GB
11
2. CMB-P108, 1012, 1016V-JA, CMB-P1016V-KA (When a Sub BC controller is connected)
Ⓓ
a
a
b
b
Ⓐ
Ⓔ
Ⓓ
Ⓓ
B
B
c
c
d d
Ⓕ
Ⓖ
Ⓐ
Ⓒ
Ⓒ
Ⓒ
Ⓓ
Ⓓ
K
K
L
L
A
C
C
C
D
D
D
E
E
Ⓓ
Ⓒ
G
G
G
J
J
J
M
M
M
F
F
F
e e
f
f
g g
j
j
*1
Ⓖ
Ⓓ
h4
H
H
1
h1
h1
h1
h3
h2
Ⓑ
E
Ⓖ
Ⓖ
A
(Unit: m)
Item
Piping portion
Allowable value
Length
Total piping length
"K+L+A+B+C
+D+E+F+G+J
+M+a+b+c+d
+e+f+g+j"
Not to exceed the
maximum refrigerant
piping length *1
Longest piping length
"K(L)+A+C
+E+G+J+j"
165 or less
(Equivalent length of
190 or less)
Between outdoor (heat source)
unit and Main BC controller
"K(L)+A"
110 or less
Direct connection between indoor
units and (Main or Sub) BC
controller
"a" or "b" or
"B+c" or
"B+d" or "e"
or "f" or "g" or
"j"
60 or less *2
Between indoor units and Main
BC controller via Sub BC
controller
"C+D+e" or
"C+E+F+f" or
"C+E+G+M+g"
or
"C+E+G+J+j"
90 or less *3
Dif
ference of height
Between
indoor and
outdoor (heat
source) units
Above outdoor
(heat source) unit H
50 or less
Below outdoor
(heat source) unit H1
40 or less
Between BC controller (Both Main
and Sub) and indoor unit
h1
15 or less
(10 or less *4)
Between indoor units
h2
30 or less
(20 or less *4)
Between BC controller (Both Main
and Sub) and Sub BC controller
h3
15 or less
Between outdoor (heat source)
units
h4
0.1 or less
Ⓐ
Outdoor unit (Heat source unit)
Ⓑ
BC controller (Main)
Ⓒ
BC controller (Sub)
Ⓓ
Indoor unit (Total capacity of downstream indoor unit: 15 to 80)
Ⓔ
Indoor unit (Total capacity of downstream indoor unit: 100 to 250)
Ⓕ
Twinning pipe (Model name: CMY-R160-J1)
Ⓖ
2-Branch Joint Pipe
Notes:
*1 Refer to “Restrictions on piping length” on P. 3.
*2 Refer to Fig. 1. (However, when P200 or P250 model of indoor unit is
connected, the maximum allowable distance between BC controller and
farthest indoor unit is 40 m.)
*3 When the piping length or the height difference exceeds the restriction
specified in Fig. 1, connect a sub BC controller to the system. The
restriction for a system with a sub BC controller is shown in Fig. 2.
When a given system configuration falls within the shaded area in Fig.
2, increase the size of the high-pressure pipe and the liquid pipe
between the main and sub BC controller by one size. When using P32,
P40, P50, P100, or P125 model of indoor units, increase the size of the
liquid branch pipe between the sub BC controller and indoor unit by
one size.
When using P140 or larger model of indoor units, the restriction shown
in Fig. 1 cannot be exceeded.
*4 The values in the parentheses show the maximum piping length to be
followed when the connection capacity of the indoor unit is 200 or
above.
*5 In the system to which indoor units of the P200 model or above are
connected, neither a branch joint nor a branch header may be used.
*6 Do not connect the P200 or P250 models of indoor units and other
models of indoor units at the same port.
*7 In the system to which indoor units of the P100 through P140 models
are connected, merge the two ports before connecting them. (Set DIP
SW4-6 on the BC controller to ON.)
*8 It is possible to connect the P100 through P140 models of indoor units
to a single port. (Set DIP SW4-6 to OFF.) Note that the cooling capacity
will somewhat decrease. (The factory setting for DIP SW4-6 is OFF.)
When connecting only PEFY-P50/63/71/80VMHS2-E units, set the
dipswitches SW4-1 and SW4-6 on the BC controller to ON.
*9 Indoor units that are connected to the same branch joint cannot be
simultaneously operated in different operation modes.
*10 When connecting PEFY-P50/63/71/80VMHS2-E units to two ports, use a
Joint Pipe Kit CMY-R160-J1.
*11 The maximum total capacity of indoor units that can be connected to
each Sub BC controller is P350.
*12 Sub BC controller cannot be used at
Ⓑ
.
*13 For connecting 15 to 50 model indoor units
Have pipe expansion of indoor unit connecting port by cutting the piping at
the cutting point which depends on the indoor unit capacity.
*14 Up to 11 Sub BC controllers can be connected.
Unit 1
Unit 2