2. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
*1. If an address is a duplicate of an indoor unit or outdoor unit of another refrigerant circuit, set another address, which
is within the setting range and is not in use.
*2. To set the outdoor unit address to "100," set the switches to "50."
*3. For the addresses of the outdoor units to be used together, set consecutive numbers in order from the one with the
highest capacity.
Furthermore, for the outdoor units of the same refrigerant circuit, the order of OC and OS becomes from the one with
the highest capacity. (If the capacity is the same, the order is from the one with the lowest address.)
Unit or controller
Symbol Address setting
range
Setting method
Facto-
ry set-
ting
Indoor unit
Main/sub unit
IC
01 to 50
*1
Assign the smallest address to the main indoor
unit in the group, and assign sequential address
numbers to the rest of the indoor units in the
same group.
00
LOSSNAY, OA processing unit
LC
01 to 50
*1
Assign an arbitrary but unique address to
each of these units after assigning an ad-
dress to all indoor units.
00
MA remote controller
MA
No address settings required. (The main/sub setting must be
made if 2 remote controllers are connected to the system.)
Main
Outdoor unit
OC
OS
51 to 100
*2
Assign an address that equals the lowest ad-
dress of the indoor units in the same refriger-
ant circuit plus 50.
Assign sequential addresses to the outdoor
units in the same refrigerant circuit. The out-
door units in the same refrigerant circuit are
automatically designated as OC and OS.
*3
00
System controller Group remote
controller
TR,
SC
0, 201 to 250
Assign an address that equals the sum of the
smallest group number of the group to be
controlled and 200.
201
System remote
controller
SR,
SC
Assign an arbitrary but unique address within
the range listed on the left to each unit.
ON/OFF re-
mote controller
AN,
SC
Assign an address that equals the sum of the
smallest group number of the group to be
controlled and 200.
Schedule timer
(compatible
with M-NET)
ST,
SC
Assign an arbitrary but unique address within
the range listed on the left to each unit.
202
Central con-
troller
G(B)-50A
GR,
SC
000,
201 to 250
Assign an arbitrary but unique address within
the range listed on the left to each unit.
000
LM adapter
SC
201 to 250
Assign an arbitrary but unique address within
the range listed on the left to each unit.
247
Содержание City Multi PFAV-P500VMH-E
Страница 1: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 37: ... 28 ...
Страница 39: ... 30 ...
Страница 48: ... 39 HWE07150 GB IV Indoor Unit Structure 1 External View 41 2 Control Box 42 3 Board 43 4 Fan 44 ...
Страница 49: ... 40 ...
Страница 50: ... IV Indoor Unit Structure 41 HWE07150 GB IV Indoor Unit Structure 1 External View PFAV P500VMH E ...
Страница 55: ... 46 ...
Страница 59: ... 50 ...
Страница 61: ... 52 ...
Страница 65: ... 56 ...
Страница 66: ... 57 HWE07150 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 59 2 Principal Parts and Functions 60 ...
Страница 67: ... 58 ...
Страница 73: ... 64 ...
Страница 75: ... 66 ...
Страница 95: ... 86 ...
Страница 107: ... 98 ...
Страница 195: ... X Troubleshooting 186 HWE07150 GB ...
Страница 196: ... 187 HWE07150 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 189 ...
Страница 197: ... 188 ...
Страница 242: ......