background image

-

 

 

-

 '11 • SRK-T-118

INSTALLATION MANUAL FOR OUTDOOR UNIT

RWC012A032B

Model 09, 12, 18

Accessories for outdoor unit

• Model name and power source

• Refrigerant piping length

• Piping, wiring and miscellaneous small parts

• Indoor unit installation manual

Necessary tools for the installation work

Wrench key (Hexagon) [4m/m]
Vacuum pump
Vacuum pump adapter (Anti-reverse flow type)
(Designed specifically for R410A)
Gauge manifold (Designed specifically for R410A)
Charge hose (Designed specifically for R410A)
Flaring tool set (Designed specifically for R410A)
Gas leak detector (Designed specifically for R410A)
Gauge for projection adjustment
(Used when flare is made by using conventional flare tool)

9

10

11

12
13
14
15

16

Plus headed driver
Knife
Saw
Tape measure
Hammer
Spanner wrench
Torque wrench [14.0

~

62.0N·m (1.4

~

6.2kgf·m)]

Hole core drill (65mm in diameter)

1
2
3
4
5
6
7
8

Grommet (Heat
pump type only)
Drain elbow (Heat pump type only)

Model 09, 12
Model 18

Q’ty

1
4
1

1

2

Option parts

Sealing plate
Sleeve
Inclination plate
Putty
Drain hose (extension hose)
Piping cover
(for insulation of connection piping)

Q’ty

1
1
1
1
1

1

Check before installation work

a
b
c
d
e

f

R410A REFRIGERANT USED

1. HAULAGE AND INSTALLATION

(Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)

Intake

The height of a wall is 1200mm or less.

(

service

space

)

Intake

Outlet

Fasten with bolts

(M10-12)

Use a thicker block to anchor deeper.

Use a long block to extend the width.

CAUTION

When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity center position.

If not properly balanced, the unit can be thrown off-balance and fall.

1) Delivery

2) Portage

3) Selecting the installation location

5) Installation space

L

3

L

2

L

4

L

1

Model 09, 12, 18

Model 09, 12

Example installation

Size

L1
L2
L3
L4

Open

100
100
250

280

75
80

Open

280

Open

80

250

180

Open

80

Open

(mm)

I

II

III

IV

Heavy

6) Installation

Pad

Over 500mm

Intake

Outlet

31

2.

5

24

.3

14

.8

28

8.

8

111

510

157.8

35

1.

6

Model 18

Intake

Outlet

31

2.

5

24

.3

14

.8

28

8.

8

88.4

510

200

35

1.

6

• Deliver the unit as close as possible to the installation site before removing it from

the packaging.

• When you have to unpack the unit for a compelling reason before you haul it to

the installation point, hoist the unit with nylon slings or ropes and protection pads

so that you may not damage the unit.

• The right hand side of the unit as viewed from the front (diffuser side) is heavier.

A person carrying the right hand side must take heed of this fact. A person

carrying the left hand side must hold with his right hand the handle provided on

the front panel of the unit and with his left hand the corner column section.

(1) If the unit is installed in the area where the snow will accumulate, following measures are required.

The bottom plate of unit and intake, outlet may be blocked by snow.

1 Install the unit on the base so that the bottom is

higher than snow cover surface.

Since drain water generated by defrost control may freeze, following measures are required.

• Do not execute drain piping work by using a drain elbow and drain grommets (optional parts).

[Refer to Drain piping work.]

Determine refrigerant pipe size pursuant to the following guidelines based

on the indoor unit specifications.

Without nitrogen gas, a large quantity of foreign matters

(oxidized film) are created, causing a critical failure from

capillary tube or expansion valve clogging.

2 Install the unit under or provide the roof on site.

Be careful of the following conditions and choose an installation place.
• Where air is not trapped.

• Where the installation fittings can be firmly installed.

• Where wind does not hinder the intake and outlet pipes.

• Out of the heat range of other heat sources.

• A place where stringent regulation of electric noises is applicable.

• Where it is safe for the drain water to be discharged.

• Where noise and hot air will not bother neighboring residents.

• Where snow will not accumulate.

• Where strong winds will not blow against the outlet pipe.

• A place where no TV set or radio receiver is placed within 1m.

(If electrical interference is caused, seek a place less likely to cause the problem)

• If a operation is conducted when the outdoor air temperature is –5 C lower, the outdoor unit should be

installed at a place where it is not influenced by natural wind.

• Where it is likely that the unit is subjected to strong winds, provide wind guards according to the

following guidelines. Strong winds can cause performance degradation, an accidental stop due to a rise of

high pressure and a broken fan.

2. REFRIGERANT PIPING WORK

1) Restrictions on unit installation and use

2) Determination of pipe size

15m or less

10m or less

10m or less

L

H

H

L

H

Outdoor unit

Indoor unit

The use restrictions appearing in the table above are applicable to the standard pipe size combinations shown in the table below.

Restrictions

Model 09, 12

Marks appearing in the

drawing on the right

Main pipe length

When the outdoor unit is positioned higher,

When the outdoor unit is positioned lower,

Elevation difference between

indoor and outdoor units

Plug the end of the pipe with tape, or other

material, and fill the pipe with nitrogen gas.

Only use nitrogen gas (N

2

)

Taping

<N2>

Ni

tro

ge

n

Brazing

Station valve

Primary side

Secondary side

0.5MPa

Hand

Relief valve

Nitrogen

gas

Brazing must be performed under a nitrogen gas flow.

About brazing

When pipe is brazing.

4) Caution about selection of installation location

• Walls surrounding the unit in the four sides are not

acceptable.

• There must be a 1-meter or larger space in the above.

• When more than one unit are installed side by side,

provide a 250mm or wider interval between them as a

service space. In order to facilitate servicing of

controllers, please provide a sufficient space between

units so that their top plates can be removed easily.

• Where a danger of short-circuiting exists, install guide

louvers.

• When more than one unit are installed, provide sufficient

intake space consciously so that short-circuiting may not

occur.

• Where piling snow can bury the outdoor unit, provide

proper snow guards.

• In installing the unit, fix the unit’s legs with bolts specified on the left.

• The protrusion of an anchor bolt on the front side must be kept within 15mm.

• Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.

• Refer to the above illustrations for information regarding concrete foundations.

• Install the unit in a level area. (With a gradient of 5mm or less.) Improper installation can result in a

compressor failure, broken piping within the unit and abnormal noise generation.

1 Anchor bolt fixed position

2 Notabilia for installation

(2) If the unit can be affected by strong wind, following measures are required.

Strong wind can cause damage of fan (fan motor), or can cause performance degradation, or can trigger

anomalous stop of the unit due to rising of high pressure.

1 Place the unit outlet pipe perpendicular to the

wind direction.

2 Install so the direction of the air from the

blowing outlet will be perpendicular to the

direction of the wind.

Wind

direction

Wind

direction

• Check the following points in light of the indoor unit specifications and the installation site.

• Observe the following restrictions on unit installation and use. Improper installation can result in a compressor failure or performance degradation.

• Additional refrigerant charge is not required at all (Model 09, 12).

25m or less

15m or less

15m or less

Dimensional restrictions

Model 18

ø12.7

Flare

ø12.7

ø12.7

Gas pipe

ø6.35

Flare

ø6.35

ø6.35

Model 18

Liquid pipe

ø9.52

Flare

ø9.52

ø9.52

Gas pipe

ø6.35

Flare

ø6.35

ø6.35

Model 09, 12

Liquid pipe

Outdoor unit connected

Refrigerant piping (branch pipe L)

Indoor unit connected

Notabilia as a unit designed for R410A

• Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant.

A cylinder containing R410A has a pink indication mark on the top.

• A unit designed for R410A has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.

The processed dimension of the flared part of a refrigerant pipe and a flare nut’s parallel side measurement have also been altered to raise strength against pressure.

Accordingly, you are required to arrange dedicated R410A tools listed in the table on the right before installing or servicing this unit.

• Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to change, which results in performance degradation.

• In charging refrigerant, always take it out from a cylinder in the liquid phase.

• All indoor units must be models designed exclusively for R410A. Check connectable indoor unit models in a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)

CAUTION

• Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation work in order

to protect yourself.

• The precautionary items mentioned below are distinguished into two levels,

and

.

: Wrong installation would cause serious consequences such as injuries or death.
: Wrong installation might cause serious consequences depending on circumstances.

Both mentions the important items to protect your health and safety so strictly follow them by any means.

• Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the

operating methods as well as the maintenance methods of this equipment to the user according to the owner’s
manual.

• Keep the installation manual together with owner’s manual at a place where any user can read at any time.

Moreover if necessary, ask to hand them to a new user.

• For installing qualified personnel, take precautions in respect to themselves by using suitable protective

clothing, groves, etc., and then perform the installation works.

• Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
• If unusual noise can be heard during operation, consult the dealer.
• The meanings of “Marks” used here are shown as follows:

• This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to the respective installation manuals supplied with the units.
• When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power

supply voltage and etc.) and installation spaces.

SAFETY PRECAUTIONS

WARNING

Never do it under any circumstances.

Always do it according to the instruction.

CAUTION

WARNING

CAUTION

WARNING

CAUTION

• Carry out the electrical work for ground lead with care.

Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting.

• Installation must be carried out by the qualified installer.

If you install the system by yourself, it may cause serious trouble such as water leaks,

electric shocks, fire and personal injury, as a result of a system malfunction. Do not

carry out the installation and maintenance work except the by qualified installer.

• Install the system in full accordance with the installation manual.

Incorrect installation may cause bursts, personal injury, water leaks, electric

shocks and fire.

• Be sure to use only for household and residence.

If this appliance is installed in inferior environment such as machine shop and etc.,

it can cause malfunction.

• When installing in small rooms, take prevention measures not to

exceed the density limit of refrigerant in the event of leakage, referred

by the formula (accordance with ISO5149).

If the density of refrigerant exceeds the limit, please consult the dealer and install

the ventilation system, otherwise lack of oxygen can occur, which can cause serious

accident.

• Use the original accessories and the specified components for

installation.

If parts other than those prescribed by us are used, It may cause water leaks,

electric shocks, fire and personal injury.

• Install the unit in a location with good support.

Unsuitable installation locations can cause the unit to fall and cause material

damage and personal injury.

• Ensure the unit is stable when installed, so that it can withstand

earthquakes and strong winds.

Unsuitable installation locations can cause the unit to fall and cause material

damage and personal injury.

• Ventilate the working area well in the event of refrigerant leakage during

installation.

If the refrigerant comes into contact with naked flames, poisonous gas is produced.

• Use the prescribed pipes, flare nuts and tools for R410A.

Using existing parts (for R22 or R407C) can cause the unit failure and serious

accidents due to burst of the refrigerant circuit.

• Tighten the flare nut by torque wrench with specified method.

If the flare nut were tightened with excess torque, this may cause burst and

refrigerant leakage after a long period.

• Do not open the operation valves for liquid line and gas line until

completed refrigerant piping work, air tightness test and evacuation.

If the compressor is operated in state of opening operation valves before

completed connection of refrigerant piping work, air can be sucked into refrigerant

circuit, which can cause bust or personal injury due to anomalously high pressure

in the refrigerant.

• The electrical installation must be carried out by the qualified electrician

in accordance with “the norm for electrical work” and “national wiring

regulation”, and the system must be connected to the dedicated circuit.

Power supply with insufficient capacity and incorrect function done by improper

work can cause electric shocks and fire.

• Be sure to shut off the power before starting electrical work.

Failure to shut off the power can cause electric shocks, unit failure or incorrect

function of equipment.

• Be sure to use the cables conformed to safety standard and cable

ampacity for power distribution work.

Unconformable cables can cause electric leak, anomalous heat production or fire.

• This appliance must be connected to main power supply by means of a

circuit breaker or switch (fuse:16A) with a contact separation of at least

3mm.

• Arrange the wiring in the control box so that it cannot be pushed up

further into the box. Install the service panel correctly.

Incorrect installation may result in overheating and fire.

• Use the prescribed cables for electrical connection, tighten the cables

securely in terminal block and relieve the cables correctly to prevent

overloading the terminal blocks.

Loose connections or cable mountings can cause anomalous heat production or fire.

• Be sure to fix up the service panels.

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.

• Be sure to switch off the power supply in the event of installation,

inspection or servicing.

If the power supply is not shut off, there is a risk of electric shocks, unit failure or

personal injury due to the unexpected start of fan.

• Stop the compressor before removing the pipe after shutting the

service valve on pump down work.

If the pipe is removed when the compressor is in operation with the service valve

open, air would be mixed in the refrigeration circuit and it could cause explosion

and injuries due to abnormal high pressure in the cooling cycle.

• Only use prescribed optional parts. The installation must be carried out

by the qualified installer.

If you install the system by yourself, it can cause serious trouble such as water

leaks, electric shocks, fire.

• Be sure to wear protective goggles and gloves while at work.

• Earth leakage breaker must be installed.

If the earth leakage breaker is not installed, it can cause electric shocks.

• Ensure that no air enters in the refrigerant circuit when the unit is

installed and removed.

If air enters in the refrigerant circuit, the pressure in the refrigerant circuit

becomes too high, which can cause burst and personal injury.

• Do not processing, splice the power cord, or share a socket with other power plugs.

This may cause fire or electric shock due to defecting contact, defecting insulation

and over-current etc.

• Do not bundling, winding or processing for the power cord. Or, do not

deforming the power plug due to tread it.

This may cause fire or heating.

• Do not run the unit with removed panels or protections.

Touching rotating equipments, hot surfaces or high voltage parts can cause

personal injury due to entrapment, burn or electric shocks.

• Do not perform any change of protective device itself or its setup

condition.

The forced operation by short-circuiting protective device of pressure switch and

temperature controller or the use of non specified component can cause fire or

burst.

• Use the circuit breaker for all pole correct capacity. Circuit breaker

should be the one that disconnect all poles under over current.

Using the incorrect circuit breaker, it can cause the unit malfunction and fire.

• Install isolator or disconnect switch on the power supply wiring in

accordance with the local codes and regulations.

The isolator should be locked in OFF state in accordance with EN60204-1.

• After maintenance, all wiring, wiring ties and the like, should be returned

to their original state and wiring route, and the necessary clearance from

all metal parts should be secured.

• Secure a space for installation, inspection and maintenance specified in

the manual.

Insufficient space can result in accident such as personal injury due to falling from

the installation place.

• Take care when carrying the unit by hand.

If the unit weights more than 20kg, it must be carried by two or more persons. Do

not carry by the plastic straps, always use the carry handle when carrying the unit

by hand. Use gloves to minimize the risk of cuts by the aluminum fins.

• Dispose of any packing materials correctly.

Any remaining packing materials can cause personal injury as it contains nails and

wood. And to avoid danger of suffocation, be sure to keep the plastic wrapper

away from children and to dispose after tear it up.

• Be sure to insulate the refrigerant pipes so as not to condense the

ambient air moisture on them.

Insufficient insulation can cause condensation, which can lead to moisture

damage on the ceiling, floor, furniture and any other valuables.

• When perform the air conditioner operation (cooling or drying operation)

in which ventilator is installed in the room. In this case, using the air

conditioner in parallel with the ventilator, there is the possibility that

drain water may backflow in accordance with the room lapse into the

negative pressure status. Therefore, set up the opening port such as

incorporate the air into the room that may appropriate to ventilation (For

example; Open the door a little). In addition, just as above, so set up the

opening port if the room lapse into negative pressure status due to

register of the wind for the high rise apartment etc.

• Do not install the unit in the locations listed below.

•Locations where carbon fiber, metal powder or any powder is floating.

•Locations where any substances that can affect the unit such as sulphide gas,

chloride gas, acid and alkaline can occur.

•Vehicles and ships.

•Locations where cosmetic or special sprays are often used.

•Locations with direct exposure of oil mist and steam such as kitchen and

machine plant.

•Locations where any machines which generate high frequency harmonics are

used.

•Locations with salty atmospheres such as coastlines.

•Locations with heavy snow (If installed, be sure to provide base flame and snow

hood mentioned in the manual).

•Locations where the unit is exposed to chimney smoke.

•Locations at high altitude (more than 1000m high).

•Locations with ammonic atmospheres.

•Locations where heat radiation from other heat source can affect the unit.

•Locations without good air circulation.

•Locations with any obstacles which can prevent inlet and outlet air of the unit.

•Locations where short circuit of air can occur (in case of multiple units

installation).

•Locations where strong air blows against the air outlet of outdoor unit.

•Locations where something located above the unit could fall.

It can cause remarkable decrease in performance, corrosion and damage of

components, malfunction and fire.

• Do not install the outdoor unit in the locations listed below.

Locations where discharged hot air or operating sound of the outdoor unit can

bother neighborhood.

Locations where outlet air of the outdoor unit blows directly to an animal or

plants. The outlet air can affect adversely to the plant etc.

Locations where vibration can be amplified and transmitted due to insufficient

strength of structure.

Locations where vibration and operation sound generated by the outdoor unit

can affect seriously (on the wall or at the place near bed room).

Locations where an equipment affected by high harmonics is placed (TV set or

radio receiver is placed within 1m).

Locations where drainage cannot run off safely.

It can affect surrounding environment and cause a claim.

• Do not install the unit near the location where leakage of combustible

gases can occur.

If leaked gases accumulate around the unit, it can cause fire.

• Do not install the unit where corrosive gas (such as sulfurous acid gas etc.)

or combustible gas (such as thinner and petroleum gases) can accumulate

or collect, or where volatile combustible substances are handled.

Corrosive gas can cause corrosion of heat exchanger, breakage of plastic parts

and etc. And combustible gas can cause fire.

• Do not install nor use the system close to the equipment that generates

electromagnetic fields or high frequency harmonics.

Equipment such as inverters, standby generators, medical high frequency

equipments and telecommunication equipments can affect the system, and cause

malfunctions and breakdowns. The system can also affect medical equipment and

telecommunication equipment, and obstruct its function or cause jamming.

Do not install the outdoor unit in a location where insects and small

animals can inhabit.

Insects and small animals can enter the electric parts and cause damage or fire.

Instruct the user to keep the surroundings clean.

Do not use the base flame for outdoor unit which is corroded or damaged

due to long periods of operation.

Using an old and damage base flame can cause the unit falling down and cause

personal injury.

Do not use any materials other than a fuse with the correct rating in the

location where fuses are to be used.

Connecting the circuit with copper wire or other metal thread can cause unit

failure and fire.

Do not touch any buttons with wet hands.

It can cause electric shocks.

Do not touch any refrigerant pipes with your hands when the system is in

operation.

During operation the refrigerant pipes become extremely hot or extremely cold

depending the operating condition, and it can cause burn injury or frost injury.

Do not touch the suction or aluminum fin on the outdoor unit.

This may cause injury.

Do not put anything on the outdoor unit and operating unit.

This may cause damage the objects or injury due to falling to the object.

Do not use the unit for special purposes such as storing foods, cooling

precision instruments and preservation of animals, plants or art.

Do not clean up the unit with water.

Over 500mm

a

Wires for connecting indoor

and outdoor units

Exterior tape

Gas piping

Insulation

Liquid piping

Band (accessory)

Pipe cover (accessory)

8) Heating and condensation prevention

Take care so that installed pipes may not touch components within a unit.

If touching with an internal component, it will generate abnormal sounds and/or vibrations.

4) On-site piping work

IMPORTANT

How to remove the side cover

Please remove the screw of a side cover and

remove to the front.

A

B

Flared pipe end : A

(mm)

ø6.35
ø9.52
ø12.7

Copper pipe

outer diameter

0

A –04

9.1

13.2
16.6

ø6.35
ø9.52
ø12.7

Copper pipe

outer diameter

0

~

0.5

1.0

~

1.5

Copper pipe protrusion for flaring : B

(mm)

In the case of a rigid (clutch) type

With an R410A tool With a conventional tool

CAUTION

Do not apply force beyond proper fastening torque in tightening the flare nut.

Tightening angle ( )

Tightening torque (N·m)

ø6.35 (1/4")
ø9.52 (3/8")
ø12.7 (1/2")

Recommended length of a tool handle (mm)

Operation valve size (mm)

5) Air tightness test

Gas side

operation valve
Check joint

Pre

ssu

rize

Cl

os

e

Outdoor unit

Indoor unit

<Work flow>

6) Evacuation

Pay attention to the following points in addition to the above for the R410A and compatible machines.

Air tightness test completed

Fill refrigerant

Vacuum gauge check

Vacuuming completed

Vacuuming begins

Do not hold the valve cap area with a spanner.

3) Refrigerant pipe wall thickness and material

NOTE

*Phosphorus deoxidized seamless copper pipe ICS 23.040.15, ICS 77.150.30

ø6.35

0.8

O-type pipe

ø9.52

0.8

O-type pipe

ø12.7

0.8

O-type pipe

Pipe diameter [mm]

Minimum pipe wall thickness [mm]

Pipe material*

• Select refrigerant pipes of the table shown on the right wall thickness and

material as specified for each pipe size.

Although outdoor and indoor units themselves have been tested for air tightness at the factory, check the connecting pipes after the installation work for air tightness

from the operation valve’s check joint equipped on the outdoor unit side. While conducting a test, keep the operation valve shut all the time.

a) Raise the pressure to 0.5MPa, and then stop. Leave it for five minutes to see if the pressure drops.

b) Then raise the pressure to 1.5MPa, and stop. Leave it for five more minutes to see if the pressure drops.

c) Then raise the pressure to the specified level (4.15MPa), and record the ambient temperature and the pressure.

d) If no pressure drop is observed with an installation pressurized to the specified level and left for about one day, it is acceptable. When the ambient temperature fall

1 C, the pressure also fall approximately 0.01MPa. The pressure, if changed, should be compensated for.

e) If a pressure drop is observed in checking e) and a) – d), a leak exists somewhere. Find a leak by applying bubble test liquid to welded parts and flare joints and

repair it. After repair, conduct an air tightness test again.

In conducting an air tightness test, use nitrogen gas and pressurize the system with nitrogen gas from the gas side. Do not use a medium other than nitrogen gas

under any circumstances.

• Carry out the on site piping work with the operation valve fully closed.

• Give sufficient protection to a pipe end (compressed and blazed, or with an

adhesive tape) so that water or foreign matters may not enter the piping.

• Bend a pipe to a radius as large as practical (R100~R150). Do not bend a pipe

repeatedly to correct its form.

• Flare connection is used between the unit and refrigerant pipe. Flare a pipe after

engaging a flare nut onto it. Flare dimensions for R410A are different from

those for conventional R407C. Although we recommend the use of flaring tools

designed specifically for R410A, conventional flaring tools can also be used by

adjusting the measurement of protrusion B with a protrusion control gauge.

• The pipe should be anchored every 1.5m or less to isolate the vibration.

• Tighten a flare joint securely.

• To prevent a different oil from entering, assign dedicated tools, etc. to each refrigerant type. Under no circumstances must a

gauge manifold and a charge hose in particular be shared with other refrigerant types (R22, R407C, etc.).

• Use a counterflow prevention adapter to prevent vacuum pump oil from entering the refrigerant system.

Put down the refrigerant volume calculated from the pipe length onto the caution label attached

on the service panel.

• This

 

unit

 

contains factory charged refrigerant covering 15m of refrigerant piping and additional refrigerant

charge on the installation site is not required for an installation with up to 15m refrigerant piping.

When refrigerant piping exceeds 15m, additionally charge an amount calculated from the pipe length and

the above table for the portion in excess of 15m.

* When an additional charge volume calculation result is negative, it is not necessary to charge refrigerant

additionally.

• For an installation measuring 15m or shorter in pipe length, please charge the refrigerant volume charged

for shipment at the factory, when you recharge refrigerant after servicing etc.

Fix both liquid and gas operation valves at the valve main bodies as illustrated on the right, and then fasten them,

applying appropriate fastening torque.

Select pipes having a wall thickness larger than the specified

minimum pipe thickness.

14

~

18

34

~

42

49

~

61

45

~

60

30

~

45

30

~

45

150
200
250

Use a torque wrench. If a torque wrench is not

available, fasten the flare nut manually first and then

tighten it further, using the left table as a guide.

1

2

Run the vacuum pump for at least one hour after the vacuum

gauge shows –0.1MPa or lower. (–76cmHg or lower)

When the system has remaining moisture

inside or a leaky point, the vacuum gauge

indicator will rise.

Check the system for a leaky point and

then draw air to create a vacuum again.

Confirm that the vacuum gauge indicator does not rise even if

the system is left for one hour or more.

(three-way valve)

Charge hose (Designed specifically for R410A)

Compound pressure gauge
Pressure gauge
Gauge manifold

(Designed specifically for R410A)
Handle Hi

Vacuum pump

Vacuum pump adapter

(Anti-reverse flow type)

(Designed specifically for R410A)

Charge hose

(Designed specifically for R410A)

Check joint

-0.1MPa

(-76cmHg)

Handle Lo

Operation valve

Operation valve

(two-way valve)

Operation valve cap

Operation valve cap

Operation valve cap

tightening torque (N·m)

Check joint blind nut

tightening torque (N·m)

ø6.35 (1/4")
ø9.52 (3/8")
ø12.7 (1/2")

20

~

30

25

~

35

10

~

12

Operation valve size

(mm)

Securely tighten the operation valve cap and the check joint blind nut after adjustment.

(1) Dress refrigerant pipes (both gas and liquid pipes) for heat insulation and prevention of dew condensation.

• Improper heat insulation/anti-dew dressing can result in a water leak or dripping causing damage to household effects, etc.

(2) Use a heat insulating material that can withstand 120 C or a higher temperature. Poor heat insulating capacity can cause heat insulation problems or cable

deterioration.

• All gas pipes must be securely heat insulated in order to prevent damage from dripping water that comes from the condensation formed on them during a cooling

operation or personal injury from burns because their surface can reach quite a high temperature due to discharged gas flowing inside during a heating operation.

• Wrap indoor units’ flare joints with heat insulating parts (pipe cover) for heat insulation (both gas and liquid pipes).

• Give heat insulation to both gas and liquid side pipes. Bundle a heat insulating material and a pipe tightly together so that no gaps may be left between them and

wrap them together with a connecting cable by a dressing tape.

• Both gas and liquid pipes need to be dressed with 20mm or thicker heat insulation materials above the ceiling where relative humidity exceeds 70%.

(1) Calculate a required refrigerant charge volume from the following table.

• Since R410A refrigerant must be charged in the liquid phase, you should charge it, keeping the container

cylinder upside down or using a refrigerant cylinder equipped with a siphon tube.

• Charge refrigerant always from the liquid side service port with the operation valve shut. When you find it

difficult to charge a required amount, fully open the outdoor unit valves on both liquid and gas sides and

charge refrigerant from the gas (suction) side service port, while running the unit in the cooling mode. In

doing so, care must be taken so that refrigerant may be discharged from the cylinder in the liquid phase

all the time. When the cylinder valve is throttled down or a dedicated conversion tool to change liquid

phase refrigerant into mist is used to protect the compressor, however, adjust charge conditions so that

refrigerant will gasify upon entering the unit.

• In charging refrigerant, always charge a calculated volume by using a scale to measure the charge

volume.

• When refrigerant is charged with the unit being run, complete a charge operation within 30minutes.

Running the unit with an insufficient quantity of refrigerant for a long time can cause a compressor failure.

(2) Charging refrigerant

Formula to calculate the volume of additional refrigerant required

7) Additional refrigerant charge (Model 18)

Additional charge volume (kg) = { Main length (m) – Factory charged volume 15 (m) } x 0.02 (kg/m)

0.02

1.35

15

Model 18

NOTE

Additional charge volume (kg)

per meter of refrigerant piping

(liquid pipe ø6.35)

Refrigerant volume charged

for shipment at the factory

(kg)

Installation’s pipe length (m)

covered without additional

refrigerant charge

Clearance

3. DRAIN PIPING WORK

• Execute drain piping by using a drain elbow and drain

grommets supplied separately as optional parts, where

water drained from the outdoor unit is a problem.

• Water may drip where there is a larger amount of drain

water. Seal around the drain elbow and drain

grommets with putty or adequate caulking material.

• Condensed water may flow out from vicinity of

operation valve or connected pipes.

• Where you are likely to have several days of sub-zero

temperatures in a row, do not use a drain elbow and

drain grommets. (There is a risk of drain water freezing

inside and blocking the drain.)

• When condensed water needs to be led to a drain, etc., install

the unit on a flat base (supplied separately as an optional part)

or concrete blocks.

Then, please secure space for the drain elbow and the drain

hose.

Drain elbow

Grommet

Drain hose

(To be procured on the installer’s part)

Do not put a grommet on

this hole.

This is a supplementary

drain hole to discharge

drain water, when a large

quantity of it is gathered.

Model 09, 12

Drain elbow

Grommet

Drain hose

(To be procured on the installer’s part)

Model 18

Cable name plate

Power supply terminal block

Grounding terminal

Cable clamp

4. ELECTRICAL WIRING WORK

For details of electrical cabling, refer to the indoor unit installation manual.

CAUTION

Always use an earth leakage circuit breaker designed for inverter circuits to

prevent a faulty operation.

Outdoor unit

Switchgear or Circuit breaker

1

1

2/N

2/N

3

1 2/N 3

Indoor unit

Interconnecting and

grounding wires

(minimum)

09
12
18

Switch breaker

Over current protector

rated capacity

Power source

(minimum)

Model

15A, 30mA,

0.1sec or less

30A

16A

2.0mm

2

1.5mm

2

X 4

Earth leakage breaker

Phase

Single-phase

INSTALLATION TEST CHECK POINTS

After installation

Check the following points again after completion of the installation, and before turning on the power. Conduct a test run again and ensure that the unit operates properly.

Explain to the customer how to use the unit and how to take care of the unit following the instruction manual.

In case of faulty wiring connection, the indoor unit stops,

and then the run lamp turns on and the timer lamp blinks.

Use cables for interconnection wiring to avoid loosening of the wires.

CENELEC code for cables Required field cables.

H

05

R

N

R

4or5

G

1.5

Harmonized cable type

300/500 volts

Natural-and/or synth. rubber wire insulation

Polychloroprene rubber conductors insulation

Stranded core

Number of conductors

One conductor of the cable is the earth conductor

(yellow/green)

Section of copper wire (mm

2

)

Power cables and connecting wires are securely fixed to the terminal block.
The power supply voltage is correct as the rating.
The drain hose is fixed securely.
Operation valve is fully open.
No gas leaks from the joints of the operation valve.

The pipe joints for indoor and outdoor pipes have been insulated.
The reverse flow check cap is attached.
The cover of the pipe cover (A) faces downward to prevent rain from entering.
Gaps are properly sealed between the pipe covers (A) (B) and the wall surface / pipes.

H05RNR4G1.5 (Example) or 245IEC57

Electrical installation work must be performed by an electrical installation service provider qualified by a power provider of the country.

Electrical installation work must be executed according to the technical standards and other regulations applicable to electrical installations in the country.

• Do not use any supply cord lighter than one specified in parentheses for each type below.

• braided cord (code designation 60245 IEC 51)

• ordinary tough rubber sheathed cord (code designation 60245 IEC 53)

• flat twin tinsel cord (code designation 60227 IEC 41)

Use polychloroprene sheathed flexible cord (code designation 60245 IEC57) for supply cords of parts of appliances for outdoor use.

• Ground the unit. Do not connect the grounding wire to a gas pipe, water pipe, lightning rod or telephone grounding wire.

If improperly grounded, an electric shock or malfunction may result.

• A grounding wire must be connected before connecting the power cable. Provide a grounding wire longer than the power cable.

• The installation of an impulse withstanding type earth leakage breaker is necessary. A failure to install an earth leakage breaker can result in an accident

such as an electric shock or a fire.

• Do not turn on the power until the electrical work is completed.

• Do not use a condensive capacitor for power factor improvement under any circumstances. (It dose not improve power factor, while it can cause an

abnormal overheat accident)

• For power supply cables, use conduits.

• Do not lay electronic control cables (remote control and signaling wires) and other cables together outside the unit. Laying them together can result in

the malfunctioning or a failure of the unit due to electric noises.

• Fasten cables so that may not touch the piping, etc.

• When cables are connected, make sure that all electrical components within the electrical component box are free of loose connector coupling or

terminal connection and then attach the cover securely. (Improper cover attachment can result in malfunctioning or a failure of the unit, if water

penetrates into the box.)

• Never use a shield cable.

Indoor - Outdoor

connecting wire

Power cable

Power cable, indoor - outdoor connecting wire circuit diagram

Power cable, indoor-outdoor connecting wires

• It holds cables in place and protect the

terminal connection from external force.

• This clamp is for the cable in the outside

diameter 9

~

15mm.

Please adjust it when not suitable.

• Please be sure to carry out D-type (type

III) grounding work.

• It has stuck on the lid of a control box.

Indoor - Outdoor

connecting wire

Please connect the earthed

line of indoor and outdoor

connecting wire to a bracket

part of the illustration.

Model 09, 12

Model 18

Model 09, 12

Model 18

Power cable

L

Outdoor unit

Switchgear or Circuit breaker

N

1 2/N 3

1 2/N 3

Indoor unit

Earth leakage breaker

(Harmonic resistant type)

Earth leakage breaker

(Harmonic resistant type)

Always perform grounding system installation work with the power cord unplugged.

Connect a pair bearing a common terminal number with an indoor-outdoor connecting wire.

In cabling, fasten cables securely with cable clamps so that no external force may work on terminal connections.

Grounding terminals are provided in the control box.

• The specifications shown in the above table are for units without heaters. For units with heaters, refer to the

installation instructions or the construction instructions of the indoor unit.

• Switchgear or Circuit breaker capacity which is calculated from MAX. over current should be chosen along the

regulations in each country.

• The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than

three cables contained in a conduit and a voltage drop is 2%. For an installation falling outside of these

conditions, please follow the internal cabling regulations. Adapt it to the regulation in effect in each country.

Switchgear or Circuit Breaker

CAUTION

CAUTION

CAUTION

The screw of the side cover is tightened securely.

The screw of the

side cover is

tightened securely.

Side cover

Содержание DXK09ZJ-S

Страница 1: ...ESIDENTIAL AIR CONDITIONING TECHNICAL MANUAL PARTS LIST INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONER Split system air to air heat pump type DXK09ZJ S DXK12ZJ S DXK18ZJ S Manual No 11 SRK T 118 ...

Страница 2: ......

Страница 3: ...TECHNICAL MANUAL ...

Страница 4: ... operation 43 40 1 Operation control function by remote controller 5 Flap and louver control 41 4 Custom cord switching procedure 40 3 Auto restart function 2 Unit ON OFF button 40 39 8 Installation location setting 43 9 Outline of heating operation 44 11 Outline of automatic operation 45 10 Outline of cooling operation 45 12 Protective control function 46 53 10 MAINTENANCE DATA 54 4 Troubleshooti...

Страница 5: ...tion procedures corresponding to detail of trouble 64 9 Checking the indoor electrical equipment 69 11 1 Instullation of wired remote controller RC E4 74 11 OPTION PARTS 74 11 2 Interface kit SC BIKN E 80 11 3 Super link E board SC ADNA E 84 How to read the model name Example DXK 09 Z Series code Inveter type Product capacity Model name DXK Wall mounted type DXC Outdoor unit J S ...

Страница 6: ...RFRPSXWHU WKHUPRVWDW ዙ 2SHUDWLRQ LVSOD 581 UHHQ 7 0 5 HOORZ 32 5 UHHQ 872 UHHQ 6DIHW GHYLFHV RPSUHVVRU RYHUKHDW SURWHFWLRQ 2YHUFXUUHQW SURWHFWLRQ URVW SURWHFWLRQ 6HULDO VLJQDO HUURU SURWHFWLRQ QGRRU IDQ PRWRU HUURU SURWHFWLRQ HDWLQJ RYHUORDG SURWHFWLRQ LJK SUHVVXUH FRQWURO RROLQJ RYHUORDG SURWHFWLRQ QVWDOODWLRQ 5HIULJHUDQW SLSLQJ VL H 2 PP LTXLG OLQH Ǿ DV OLQH Ǿ FRQQHFWLQJ PHWKRG P ODUH FRQQHFWLQJ...

Страница 7: ...5 HOORZ 32 5 UHHQ 872 UHHQ 6DIHW GHYLFHV RPSUHVVRU RYHUKHDW SURWHFWLRQ 2YHUFXUUHQW SURWHFWLRQ URVW SURWHFWLRQ 6HULDO VLJQDO HUURU SURWHFWLRQ QGRRU IDQ PRWRU HUURU SURWHFWLRQ HDWLQJ RYHUORDG SURWHFWLRQ LJK SUHVVXUH FRQWURO RROLQJ RYHUORDG SURWHFWLRQ QVWDOODWLRQ 5HIULJHUDQW SLSLQJ VL H 2 PP LTXLG OLQH Ǿ DV OLQH Ǿ FRQQHFWLQJ PHWKRG P ODUH FRQQHFWLQJ ዙ LTXLG OLQH DV LQH QVXODWLRQ IRU SLSLQJ P 1HFHVVDU...

Страница 8: ...tric heater Operation control Operation switch Wireless Remote control Room temperature control Microcomputer thermostat Operation Display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green Safety devices Compressor overheat protection Overcurrent protection Frost protection Serial signal error protection Indoor fan motor error protection Heating overload protection High pressure control Cooling ...

Страница 9: ... piping 㧔Refer to the above view㧕 Hole on wall for right rear piping Hole on wall for left rear piping Gas piping Outlet for wiring Drain hose Liquid piping F E C D B Symbol A 㧔Ǿ65㧕 VP16 Ǿ6 35㧔1㧛4 㧕㧔Flare㧕 Content 㧔Ǿ65㧕 09 12 Ǿ9 52㧔3㧛8 㧕㧔Flare㧕 Outlet for piping㧔on both side㧕 G 18 Ǿ12 7㧔1㧛2 㧕㧔Flare㧕 Model Unit mm غ 120 19 60 150 17 3 G 790 60 14 5 45 31 60 45 798 294 229 3 45 60 9 100 106 5 585 10...

Страница 10: ...ounded by walls on the four sides 2 The unit must be fixed with anchor bolts An anchor bolt must not protrude more than 15mm 3 Where the unit is subject to strong winds lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction 4 Leave 1m or more space above the unit 5 A wall in front of the blower outlet must not exceed the units height 6 The model name...

Страница 11: ...Flare Notes 1 It must not be surrounded by walls on the four sides 2 The unit must be fixed with anchor bolts An anchor bolt must not protrude more the 15mm 3 Where the unit is subject to strong winds lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction 4 Leave 1m or more space above the unit 5 A wall in front of the blower outlet must not exceed t...

Страница 12: ... 11 SRK T 118 3 Remote controller a Wireless remote controller Unit mm 60 17 3 150 ...

Страница 13: ...kness 100 to 200m 0 5mm2 2 cores 0 75mm2 2 cores 1 25mm2 2 cores 2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y Sheath Upper cace Board Wiring Upper Lower Y X Tighten the screws after cutting off the thin part of screw mounting part Embedded mounting The peeling off length of sheath The peeling off length of sheath In...

Страница 14: ... 2 t o R AMP 2 HEAT EXCHANGER 5 FMI SMI LM1 LM2 F Va ThI Th2 Th3 T DS 㨪 㨪 Blue Black BK Red BL RD White WH Yellow㧛Green Y㧛G Color Mark Heat exch sensor Fan motor Room temp sensor Flap motor Diode stack DS Fuse F Connector CNE CNY FMI Terminal block T Description Item Varistor Va LM1 2 SMI Louver motor ThI Th2 3 Yellow Y Humidity sensor HD Power Source 1 Phase 220㧛230㧛240V 50Hz 3 ELECTRICAL WIRING ...

Страница 15: ... The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please follow the internal cabling regulations Adapt it to the regulation in effect in each country 9 2 0 32 1 5mm2 x 3 1 5mm2 12 09 MAX running current Power cable size 㧔m...

Страница 16: ... in each country The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2 For an installation falling outside of these conditions please follow the internal cabling regulations Adapt it to the regulation in effect in each country 14 2 0 18 1 5mm2 x 3 1 5mm2 3 1 2 N 18 M T2 T1 S BK WH R...

Страница 17: ...ressure Level dB standard 2 10 5 P a Mid Octave Band frequency Hz 1000 2000 4000 8000 63 125 250 500 Mid Octave Band frequency Hz Indoor Unit Model DXK09ZJ S Noise Level Cooling 34 dB A Heating 39 dB A Cooling Heating Condition ISO T1 JIS C9612 N70 N60 N50 N40 N30 N20 N70 N60 N50 N40 N30 N20 Outdoor Unit Model DXC09ZJ S Noise Level Cooling 48 dB A Heating 47 dB A Cooling Heating ISC10016 4 NOISE L...

Страница 18: ...Sound Pressure Level dB standard 2 10 5 P a Mid Octave Band frequency Hz 1000 2000 4000 8000 63 125 250 500 Mid Octave Band frequency Hz Indoor Unit Model DXK12ZJ S Noise Level Cooling 45 dB A Heating 42 dB A Cooling Heating Condition ISO T1 JIS C9612 N70 N60 N50 N40 N30 N20 Outdoor Unit Model DXC12ZJ S Noise Level Cooling 50 dB A Heating 50 dB A Cooling Heating N70 N60 N50 N40 N30 N20 ISC10016 ...

Страница 19: ...N50 N30 N40 N60 N70 N20 Sound Pressure Level dB standard 2 10 5 P a Mid Octave Band frequency Hz 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Indoor Unit Model DXK18ZJ S Noise Level Cooling 46 dB A Heating 45 dB A Cooling Heating Model DXK18ZJ S Outdoor Unit Model DXC18ZJ S Noise Level Cooling 51 dB A Heating 53 dB A Cooling Heating Condition ISO T1 JIS C9612 ...

Страница 20: ...sensor Th1 Th2 Gas TH2 Heat exchanger sensor TH1 EEV Capillary tube Heat exchanger Humidity sensor HD Model DXK18ZJ S Models DXK09ZJ S 12ZJ S Indoor unit Outdoor unit Flare connection Flare connection Liquid pipe φ Gas pipie φ Service valve Heat exchanger Heat exchanger sensor Electronic expansion valve Liquid Strainer Muffler Capillary tube Outdoor air temp sensor Muffler Muffler Compressor Accum...

Страница 21: ...rt Cooling operation Approximately 15 to 46 D B Heating operation Approximately 15 to 24 D B Refer to the selection chart Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows The net cooling and heating capacity can be obtained in the following way Net capacity Capacity shown on specication Correction factors as follows 1 Coefcient of cooling and he...

Страница 22: ...ing on outdoor heat exchanger during heating How to obtain the cooling and heating capacity Piping length m Cooling Heating 7 1 0 1 0 10 0 99 1 0 15 0 975 1 0 20 0 965 1 0 25 0 95 1 0 Air inlet temperature of DXK12ZJ S outdoor unit in CWB Adjustment coefficient 15 0 95 0 95 0 94 0 93 0 91 0 88 0 86 0 87 0 92 1 00 10 9 7 5 3 1 1 3 5 or more DXK12ZJ S 3300 3217 ...

Страница 23: ... 01 4 18 2 94 m3 min 6 WB 4 09 4 04 4 00 3 95 3 90 Hi 22 3 29 2 80 3 47 2 77 3 66 2 92 3 75 2 90 3 83 2 87 3 99 3 00 4 13 2 93 10 WB 4 35 4 31 4 28 4 22 4 18 10 1 24 3 21 2 76 3 39 2 73 3 59 2 90 3 69 2 87 3 77 2 85 3 93 2 98 4 07 2 91 15 WB 4 73 4 69 4 66 4 61 4 56 m3 min 26 3 13 2 72 3 31 2 70 3 52 2 86 3 62 2 85 3 70 2 82 3 87 2 96 4 02 2 89 20 WB 5 09 5 05 5 02 4 96 4 92 28 3 04 2 69 3 23 2 66...

Страница 24: ...re damage on the ceiling floor furniture and any other valuables When perform the air conditioner operation cooling or drying opera tion in which ventilator is installed in the room In this case using the air conditioner in parallel with the ventilator there is the possibility that drain water may backflow in accordance with the room lapse into the negative pressure status Therefore set up the ope...

Страница 25: ...st of the refrigerant circuit Tighten the flare nut by torque wrench with specified method If the flare nut were tightened with excess torque this may cause burst and refrigerant leakage after a long period The electrical installation must be carried out by the qualified electrician in accordance with the norm for electrical work and national wiring regulation and the system must be connected to t...

Страница 26: ...Please note that measurement B protrusion from the flaring block will vary depending on the type of a flare tool in use If a conventional flare tool is used please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value Clutch type flare tool for R410A Conventional R22 flare tool ø6 35 ø9 52 ø12 7 0 0 0 5 0 0 0 5 0 0 0 5 1 0 1 5 1 0...

Страница 27: ...ventional flare tool Please note that measurement B protrusion from the flaring block will vary depending on the type of a flare tool in use If a conventional flare tool is used please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value Clutch type flare tool for R410A Conventional R22 flare tool ø6 35 ø9 52 ø12 7 0 0 0 5 0 0 0 ...

Страница 28: ...g If the power supply is not shut off there is a risk of electric shocks unit failure or personal injury due to the unexpected start of fan Stop the compressor before removing the pipe after shutting the service valve on pump down work If the pipe is removed when the compressor is in operation with the service valve open air would be mixed in the refrigeration circuit and it could cause explosion ...

Страница 29: ...processing for the power cord Or do not deforming the power plug due to tread it This may cause fire or heating Do not run the unit with removed panels or protections Touching rotating equipments hot surfaces or high voltage parts can cause personal injury due to entrapment burn or electric shocks Do not perform any change of protective device itself or its setup condition The forced operation by ...

Страница 30: ...e and hot air will not bother neighboring residents 〇 Where snow will not accumulate 〇 Where strong winds will not blow against the outlet pipe 〇 A place where no TV set or radio receiver is placed within 5m If electrical interference is caused seek a place less likely to cause the problem 〇 If a operation is conducted when the outdoor air temperature is 5 lower the outdoor unit should be installe...

Страница 31: ... hold connec This cl diamet Please Please ground It has Groundi Cable cla 4 ELECTRICAL WIRING Take care so that installed pipes may not touch components within a unit If touching with an internal component it will generate abnormal sounds and or vibrations 4 On site piping work IMPORTANT How to remove the side cover Carry out the on site piping work with the operation valve fully closed Give suffi...

Страница 32: ...d for air tightness at the factory check the connecting pipes after the installation work for air tightness from the operation valve s check joint equipped on the outdoor unit side While conducting a test keep the operation valve shut all the time a Raise the pressure to 0 5 MPa and then stop Leave it for five minutes to see if the pressure drops b Then raise the pressure to 1 5 MPa and stop Leave...

Страница 33: ...ol box Grounding terminal Cable clamp Indoor Outdoor connecting wire Power cable Please connect the earthed line of indoor and outdoor connecting wire to a bracket part of the illustration power cable indoor outdoor connecting wire circuit diagram 4 ELECTRICAL WIRING WORK For details of electrical cabling refer to the indoor unit installation manual CAUTION CAUTION Power cable indoor outdoor conne...

Страница 34: ...de for cables Required field cables H 05 R N R 4or5 G 1 5 Harmonized cable type 300 500 volts Natural and or synth rubber wire insulation Polychloroprene rubber conductors insulation Stranded core Number of conductors One conductor of the cable is the earth conductor yellow green Section of copper wire mm2 Power cables and connecting wires are securely fixed to the terminal block The power supply ...

Страница 35: ...ompressor before removing the pipe after shutting the service valve on pump down work If the pipe is removed when the compressor is in operation with the service valve open air would be mixed in the refrigeration circuit and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle Only use prescribed optional parts The installation must be carried out by the qualifi...

Страница 36: ... Any remaining packing materials can cause personal injury as it contains nails and wood And to avoid danger of suffocation be sure to keep the plastic wrapper away from children and to dispose after tear it up Be sure to insulate the refrigerant pipes so as not to condense the ambient air moisture on them Insufficient insulation can cause condensation which can lead to moisture damage on the ceil...

Страница 37: ...erence between indoor and outdoor units Plug the end of the pipe with tape or other material and fill the pipe with nitrogen gas Only use nitrogen gas N2 Taping N2 Nitrogen Brazing Station valve Primary side Secondary side 0 5MPa Hand Relief valve Nitrogen gas Brazing must be performed under a nitrogen gas flow About brazing When pipe is brazing 4 Caution about selection of installation location W...

Страница 38: ... tool handle mm Operation valve size mm 5 Air tightness test Gas side operation valve Check joint Pressurize Close Outdoor unit Indoor unit Work flow 6 Evacuation Air tightness test completed Vacuuming completed Vacuuming begins Do not hold the valve cap area with a spanner 3 Refrigerant pipe wall thickness and material NOTE Phosphorus deoxidized seamless copper pipe ICS 23 040 15 ICS 77 150 30 ø6...

Страница 39: ...ness larger than the specified minimum pipe thickness 14 18 34 42 49 61 45 60 30 45 30 45 150 200 250 Use a torque wrench If a torque wrench is not available fasten the flare nut manually first and then tighten it further using the left table as a guide 1 2 Run the vacuum pump for at least one hour after the vacuum gauge shows 0 1MPa or lower 76cmHg or lower When the system has remaining moisture ...

Страница 40: ...external force may work on terminal connections Grounding terminals are provided in the control box Switchgear or Circuit Breaker CAUTION CAUTION CAUTION Wires for connecting indoor and outdoor units Exterior tape Gas piping Insulation Liquid piping Band accessory Pipe cover accessory 8 Heating and condensation prevention Pay attention to the following points in addition to the above for the R410A...

Страница 41: ... IEC57 for supply cords of parts of appliances for outdoor use Ground the unit Do not connect the grounding wire to a gas pipe water pipe lightning rod or telephone grounding wire If improperly grounded an electric shock or malfunction may result A grounding wire must be connected before connecting the power cable Provide a grounding wire longer than the power cable The installation of an impulse ...

Страница 42: ...N CLEAR button ACL switch This switch is for resetting microcomputer and setting time OFF TIMER button This button selects OFF TIMER operation TEMPERATURE button These buttons sets the indoor temperature These buttons are used for setting the current time and timer function as well This button cancels the ON timer OFF timer and SLEEP operation CANCEL button The above illustration shows all control...

Страница 43: ...peration b Details of operation 3 ޓ Auto restart function a b 1 2 4 ޓ Custom cord switching procedure a Modifying the indoor printed circuit board b Modifying the wireless remote controller 1 2 Cut Function operation mode Indoor temperature setting Fan speed Flap Louver Timer Switch Cooling Thermal dry Heating ...

Страница 44: ...ox 50 Approx 60 Approx 60 Angle of Flap from Horizontal Center installation Remote controller display Right end installation Left end installation Angle of Louver Left Approx 50 Left Approx 50 Left Approx 20 Left Approx 45 Center Left Approx 30 Right Approx 20 Center Right Approx 50 Right Approx 20 Left Approx 20 Center Right Approx 30 Right Approx 45 Right Approx 50 Louver stopped Swing Spot Wide...

Страница 45: ...p down Swing Heating Center Fixed Wide Fixed Flap Louver Cooling Heating Horizontal blowing Fixed Slant forwardl blowing Fixed Operation mode Indoor temp Setting temp 2 C Setting temp Indoor temp 2 C At heating At cooling Air flow direction contorol 2 C Setting temp Indoor temp 5 C 2 C Indoor temp Setting temp 5 C Indoor temp Setting temp 5 C Setting temp Indoor temp 5 C The control in 4 continues...

Страница 46: ...ng unit is running press the ON OFF button to stop 2 Press the AIR FLOW UP DOWN button and the AIR FLOW LEFT RIGHT button together for 5 seconds or more 3 Setting the air conditioning installation location 4 Press the ON OFF button Airflow range Airflow range Airflow range Left End Installation Center Installation Right End Installation Center Installation Right End Installation Left End Installat...

Страница 47: ...c d e a b 2 30 115rps 30 115rps 30 76rps 30 46rps DXK12ZJ S 23 106rps 23 106rps 23 78rps 23 50rps DXK18ZJ S 30 115rps 30 115rps 30 72rps 30 42rps DXK09ZJ S Model Fan speed Auto MED HI LO model 18 35 model 18 35 model 18 2 ޓ model 18 2 ޓ a b c e model 18 10 16 minutes and 50 seconds model 18 18 minutes 20 20 15 10 5 0 5 10 15 10 5 0 Outdoor air temperature Outdoor heat exchanger temperature 20 20 1...

Страница 48: ...ps 23 38rps DXK18ZJ S 20 74rps 20 74rps 20 55rps 20 34rps DXK09ZJ S Model Fan speed Auto MED HI LO 11 ޓ Outline of automatic operation a Determination of operation mode Heating Dehumidifying Cooling Indoor air temperature C Outdoor air temperature C A When both the indoor and the outdoor air temperatures are in the range A cooling or heating is switched depending on d e a b 2 model 18 2 ޓ model 18...

Страница 49: ...pressor running the lower limit 41 C or more 29 rps The lower limit of compressor command speed is set to 30 or 40 model 18 29 rps and even if the calculated result becomes lower than that after fuzzy calculation the speed is kept to 30 or 40 model 18 29 rps However when the thermo becomes OFF the speed is reduced to 0 rps b 1 2 3 c d 18 0 18 30 Heating Dehumidifying Indoor air temperature C Outdo...

Страница 50: ...30 rps the speed is kept to 50 44 30 rps However when the thermo becomes OFF the speed is Models 09 12 First time Since the second times Outdoor air temperature C A B C D Model 18 model 18 9ºC or 10ºC 9 16 19 10 Note 1 Value in are for the model 18 2 Detail of operation 3 Reset conditions c Cooling high pressure control 1 Purpose 2 Detector 3 Detail of operation 53 58 63 Outdoor heat exchanger tem...

Страница 51: ...the output speed obtained with the fuzzy calculation exceeds the upper limit the upper limit value is maintained The lower limit of compressor command speed is set to 40 rps and even if the calculated result becomes lower than that after fuzzy calculation the speed is kept to 40 rps However when the thermo becomes OFF the speed is reduced to 0 prs rps 3 Reset conditions e Heating high pressure con...

Страница 52: ...tion iii iv that after fuzzy calculation the speed is kept to 40 rps However when the thermo becomes OFF the speed is reduced to 0 prs rps a Operating conditions b Detail of operation When the outdoor air temperature TH2 is 11ºC or higher continues for 30 seconds while the compressor command speed other than 0 rps i ii iii iv Taking the upper limit of compressor command speed range at 78 rps if th...

Страница 53: ...ir temperature C a b 09 SRK DB 087D h Compressor overheat protection 1 Purpose 2 Detail of operation a Discharge pipe temperature C Example Fuzzy 90 100 110 b i Current safe 1 Purpose 2 Detail of operation j Current cut 1 Purpose 2 Detail of operation k Outdoor unit failure Cooling Heating Lower limit speed Item Model 3 ޓ Reset conditions When either of the following condition is satisfied a ޓ The...

Страница 54: ...Serial signal transmission error protection 1 Purpose 2 Detail of operation n Rotor lock o Outdoor fan motor protection p Outdoor fan control at low outdoor temperature Cooling 1 Operating conditions 2 Detail of operation 3 Reset conditions Heating 1 Operating conditions 2 Detail of operation 3 Reset conditions Outdoor temperature 10 C Outdoor temperature 10 C Outdoor fan a b a b a c model 50 0ºC ...

Страница 55: ...ion When the compressor has been turned OFF b When the conditions of 1 above are met the compressor stops Error stop occurs when the compressor has stopped 3 times within 60 minutes c When after meeting the conditions of a and b above the compressor speed indoor air temperature Th1 and indoor heat exchanger temperature Th2 have met the conditions in the following table for 5 minutes Compressor spe...

Страница 56: ...H YDOYH RSHQ 3 Troubleshooting procedure If the air conditioner does not run at all I WKH DLU FRQGLWLRQHU GRHV QRW UXQ DW DOO GLDJQRVH WKH WURXEOH XVLQJ WKH IROORZLQJ WURXEOHVKRRWLQJ SURFHGXUH I WKH DLU FRQGLWLRQHU LV UXQQLQJ EXW EUHDNV GRZQ SURFHHG WR WURXEOHVKRRWLQJ VWHS Important KHQ DOO WKH IROORZLQJ FRQGLWLRQV DUH PHW ZH VD WKDW WKH DLU FRQGLWLRQHU ZLOO QRW UXQ DW DOO D 7KH 581 OLJKW GRHV QRW...

Страница 57: ... 54 11 SRK T 118 09 SRK DB 087D 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 55 56 62 56 62 ...

Страница 58: ...rned on or when there is no signal for 7 minute 35 seconds or longer during operation the compressor is stopped Defective power supply Broken signal wire defective indoor outdoor PCB Error of signal transmission If the compressor motor s magnetic pole positions cannot be correctly detected when the compressor starts The air conditioner stops Defective compressor Open phase on compressor Defective ...

Страница 59: ... indoor unit Data are recorded for up to 5 previous occurrences Data which are older than the 5th previous occurrence are erased In addition data on the temperature of each sensor room temperature indoor heat exchanger outdoor heat exchanger outdoor air temperature discharge pipe remote controller information operation switching fan speed switching are recorded when trouble occurs so more detailed...

Страница 60: ...VZLWFKLQJ 0 872 2 0 872 LVSOD V WKH UHDVRQ IRU VWRSSLQJ GLVSOD LQ WKH SDVW HUURU FRGH LVSOD V WKH URRP WHPSHUDWXUH VHQVRU WHPSHUDWXUH DW WKH WLPH WKH HUURU FRGH ZDV GLVSOD HG LQ WKH SDVW LVSOD V WKH LQGRRU KHDW H FKDQJHU VHQVRU WHPSHUDWXUH DW WKH WLPH WKH HUURU FRGH ZDV GLVSOD HG LQ WKH SDVW LVSOD V WKH UHPRWH FRQWUROOHU LQIRUPDWLRQ DW WKH WLPH WKH HUURU FRGH ZDV GLVSOD HG LQ WKH SDVW LVSOD V WKH ...

Страница 61: ...on for the stop stop code 2 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 3 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 4 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 5 ...

Страница 62: ... sensor is abnormal 38 8 time flash Outdoor unit s fan motor is abnormal 48 8 time flash Current safe 58 8 time flash Connection lines between the indoor and outdoor units are faulty 61 1 time flash Serial transmission error 62 2 time flash Discharge pipe sensor is abnormal anomalous stop 39 9 time flash Rotor lock 60 OFF 5 times 3 times 3 times 3 times 2 times Number of flashes when in service mo...

Страница 63: ... controller information tables 2SHUDWLRQ VZLWFKLQJ RUN light Operation switching Display pattern when in service mode Operation switching when there is an abnormal stop 0 1 2 4 3 AUTO DRY COOL FAN HEAT DQ VSHHG VZLWFKLQJ TIMER light Fan speed switching Display pattern when in service mode Fan speed switching when there is an abnormal stop 0 2 3 4 6 7 AUTO HI MED LO HI POWER ECONO I QR GDWD DUH UHF...

Страница 64: ...26 16 6 6 16 26 36 46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 88 98 59 49 39 29 19 9 9 19 29 39 49 59 69 79 89 99 No does not sound I QR GDWD DUH UHFRUGHG HUURU FRGH LV QRUPDO WKH GLVSOD IRU HDFK VHQVRU EHFRPHV DV VKRZQ EHORZ Sensor name Room temperature sensor Indoor heat exchanger sensor Outdoor air temperature sensor Outdoor heat exch...

Страница 65: ...32 12 12 32 52 72 92 112 132 54 34 14 14 34 54 74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 118 138 No does not sound I QR GDWD DUH UHFRUGHG HUURU FRGH LV QRUPDO WKH GLVSOD IRU HDFK VHQVRU EHFRPHV DV VKRZQ EHORZ Sensor value displayed when the error code is normal 64ºC DPSOH LVFKDUJH SLSH WHPSHUDWXUH Q WKH FDVH RI GLVFKDUJH SLSH GDWD PXOWLSO WKH UHDGLQJ YDOXH E HORZ 0 5 se...

Страница 66: ... 63 11 SRK T 118 09 SRK DB 087D Service data record form 57 ...

Страница 67: ...70 0 10 Discharge pipe sensor temperature characteristics Indoor fan motor error Broken sensor wire connector poor connection 0 0 20 40 60 80 100 120 135 20 40 60 80 100 120 140 160 180 Temperature C Resistance k Defective fan motor connector poor connection defective indoor PCB 69 for the fan motor and indoor PCB check proc Power supply reset Is it normalized Malfunction by temporary noise Replac...

Страница 68: ...circuit Compressor output is open phase Outdoor PCB is faulty Service valve is closed EEV is faulty Compressor faulty Current safe stop Overload operation compressor lock overcharge 73 70 DXC09 12 1 703Ω U V V W U W or more at 20ºC DXC18 1 417Ω U V 1 392Ω V W 1 435Ω U W or more at 20ºC ...

Страница 69: ... 66 11 SRK T 118 09 SRK DB 087D Over heat of compressor Gas shortage defective discharge pipe sensor Error of signal transmission Wiring error including power cable defective indoor outdoor PCB 64 ...

Страница 70: ...age 65 Outdoor fan motor error Defective fan motor connector poor connection defective outdoor PCB See pages 73 for the fan motor and outdoor PCB check proc After making sure the fan motor and outdoor PCB are nor Power supply reset Is it normalized Malfunction by temporary noise Replace fan motor If the error persists after replacing the fan motor replace the outdoor PCB the fan motor and outdoor ...

Страница 71: ... Humidity sensor 1 Cooling Heating Humidity sensor operation Failure mode Control input circuit resding Air conditioning system operation See page 65 Note 1 DXK12 18ZJ S only 09 SRK DB 087D 9 Checking the indoor electrical equipment a Indoor PCB check procedure b Outdoor unit Is there voltage between terminal blocks and AC 220 230 240 V Indoor electrical components are normal Is the voltage betwee...

Страница 72: ... out 3 15 A YES YES YES NO NO NO b Indoor unit fan motor check procedure 1 Indoor PCB output check 2 Fan motor resistance check FMI DC15V Indoor PCB DC 308 336V DC several V 4 6 V CNU GND Blue Yellow White Black Red Heat exchanger sensor Cooling Heating Ourdoor air temperature sensor Cooling Heating Discharge pipe sensor All modes Measuring point Resistance when normal Measuring point Resistance w...

Страница 73: ...he compressor system burns wiring mistakes etc If no problems are found check the output of the power transistor 2 Output inspection procedure Disconnect the terminals for the compresseor If an output such as the one shown in the figure on the below can be measured the power transistor and the circuit board for the outdoor unit are normal Example RUN light ON TIMER light 2 time flash Measure in th...

Страница 74: ... 71 11 SRK T 118 09 SRK DB 087D 11 Outdoor unit inspection points DXC09ZJ S 12ZJ S 73 73 64 ...

Страница 75: ...l inspection 1 to 2 AC 220 230 240V 2 to 3 Normal if the voltage oscillates between DC 0 and approx 20V CAUTION HIGH VOLTAGE High voltage is produced in the control box Don t touch electrical parts in the control box for 5 minutes after the unit is stopped Color symbol L to N AC 220 230 240V Model DXC18ZJ S Outdoor unit M T2 T1 S BK WH RD V W U PCB ASSY MAIN M M R TRANSISTOR POWER CIRCUIT SWITCHIN...

Страница 76: ...DQ PRWRU HUURU LV GHWHFWHG GLDJQRVH ZKLFK RI WKH RXWGRRU XQLW IDQ PRWRU RU RXWGRRU 3 LV GHIHFWLYH LDJQRVH WKLV RQO DIWHU FRQ UPLQJ WKDW WKH LQGRRU XQLW LV QRUPDO 2XWGRRU 3 RXWSXW FKHFN 7XUQ RII WKH SRZHU LVFRQQHFW WKH RXWGRRU XQLW IDQ PRWRU FRQQHFWRU 1 1 KHQ WKH LQGRRU XQLW LV RSHUDWHG E LQVHUWLQJ WKH SRZHU VXSSO SOXJ DQG SUHVVLQJ 21 WKH EDFNXS VZLWFK IRU PRUH WKDQ VHFRQGV LI WKH YROWDJH RI SLQ 1R...

Страница 77: ...a nipper or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote controller co terminal block Connect the terminal of remote c with the terminal of indoor unit X X and Y are no polarity Wiring route is as shown in the rig depending on the pulling out dire The wiring inside the remote cont The sheath should be peeled off Th...

Страница 78: ...nnect the remote controller cord to the terminal block Connect the terminal of remote controller X Y with the terminal of indoor unit X Y X and Y are no polarity Wiring route is as shown in the right diagram depending on the pulling out direction The wiring inside the remote controller case should be within 0 3mm2 recommended to 0 5mm2 The sheath should be peeled off inside the remote controller c...

Страница 79: ...er three seconds The indication changes to FUNCTION SET 2 Press button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT by using button 5 Press SET button to fix 6 When UPPER LIMIT is selected valid during heating Press SET button to fix Indication example UPPER 26 C Displayed for two seconds After the ...

Страница 80: ...stop position in the four The louver can stop at any position In normal working indication indoor unit temperature is indicated instead of airflow Only the master remote controller can be indicated Heating preparation indication should not be indicated Temperature indication is by degree C Temperature indication is by degree F ON OFF button finished Start Stop air conditioner and press SET and MOD...

Страница 81: ...crease in return air temperature of indoor unit To be reset producing 1 5 C increase in return air temperature of indoor unit To be reset producing 2 0 C increase in return air temperature of indoor unit When heating thermostat is OFF to be operated with low fan speed or with ultra low fan speed in case of some models When heating thermostat is OFF to be operated with set fan speed When heating th...

Страница 82: ...he FUNCTION SET will be displayed Press SET button Selecct FUNCTION remote controller function or I U FUNCTION indoor unit function Operation message Function description setting description Function No Fixing button Finishing button 7 2 1 6 Starting button Previous screen button Indoor unit selection button Press SET button 6 DATA LOADING Indication with blinking Display is changed to 01 GRILLE S...

Страница 83: ... an electric shock fire and sersonal injury Warnings Warning Always go along these instruction Safety precautions Before use please read these Safety Precautions thoroughly before installation All the cautionary items mentioned below are important safety related items to be taken into consideration so be sure to observe them at all times Incorrect installation could lead to serious consequences su...

Страница 84: ...ly 1 3m from the indoor unit Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the punch outs for the connection cables running into the casing with cutter Recess the electrical box locally procured and connection cables in the wall Mount the lower casing of the interface to the elec...

Страница 85: ...re round cable Vinyl insulated wirevinyl sheathed cable for control It is available to operate the air conditioning unit and to monitor the operation status with the external control unit remote display by sending the input output signal through CNT connector on the indoor control PCB Connect a external remote control unit locally procured to CNT terminal In case of the pulse input switch OFF the ...

Страница 86: ...should be used for the wiring of wired remote controller C Maximum length of wiring is 600m If the length of wiring exceeds 100m change the size of cable as mentioned below 100m 200m 0 5mm2 x 2 core 300m or less 0 75mm2 x 2 core 400m or less 1 25mm2 x 2 core 600m or less 2 0mm2 x 2 core However cable size connecting to the terminal of wired remote controller should not exceed 0 5mm2 Accordingly if...

Страница 87: ... 84 11 SRK T 118 11 3 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...

Страница 88: ... 85 11 SRK T 118 ...

Страница 89: ... 86 11 SRK T 118 ...

Страница 90: ... 87 PARTS LIST INDOOR UNIT DXK09ZJ S DXK12ZJ S DXK18ZJ S OUTDOOR UNIT DXC09ZJ S DXC12ZJ S DXC18ZJ S ...

Страница 91: ... 88 CRAE0221 30 35 5 7 28 8 26 25 32 29 36 34 6 18 18 17 19 24 23 22 21 20 19 16 14 12 15 15 15 11 13 9 10 6 3 2 4 35 4 31 27 33 1 PANEL FAN ASSY ...

Страница 92: ...5 LOUVER 5 1 1 2 2 14 RLA129A009 PLATE CONNECTING L 1 1 1 1 2 15 RKW935C200 COLLAR 6 16 RLA129A013 BRACKET MOTOR L 1 1 1 1 2 17 RLA129A014 BRACKET MOTOR R 1 1 1 1 2 18 RKY144A004 CRANK C 2 1 1 1 2 19 SSA512T096 MOTOR STEPPING 2 1 1 1 2 20 21 RLA129A018 BOX ASSY GEAR 1 1 1 1 2 21 SSA512T049 MOTOR STEPPING 1 1 1 1 2 22 RKS504A100M HARNESS ASSY 1 1 1 1 2 FOR FLAP MOTOR 23 RKS504A100N HARNESS ASSY 1 1...

Страница 93: ... 90 CRAE0222 26 20 1 21 28 17 11 12 22 23 25 13 24 24 2 14 15 19 18 16 9 6 10 27 29 31 30 4 5 7 8 3 HEAT EXCH CONTROL ...

Страница 94: ...R BEND 1 14 SSA551A223F SENSOR ASSY 1 1 1 2 4 15 SSA561B702B BLOCK TERMINAL 1 1 1 2 2 T1 16 SSA554D183 KILLER NOISE 1 17 19 RLA505A001BN PWB ASSY 1 2 2 4 8 18 SSA555B050C VARISTOR 1 1 1 1 2 Z1 19 SSA564A132 FUSE CURRENT 1 1 1 1 2 F1 3 15A 20 RLA503A001 DISPLAY ASSY 1 1 1 2 4 21 RLA505A003 PWB ASSY DISPLAY 1 2 2 4 8 22 23 RLA132A008 LID ASSY CONTROL 1 22 RLA132A007 LID CONTROL 1 23 RLA132A005 COVER...

Страница 95: ... 92 CRAE0221 30 35 5 7 28 8 26 25 32 29 36 34 6 18 18 17 19 24 23 22 21 20 19 16 14 12 15 15 15 11 13 9 10 6 3 2 4 35 4 31 27 33 1 PANEL FAN ASSY ...

Страница 96: ...5 LOUVER 5 1 1 2 2 14 RLA129A009 PLATE CONNECTING L 1 1 1 1 2 15 RKW935C200 COLLAR 6 16 RLA129A013 BRACKET MOTOR L 1 1 1 1 2 17 RLA129A014 BRACKET MOTOR R 1 1 1 1 2 18 RKY144A004 CRANK C 2 1 1 1 2 19 SSA512T096 MOTOR STEPPING 2 1 1 1 2 20 21 RLA129A018 BOX ASSY GEAR 1 1 1 1 2 21 SSA512T049 MOTOR STEPPING 1 1 1 1 2 22 RKS504A100M HARNESS ASSY 1 1 1 1 2 FOR FLAP MOTOR 23 RKS504A100N HARNESS ASSY 1 1...

Страница 97: ... 94 CRAE0223 27 21 22 29 17 11 12 23 24 26 13 20 25 25 2 14 15 19 18 16 9 6 10 28 30 32 31 4 5 7 8 3 1 HEAT EXCH CONTROL ...

Страница 98: ...3F SENSOR ASSY 1 1 1 2 4 15 SSA561B702B BLOCK TERMINAL 1 1 1 2 2 T1 16 SSA554D183 KILLER NOISE 1 17 19 RLA505A001BP PWB ASSY 1 2 2 4 8 18 SSA555B050C VARISTOR 1 1 1 1 2 Z1 19 SSA564A132 FUSE CURRENT 1 1 1 1 2 F1 3 15A 20 SSA551B017A SENSOR HUMIDITY 1 1 1 2 4 21 RLA503A001 DISPLAY ASSY 1 1 1 2 4 22 RLA505A003 PWB ASSY DISPLAY 1 2 2 4 8 23 24 RLA132A008 LID ASSY CONTROL 1 23 RLA132A007 LID CONTROL 1...

Страница 99: ... 96 CRAE0221 30 35 5 7 28 8 26 25 32 29 36 34 6 18 18 17 19 24 23 22 21 20 19 16 14 12 15 15 15 11 13 9 10 6 3 2 4 35 4 31 27 33 1 PANEL FAN ASSY ...

Страница 100: ...5 LOUVER 5 1 1 2 2 14 RLA129A009 PLATE CONNECTING L 1 1 1 1 2 15 RKW935C200 COLLAR 6 16 RLA129A013 BRACKET MOTOR L 1 1 1 1 2 17 RLA129A014 BRACKET MOTOR R 1 1 1 1 2 18 RKY144A004 CRANK C 2 1 1 1 2 19 SSA512T096 MOTOR STEPPING 2 1 1 1 2 20 21 RLA129A018 BOX ASSY GEAR 1 1 1 1 2 21 SSA512T049 MOTOR STEPPING 1 1 1 1 2 22 RKS504A100M HARNESS ASSY 1 1 1 1 2 FOR FLAP MOTOR 23 RKS504A100N HARNESS ASSY 1 1...

Страница 101: ... 98 CRAE0223 27 21 22 29 17 11 12 23 24 26 13 20 25 25 2 14 15 19 18 16 9 6 10 28 30 32 31 4 5 7 8 3 1 HEAT EXCH CONTROL ...

Страница 102: ...223F SENSOR ASSY 1 1 1 2 4 15 SSA561B702B BLOCK TERMINAL 1 1 1 2 2 T1 16 SSA554D183 KILLER NOISE 1 17 19 RLA505A001BR PWB ASSY 1 2 2 4 8 18 SSA555B050C VARISTOR 1 1 1 1 2 Z1 19 SSA564A132 FUSE CURRENT 1 1 1 1 2 F1 3 15A 20 SSA551B017A SENSOR HUMIDITY 1 1 1 2 4 21 RLA503A001 DISPLAY ASSY 1 1 1 2 4 22 RLA505A003 PWB ASSY DISPLAY 1 2 2 4 8 23 24 RLA132A008 LID ASSY CONTROL 1 23 RLA132A007 LID CONTROL...

Страница 103: ... 100 CRBE0323 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 19 8 10 PANEL FAN ASSY ...

Страница 104: ...UTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 1 1 2 4 8 SSA913A034F SCREW TAP 27 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A006 BRACKET ASSY 1 12 SSA512T094 MOTOR DC 1 1 1 1 2 13 RCV116A003 BRACKET MOTOR U 1 14 RCV141A002A PLATE BAFFLE 1 15 SSA431B253 PROPELLER 1 1 1 2 4 16 SSA914B007AC NUT TH 1 17 RCV111A001 BASE ASSY 1 1 1 1 2 18 W011D04X008 TAP...

Страница 105: ... 102 CRBE0339 21 3 7 6 15 16 11 12 17 2 9 10 8 14 13 5 22 25 23 26 27 CONTROL ASSY 24 30 31 24 19 4 20 28 1 18 24 29 GAS LIQ HEAT EXCH CONTROL ...

Страница 106: ...SA382F013K COIL ASSY SOLENOID 1 1 1 1 2 FOR 20S 14 SSA382F210AY COIL SOLENOID 1 1 1 1 2 FOR EEV 15 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 16 SSA914C013A NUT FLANGE 3 17 SSA941C346A CUSHION RUBBER 3 18 RSA932C004 GASKET COVER 1 19 RSA947K005 COVER TERMINAL 1 1 1 2 4 20 SSA914C016 NUT FLANGE 1 21 RCV505A101B PWB ASSY 1 2 2 4 8 22 RCV011G002AA LABEL WIRING 1 23 SSA561B723 BLOCK TERMINAL 1 1 1 2 2 24 ...

Страница 107: ... 104 CRBE0323 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 19 8 10 PANEL FAN ASSY ...

Страница 108: ...UTLET 1 1 1 2 3 6 SSA944B036B HANDLE 1 7 RCV142A001 COVER TB 1 1 1 2 4 8 SSA913A034F SCREW TAP 27 4 8 9 SSA913A034G SCREW TAP 1 4 12 10 SSA913A008F SCREW TAP 1 4 10 11 RCV116A006 BRACKET ASSY 1 12 SSA512T094 MOTOR DC 1 1 1 1 2 13 RCV116A003 BRACKET MOTOR U 1 14 RCV141A002A PLATE BAFFLE 1 15 SSA431B253 PROPELLER 1 1 1 2 4 16 SSA914B007AC NUT TH 1 17 RCV111A001 BASE ASSY 1 1 1 1 2 18 W011D04X008 TAP...

Страница 109: ... 106 CRBE0339 21 3 7 6 15 16 11 12 17 2 9 10 8 14 13 5 22 25 23 26 27 CONTROL ASSY 24 30 31 24 19 4 20 28 1 18 24 29 GAS LIQ HEAT EXCH CONTROL ...

Страница 110: ...SA382F013K COIL ASSY SOLENOID 1 1 1 1 2 FOR 20S 14 SSA382F210AY COIL SOLENOID 1 1 1 1 2 FOR EEV 15 AHT201A864DR COMPRESSOR ASSY 1 1 2 3 8 16 SSA914C013A NUT FLANGE 3 17 SSA941C346A CUSHION RUBBER 3 18 RSA932C004 GASKET COVER 1 19 RSA947K005 COVER TERMINAL 1 1 1 2 4 20 SSA914C016 NUT FLANGE 1 21 RCV505A101B PWB ASSY 1 2 2 4 8 22 RCV011G002AA LABEL WIRING 1 23 SSA561B723 BLOCK TERMINAL 1 1 1 2 2 24 ...

Страница 111: ... 108 CRBE0324 9 13 15 16 14 17 7 6 4 19 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...

Страница 112: ...3 6 RCT132A002 COVER ASSY SERVICE 1 1 1 1 2 7 SSA944B036B HANDLE 1 8 RCT131A001 GUARD FIN 1 9 RCT142A004 COVER TB 1 1 1 2 4 10 SSA913A034F SCREW TAP 25 4 8 11 SSA913A034G SCREW TAP 1 4 12 12 SSA913A008F SCREW TAP 1 4 10 13 RCT116A003 BRACKET MOTOR 1 14 SSA512T091A MOTOR DC 1 1 1 1 2 15 RCT141A001A PLATE BAFFLE 1 1 1 2 4 16 SSA431B250 PROPELLER 1 17 SSA914B007AC NUT TH 1 18 RCT111A001AG BASE ASSY 1...

Страница 113: ... 110 CRBE0326 10 11 7 8 6 30 29 32 29 33 CONTROL ASSY 21 13 3 4 2 20 19 31 16 34 17 1 12 9 5 GAS 18 29 14 15 LIQ 24 23 27 26 25 28 22 HEAT EXCH CONTROL ...

Страница 114: ...EV 14 RCT154D004 INSULATION COMP 1 15 RCV154D003 INSULATION COMP 1 16 RSA201A036 COMPRESSOR ASSY 1 1 2 3 8 17 SSA914C013A NUT FLANGE 2 18 SSA941C354 CUSHION RUBBER 3 19 RSA932C004 GASKET COVER 1 20 RSA947K005 COVER TERMINAL 1 1 1 2 4 21 SSA914C016 NUT FLANGE 1 22 RCT505A005AA PWB ASSY MAIN 1 2 2 4 8 23 RCT505A004A PWB ASSY SUB 1 2 2 4 8 24 RCT011G002AB LABEL WIRING 1 25 SSA561B665 BLOCK TERMINAL 1...

Страница 115: ...NVERTER RESIDENTIAL AIR CONDITIONERS Copyright MITSUBISHI HEAVY INDUSTRIES LTD Because of our policy of continuous improvement we reserve the right to make changes in all specifications without notice C ...

Отзывы: