire longer than the power cable The installation of an impulse ...

Страница 42: ...N CLEAR button ACL switch This switch is for resetting microcomputer and setting time OFF TIMER button This button selects OFF TIMER operation TEMPERATURE button These buttons sets the indoor temperature These buttons are used for setting the current time and timer function as well This button cancels the ON timer OFF timer and SLEEP operation CANCEL button The above illustration shows all control...

Страница 43: ...peration b Details of operation 3 ޓ Auto restart function a b 1 2 4 ޓ Custom cord switching procedure a Modifying the indoor printed circuit board b Modifying the wireless remote controller 1 2 Cut Function operation mode Indoor temperature setting Fan speed Flap Louver Timer Switch Cooling Thermal dry Heating ...

Страница 44: ...ox 50 Approx 60 Approx 60 Angle of Flap from Horizontal Center installation Remote controller display Right end installation Left end installation Angle of Louver Left Approx 50 Left Approx 50 Left Approx 20 Left Approx 45 Center Left Approx 30 Right Approx 20 Center Right Approx 50 Right Approx 20 Left Approx 20 Center Right Approx 30 Right Approx 45 Right Approx 50 Louver stopped Swing Spot Wide...

Страница 45: ...p down Swing Heating Center Fixed Wide Fixed Flap Louver Cooling Heating Horizontal blowing Fixed Slant forwardl blowing Fixed Operation mode Indoor temp Setting temp 2 C Setting temp Indoor temp 2 C At heating At cooling Air flow direction contorol 2 C Setting temp Indoor temp 5 C 2 C Indoor temp Setting temp 5 C Indoor temp Setting temp 5 C Setting temp Indoor temp 5 C The control in 4 continues...

Страница 46: ...ng unit is running press the ON OFF button to stop 2 Press the AIR FLOW UP DOWN button and the AIR FLOW LEFT RIGHT button together for 5 seconds or more 3 Setting the air conditioning installation location 4 Press the ON OFF button Airflow range Airflow range Airflow range Left End Installation Center Installation Right End Installation Center Installation Right End Installation Left End Installat...

Страница 47: ...c d e a b 2 30 115rps 30 115rps 30 76rps 30 46rps DXK12ZJ S 23 106rps 23 106rps 23 78rps 23 50rps DXK18ZJ S 30 115rps 30 115rps 30 72rps 30 42rps DXK09ZJ S Model Fan speed Auto MED HI LO model 18 35 model 18 35 model 18 2 ޓ model 18 2 ޓ a b c e model 18 10 16 minutes and 50 seconds model 18 18 minutes 20 20 15 10 5 0 5 10 15 10 5 0 Outdoor air temperature Outdoor heat exchanger temperature 20 20 1...

Страница 48: ...ps 23 38rps DXK18ZJ S 20 74rps 20 74rps 20 55rps 20 34rps DXK09ZJ S Model Fan speed Auto MED HI LO 11 ޓ Outline of automatic operation a Determination of operation mode Heating Dehumidifying Cooling Indoor air temperature C Outdoor air temperature C A When both the indoor and the outdoor air temperatures are in the range A cooling or heating is switched depending on d e a b 2 model 18 2 ޓ model 18...

Страница 49: ...pressor running the lower limit 41 C or more 29 rps The lower limit of compressor command speed is set to 30 or 40 model 18 29 rps and even if the calculated result becomes lower than that after fuzzy calculation the speed is kept to 30 or 40 model 18 29 rps However when the thermo becomes OFF the speed is reduced to 0 rps b 1 2 3 c d 18 0 18 30 Heating Dehumidifying Indoor air temperature C Outdo...

Страница 50: ...30 rps the speed is kept to 50 44 30 rps However when the thermo becomes OFF the speed is Models 09 12 First time Since the second times Outdoor air temperature C A B C D Model 18 model 18 9ºC or 10ºC 9 16 19 10 Note 1 Value in are for the model 18 2 Detail of operation 3 Reset conditions c Cooling high pressure control 1 Purpose 2 Detector 3 Detail of operation 53 58 63 Outdoor heat exchanger tem...

Страница 51: ...the output speed obtained with the fuzzy calculation exceeds the upper limit the upper limit value is maintained The lower limit of compressor command speed is set to 40 rps and even if the calculated result becomes lower than that after fuzzy calculation the speed is kept to 40 rps However when the thermo becomes OFF the speed is reduced to 0 prs rps 3 Reset conditions e Heating high pressure con...

Страница 52: ...tion iii iv that after fuzzy calculation the speed is kept to 40 rps However when the thermo becomes OFF the speed is reduced to 0 prs rps a Operating conditions b Detail of operation When the outdoor air temperature TH2 is 11ºC or higher continues for 30 seconds while the compressor command speed other than 0 rps i ii iii iv Taking the upper limit of compressor command speed range at 78 rps if th...

Страница 53: ...ir temperature C a b 09 SRK DB 087D h Compressor overheat protection 1 Purpose 2 Detail of operation a Discharge pipe temperature C Example Fuzzy 90 100 110 b i Current safe 1 Purpose 2 Detail of operation j Current cut 1 Purpose 2 Detail of operation k Outdoor unit failure Cooling Heating Lower limit speed Item Model 3 ޓ Reset conditions When either of the following condition is satisfied a ޓ The...

Страница 54: ...Serial signal transmission error protection 1 Purpose 2 Detail of operation n Rotor lock o Outdoor fan motor protection p Outdoor fan control at low outdoor temperature Cooling 1 Operating conditions 2 Detail of operation 3 Reset conditions Heating 1 Operating conditions 2 Detail of operation 3 Reset conditions Outdoor temperature 10 C Outdoor temperature 10 C Outdoor fan a b a b a c model 50 0ºC ...

Страница 55: ...ion When the compressor has been turned OFF b When the conditions of 1 above are met the compressor stops Error stop occurs when the compressor has stopped 3 times within 60 minutes c When after meeting the conditions of a and b above the compressor speed indoor air temperature Th1 and indoor heat exchanger temperature Th2 have met the conditions in the following table for 5 minutes Compressor spe...

Страница 56: ...H YDOYH RSHQ 3 Troubleshooting procedure If the air conditioner does not run at all I WKH DLU FRQGLWLRQHU GRHV QRW UXQ DW DOO GLDJQRVH WKH WURXEOH XVLQJ WKH IROORZLQJ WURXEOHVKRRWLQJ SURFHGXUH I WKH DLU FRQGLWLRQHU LV UXQQLQJ EXW EUHDNV GRZQ SURFHHG WR WURXEOHVKRRWLQJ VWHS Important KHQ DOO WKH IROORZLQJ FRQGLWLRQV DUH PHW ZH VD WKDW WKH DLU FRQGLWLRQHU ZLOO QRW UXQ DW DOO D 7KH 581 OLJKW GRHV QRW...

Страница 57: ... 54 11 SRK T 118 09 SRK DB 087D 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 55 56 62 56 62 ...

Страница 58: ...rned on or when there is no signal for 7 minute 35 seconds or longer during operation the compressor is stopped Defective power supply Broken signal wire defective indoor outdoor PCB Error of signal transmission If the compressor motor s magnetic pole positions cannot be correctly detected when the compressor starts The air conditioner stops Defective compressor Open phase on compressor Defective ...

Страница 59: ... indoor unit Data are recorded for up to 5 previous occurrences Data which are older than the 5th previous occurrence are erased In addition data on the temperature of each sensor room temperature indoor heat exchanger outdoor heat exchanger outdoor air temperature discharge pipe remote controller information operation switching fan speed switching are recorded when trouble occurs so more detailed...

Страница 60: ...VZLWFKLQJ 0 872 2 0 872 LVSOD V WKH UHDVRQ IRU VWRSSLQJ GLVSOD LQ WKH SDVW HUURU FRGH LVSOD V WKH URRP WHPSHUDWXUH VHQVRU WHPSHUDWXUH DW WKH WLPH WKH HUURU FRGH ZDV GLVSOD HG LQ WKH SDVW LVSOD V WKH LQGRRU KHDW H FKDQJHU VHQVRU WHPSHUDWXUH DW WKH WLPH WKH HUURU FRGH ZDV GLVSOD HG LQ WKH SDVW LVSOD V WKH UHPRWH FRQWUROOHU LQIRUPDWLRQ DW WKH WLPH WKH HUURU FRGH ZDV GLVSOD HG LQ WKH SDVW LVSOD V WKH ...

Страница 61: ...on for the stop stop code 2 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 3 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 4 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 5 ...

Страница 62: ... sensor is abnormal 38 8 time flash Outdoor unit s fan motor is abnormal 48 8 time flash Current safe 58 8 time flash Connection lines between the indoor and outdoor units are faulty 61 1 time flash Serial transmission error 62 2 time flash Discharge pipe sensor is abnormal anomalous stop 39 9 time flash Rotor lock 60 OFF 5 times 3 times 3 times 3 times 2 times Number of flashes when in service mo...

Страница 63: ... controller information tables 2SHUDWLRQ VZLWFKLQJ RUN light Operation switching Display pattern when in service mode Operation switching when there is an abnormal stop 0 1 2 4 3 AUTO DRY COOL FAN HEAT DQ VSHHG VZLWFKLQJ TIMER light Fan speed switching Display pattern when in service mode Fan speed switching when there is an abnormal stop 0 2 3 4 6 7 AUTO HI MED LO HI POWER ECONO I QR GDWD DUH UHF...

Страница 64: ...26 16 6 6 16 26 36 46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 88 98 59 49 39 29 19 9 9 19 29 39 49 59 69 79 89 99 No does not sound I QR GDWD DUH UHFRUGHG HUURU FRGH LV QRUPDO WKH GLVSOD IRU HDFK VHQVRU EHFRPHV DV VKRZQ EHORZ Sensor name Room temperature sensor Indoor heat exchanger sensor Outdoor air temperature sensor Outdoor heat exch...

Страница 65: ...32 12 12 32 52 72 92 112 132 54 34 14 14 34 54 74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 118 138 No does not sound I QR GDWD DUH UHFRUGHG HUURU FRGH LV QRUPDO WKH GLVSOD IRU HDFK VHQVRU EHFRPHV DV VKRZQ EHORZ Sensor value displayed when the error code is normal 64ºC DPSOH LVFKDUJH SLSH WHPSHUDWXUH Q WKH FDVH RI GLVFKDUJH SLSH GDWD PXOWLSO WKH UHDGLQJ YDOXH E HORZ 0 5 se...

Страница 66: ... 63 11 SRK T 118 09 SRK DB 087D Service data record form 57 ...

Страница 67: ...70 0 10 Discharge pipe sensor temperature characteristics Indoor fan motor error Broken sensor wire connector poor connection 0 0 20 40 60 80 100 120 135 20 40 60 80 100 120 140 160 180 Temperature C Resistance k Defective fan motor connector poor connection defective indoor PCB 69 for the fan motor and indoor PCB check proc Power supply reset Is it normalized Malfunction by temporary noise Replac...

Страница 68: ...circuit Compressor output is open phase Outdoor PCB is faulty Service valve is closed EEV is faulty Compressor faulty Current safe stop Overload operation compressor lock overcharge 73 70 DXC09 12 1 703Ω U V V W U W or more at 20ºC DXC18 1 417Ω U V 1 392Ω V W 1 435Ω U W or more at 20ºC ...

Страница 69: ... 66 11 SRK T 118 09 SRK DB 087D Over heat of compressor Gas shortage defective discharge pipe sensor Error of signal transmission Wiring error including power cable defective indoor outdoor PCB 64 ...

Страница 70: ...age 65 Outdoor fan motor error Defective fan motor connector poor connection defective outdoor PCB See pages 73 for the fan motor and outdoor PCB check proc After making sure the fan motor and outdoor PCB are nor Power supply reset Is it normalized Malfunction by temporary noise Replace fan motor If the error persists after replacing the fan motor replace the outdoor PCB the fan motor and outdoor ...

Страница 71: ... Humidity sensor 1 Cooling Heating Humidity sensor operation Failure mode Control input circuit resding Air conditioning system operation See page 65 Note 1 DXK12 18ZJ S only 09 SRK DB 087D 9 Checking the indoor electrical equipment a Indoor PCB check procedure b Outdoor unit Is there voltage between terminal blocks and AC 220 230 240 V Indoor electrical components are normal Is the voltage betwee...

Страница 72: ... out 3 15 A YES YES YES NO NO NO b Indoor unit fan motor check procedure 1 Indoor PCB output check 2 Fan motor resistance check FMI DC15V Indoor PCB DC 308 336V DC several V 4 6 V CNU GND Blue Yellow White Black Red Heat exchanger sensor Cooling Heating Ourdoor air temperature sensor Cooling Heating Discharge pipe sensor All modes Measuring point Resistance when normal Measuring point Resistance w...

Страница 73: ...he compressor system burns wiring mistakes etc If no problems are found check the output of the power transistor 2 Output inspection procedure Disconnect the terminals for the compresseor If an output such as the one shown in the figure on the below can be measured the power transistor and the circuit board for the outdoor unit are normal Example RUN light ON TIMER light 2 time flash Measure in th...

Страница 74: ... 71 11 SRK T 118 09 SRK DB 087D 11 Outdoor unit inspection points DXC09ZJ S 12ZJ S 73 73 64 ...

Страница 75: ...l inspection 1 to 2 AC 220 230 240V 2 to 3 Normal if the voltage oscillates between DC 0 and approx 20V CAUTION HIGH VOLTAGE High voltage is produced in the control box Don t touch electrical parts in the control box for 5 minutes after the unit is stopped Color symbol L to N AC 220 230 240V Model DXC18ZJ S Outdoor unit M T2 T1 S BK WH RD V W U PCB ASSY MAIN M M R TRANSISTOR POWER CIRCUIT SWITCHIN...

Страница 76: ...DQ PRWRU HUURU LV GHWHFWHG GLDJQRVH ZKLFK RI WKH RXWGRRU XQLW IDQ PRWRU RU RXWGRRU 3 LV GHIHFWLYH LDJQRVH WKLV RQO DIWHU FRQ UPLQJ WKDW WKH LQGRRU XQLW LV QRUPDO 2XWGRRU 3 RXWSXW FKHFN 7XUQ RII WKH SRZHU LVFRQQHFW WKH RXWGRRU XQLW IDQ PRWRU FRQQHFWRU 1 1 KHQ WKH LQGRRU XQLW LV RSHUDWHG E LQVHUWLQJ WKH SRZHU VXSSO SOXJ DQG SUHVVLQJ 21 WKH EDFNXS VZLWFK IRU PRUH WKDQ VHFRQGV LI WKH YROWDJH RI SLQ 1R...

Страница 77: ...a nipper or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote controller co terminal block Connect the terminal of remote c with the terminal of indoor unit X X and Y are no polarity Wiring route is as shown in the rig depending on the pulling out dire The wiring inside the remote cont The sheath should be peeled off Th...

Страница 78: ...nnect the remote controller cord to the terminal block Connect the terminal of remote controller X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram depending on the pulling out direction The wiring inside the remote controller case should be within 0 3mm2 recommended to 0 5mm2 The sheath should be peeled off inside the remote controller c...

Страница 79: ...er three seconds The indication changes to FUNCTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT by using button 5 Press SET button to fix 6 When UPPER LIMIT is selected valid during heating Press SET button to fix Indication example UPPER 26 C Displayed for two seconds After the ...

Страница 80: ...stop position in the four The louver can stop at any position In normal working indication indoor unit temperature is indicated instead of airflow Only the master remote controller can be indicated Heating preparation indication should not be indicated Temperature indication is by degree C Temperature indication is by degree F ON OFF button finished Start Stop air conditioner and press SET and MOD...

Страница 81: ...crease in return air temperature of indoor unit To be reset producing 1 5 C increase in return air temperature of indoor unit To be reset producing 2 0 C increase in return air temperature of indoor unit When heating thermostat is OFF to be operated with low fan speed or with ultra low fan speed in case of some models When heating thermostat is OFF to be operated with set fan speed When heating th...

Страница 82: ...he FUNCTION SET will be displayed Press SET button Selecct FUNCTION remote controller function or I U FUNCTION indoor unit function Operation message Function description setting description Function No Fixing button Finishing button 7 2 1 6 Starting button Previous screen button Indoor unit selection button Press SET button 6 DATA LOADING Indication with blinking Display is changed to 01 GRILLE S...

Страница 83: ... an electric shock fire and sersonal injury Warnings Warning Always go along these instruction Safety precautions Before use please read these Safety Precautions thoroughly before installation All the cautionary items mentioned below are important safety related items to be taken into consideration so be sure to observe them at all times Incorrect installation could lead to serious consequences su...

Страница 84: ...ly 1 3m from the indoor unit Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the punch outs for the connection cables running into the casing with cutter Recess the electrical box locally procured and connection cables in the wall Mount the lower casing of the interface to the elec...

Страница 85: ...re round cable Vinyl insulated wirevinyl sheathed cable for control It is available to operate the air conditioning unit and to monitor the operation status with the external control unit remote display by sending the input output signal through CNT connector on the indoor control PCB Connect a external remote control unit locally procured to CNT terminal In case of the pulse input switch OFF the ...

Страница 86: ...should be used for the wiring of wired remote controller C Maximum length of wiring is 600m If the length of wiring exceeds 100m change the size of cable as mentioned below 100m 200m 0 5mm2 x 2 core 300m or less 0 75mm2 x 2 core 400m or less 1 25mm2 x 2 core 600m or less 2 0mm2 x 2 core However cable size connecting to the terminal of wired remote controller should not exceed 0 5mm2 Accordingly if...

Страница 87: ... 84 11 SRK T 118 11 3 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...

Страница 88: ... 85 11 SRK T 118 ...

Страница 89: ... 86 11 SRK T 118 ...

Страница 90: ... 87 PARTS LIST INDOOR UNIT DXK09ZJ S DXK12ZJ S DXK18ZJ S OUTDOOR UNIT DXC09ZJ S DXC12ZJ S DXC18ZJ S ...

Страница 91: ... 88 CRAE0221 30 35 5 7 28 8 26 25 32 29 36 34 6 18 18 17 19 24 23 22 21 20 19 16 14 12 15 15 15 11 13 9 10 6 3 2 4 35 4 31 27 33 1 PANEL FAN ASSY ...

Страница 92: ...5 LOUVER 5 1 1 2 2 14 RLA129A009 PLATE CONNECTING L 1 1 1 1 2 15 RKW935C200 COLLAR 6 16 RLA129A013 BRACKET MOTOR L 1 1 1 1 2 17 RLA129A014 BRACKET MOTOR R 1 1 1 1 2 18 RKY144A004 CRANK C 2 1 1 1 2 19 SSA512T096 MOTOR STEPPING 2 1 1 1 2 20 21 RLA129A018 BOX ASSY GEAR 1 1 1 1 2 21 SSA512T049 MOTOR STEPPING 1 1 1 1 2 22 RKS504A100M HARNESS ASSY 1 1 1 1 2 FOR FLAP MOTOR 23 RKS504A100N HARNESS ASSY 1 1...

Страница 93: ... 90 CRAE0222 26 20 1 21 28 17 11 12 22 23 25 13 24 24 2 14 15 19 18 16 9 6 10 27 29 31 30 4 5 7 8 3 HEAT EXCH CONTROL ...

Страница 94: ...R BEND 1 14 SSA551A223F SENSOR ASSY 1 1 1 2 4 15 SSA561B702B BLOCK TERMINAL 1 1 1 2 2 T1 16 SSA554D183 KILLER NOISE 1 17 19 RLA505A001BN PWB ASSY 1 2 2 4 8 18 SSA555B050C VARISTOR 1 1 1 1 2 Z1 19 SSA564A132 FUSE CURRENT 1 1 1 1 2 F1 3 15A 20 RLA503A001 DISPLAY ASSY 1 1 1 2 4 21 RLA505A003 PWB ASSY DISPLAY 1 2 2 4 8 22 23 RLA132A008 LID ASSY CONTROL 1 22 RLA132A007 LID CONTROL 1 23 RLA132A005 COVER...

Страница 95: ... 92 CRAE0221 30 35 5 7 28 8 26 25 32 29 36 34 6 18 18 17 19 24 23 22 21 20 19 16 14 12 15 15 15 11 13 9 10 6 3 2 4 35 4 31 27 33 1 PANEL FAN ASSY ...

Страница 96: ...5 LOUVER 5 1 1 2 2 14 RLA129A009 PLATE CONNECTING L 1 1 1 1 2 15 RKW935C200 COLLAR 6 16 RLA129A013 BRACKET MOTOR L 1 1 1 1 2 17 RLA129A014 BRACKET MOTOR R 1 1 1 1 2 18 RKY144A004 CRANK C 2 1 1 1 2 19 SSA512T096 MOTOR STEPPING 2 1 1 1 2 20 21 RLA129A018 BOX ASSY GEAR 1 1 1 1 2 21 SSA512T049 MOTOR STEPPING 1 1 1 1 2 22 RKS504A100M HARNESS ASSY 1 1 1 1 2 FOR FLAP MOTOR 23 RKS504A100N HARNESS ASSY 1 1...

Страница 97: ... 94 CRAE0223 27 21 22 29 17 11 12 23 24 26 13 20 25 25 2 14 15 19 18 16 9 6 10 28 30 32 31 4 5 7 8 3 1 HEAT EXCH CONTROL ...

Страница 98: ...3F SENSOR ASSY 1 1 1 2 4 15 SSA561B702B BLOCK TERMINAL 1 1 1 2 2 T1 16 SSA554D183 KILLER NOISE 1 17 19 RLA505A001BP PWB ASSY 1 2 2 4 8 18 SSA555B050C VARISTOR 1 1 1 1 2 Z1 19 SSA564A132 FUSE CURRENT 1 1 1 1 2 F1 3 15A 20 SSA551B017A SENSOR HUMIDITY 1 1 1 2 4 21 RLA503A001 DISPLAY ASSY 1 1 1 2 4 22 RLA505A003 PWB ASSY DISPLAY 1 2 2 4 8 23 24 RLA132A008 LID ASSY CONTROL 1 23 RLA132A007 LID CONTROL 1...

Страница 99: ... 96 CRAE0221 30 35 5 7 28 8 26 25 32 29 36 34 6 18 18 17 19 24 23 22 21 20 19 16 14 12 15 15 15 11 13 9 10 6 3 2 4 35 4 31 27 33 1 PANEL FAN ASSY ...

Страница 100: ...5 LOUVER 5 1 1 2 2 14 RLA129A009 PLATE CONNECTING L 1 1 1 1 2 15 RKW935C200 COLLAR 6 16 RLA129A013 BRACKET MOTOR L 1 1 1 1 2 17 RLA129A014 BRACKET MOTOR R 1 1 1 1 2 18 RKY144A004 CRANK C 2 1 1 1 2 19 SSA512T096 MOTOR STEPPING 2 1 1 1 2 20 21 RLA129A018 BOX ASSY GEAR 1 1 1 1 2 21 SSA512T049 MOTOR STEPPING 1 1 1 1 2 22 RKS504A100M HARNESS ASSY 1 1 1 1 2 FOR FLAP MOTOR 23 RKS504A100N HARNESS ASSY 1 1...

Страница 101: ... 98 CRAE0223 27 21 22 29 17 11 12 23 24 26 13 20 25 25 2 14 15 19 18 16 9 6 10 28 30 32 31 4 5 7 8 3 1 HEAT EXCH CONTROL ...

Страница 102: ...223F SENSOR ASSY 1 1 1 2 4 15 SSA561B702B BLOCK TERMINAL 1 1 1 2 2 T1 16 SSA554D183 KILLER NOISE 1 17 19 RLA505A001BR PWB ASSY 1 2 2 4 8 18 SSA555B050C VARISTOR 1 1 1 1 2 Z1 19 SSA564A132 FUSE CURRENT 1 1 1 1 2 F1 3 15A 20 SSA551B017A SENSOR HUMIDITY 1 1 1 2 4 21 RLA503A001 DISPLAY ASSY 1 1 1 2 4 22 RLA505A003 PWB ASSY DISPLAY 1 2 2 4 8 23 24 RLA132A008 LID ASSY CONTROL 1 23 RLA132A007 LID CONTROL...

Страница 103: ... 100 CRBE0323 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 19 8 10 PANEL FAN ASSY ...

Страница 104: ...UTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 1 1 2 4 8 SSA913A034F SCREW TAP 27 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A006 BRACKET ASSY 1 12 SSA512T094 MOTOR DC 1 1 1 1 2 13 RCV116A003 BRACKET MOTOR U 1 14 RCV141A002A PLATE BAFFLE 1 15 SSA431B253 PROPELLER 1 1 1 2 4 16 SSA914B007AC NUT TH 1 17 RCV111A001 BASE ASSY 1 1 1 1 2 18 W011D04X008 TAP...

Страница 105: ... 102 CRBE0339 21 3 7 6 15 16 11 12 17 2 9 10 8 14 13 5 22 25 23 26 27 CONTROL ASSY 24 30 31 24 19 4 20 28 1 18 24 29 GAS LIQ HEAT EXCH CONTROL ...

Страница 106: ...SA382F013K COIL ASSY SOLENOID 1 1 1 1 2 FOR 20S 14 SSA382F210AY COIL SOLENOID 1 1 1 1 2 FOR EEV 15 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 16 SSA914C013A NUT FLANGE 3 17 SSA941C346A CUSHION RUBBER 3 18 RSA932C004 GASKET COVER 1 19 RSA947K005 COVER TERMINAL 1 1 1 2 4 20 SSA914C016 NUT FLANGE 1 21 RCV505A101B PWB ASSY 1 2 2 4 8 22 RCV011G002AA LABEL WIRING 1 23 SSA561B723 BLOCK TERMINAL 1 1 1 2 2 24 ...

Страница 107: ... 104 CRBE0323 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 19 8 10 PANEL FAN ASSY ...

Страница 108: ...UTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 1 1 2 4 8 SSA913A034F SCREW TAP 27 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A006 BRACKET ASSY 1 12 SSA512T094 MOTOR DC 1 1 1 1 2 13 RCV116A003 BRACKET MOTOR U 1 14 RCV141A002A PLATE BAFFLE 1 15 SSA431B253 PROPELLER 1 1 1 2 4 16 SSA914B007AC NUT TH 1 17 RCV111A001 BASE ASSY 1 1 1 1 2 18 W011D04X008 TAP...

Страница 109: ... 106 CRBE0339 21 3 7 6 15 16 11 12 17 2 9 10 8 14 13 5 22 25 23 26 27 CONTROL ASSY 24 30 31 24 19 4 20 28 1 18 24 29 GAS LIQ HEAT EXCH CONTROL ...

Страница 110: ...SA382F013K COIL ASSY SOLENOID 1 1 1 1 2 FOR 20S 14 SSA382F210AY COIL SOLENOID 1 1 1 1 2 FOR EEV 15 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 16 SSA914C013A NUT FLANGE 3 17 SSA941C346A CUSHION RUBBER 3 18 RSA932C004 GASKET COVER 1 19 RSA947K005 COVER TERMINAL 1 1 1 2 4 20 SSA914C016 NUT FLANGE 1 21 RCV505A101B PWB ASSY 1 2 2 4 8 22 RCV011G002AA LABEL WIRING 1 23 SSA561B723 BLOCK TERMINAL 1 1 1 2 2 24 ...

Страница 111: ... 108 CRBE0324 9 13 15 16 14 17 7 6 4 19 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...

Страница 112: ...3 6 RCT132A002 COVER ASSY SERVICE 1 1 1 1 2 7 SSA944B036B HANDLE 1 8 RCT131A001 GUARD FIN 1 9 RCT142A004 COVER TB 1 1 1 2 4 10 SSA913A034F SCREW TAP 25 4 8 11 SSA913A034G SCREW TAP 1 4 12 12 SSA913A008F SCREW TAP 1 4 10 13 RCT116A003 BRACKET MOTOR 1 14 SSA512T091A MOTOR DC 1 1 1 1 2 15 RCT141A001A PLATE BAFFLE 1 1 1 2 4 16 SSA431B250 PROPELLER 1 17 SSA914B007AC NUT TH 1 18 RCT111A001AG BASE ASSY 1...

Страница 113: ... 110 CRBE0326 10 11 7 8 6 30 29 32 29 33 CONTROL ASSY 21 13 3 4 2 20 19 31 16 34 17 1 12 9 5 GAS 18 29 14 15 LIQ 24 23 27 26 25 28 22 HEAT EXCH CONTROL ...

Страница 114: ...EV 14 RCT154D004 INSULATION COMP 1 15 RCV154D003 INSULATION COMP 1 16 RSA201A036 COMPRESSOR ASSY 1 1 2 3 8 17 SSA914C013A NUT FLANGE 2 18 SSA941C354 CUSHION RUBBER 3 19 RSA932C004 GASKET COVER 1 20 RSA947K005 COVER TERMINAL 1 1 1 2 4 21 SSA914C016 NUT FLANGE 1 22 RCT505A005AA PWB ASSY MAIN 1 2 2 4 8 23 RCT505A004A PWB ASSY SUB 1 2 2 4 8 24 RCT011G002AB LABEL WIRING 1 25 SSA561B665 BLOCK TERMINAL 1...

Страница 115: ...NVERTER RESIDENTIAL AIR CONDITIONERS Copyright MITSUBISHI HEAVY INDUSTRIES LTD Because of our policy of continuous improvement we reserve the right to make changes in all specifications without notice C ...

Отзывы: