'11 • SRK-T-118
'09•SRK-DB-087D
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
(3) Correction relative to frosting on outdoor heat exchanger during heating
How to obtain the cooling and heating capacity
=
Piping length [m]
Cooling
Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
Air inlet temperature of
DXK12ZJ-S
outdoor unit in °C WB
Adjustment coefficient
-15
0.95
0.95
0.94
0.93
0.91
0.88
0.86
0.87
0.92
1.00
-10
-9
-7
-5
-3
-1
1
3
5 or more
DXK12ZJ-S
3300
3217
Содержание DXK09ZJ-S