X
Troubleshooting ]
- 139 -
HWE07150
GB
1. Error
Code
No response error
2. Error
definition and error detection method
When no response command is returned although acknowledgement (ACK) is received after transmission, an error is detect-
ed.
When the data is transmitted 10 times in a row with 3 seconds interval, an error is detected on the transmission side.
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc-
curred.
3. Cause
1) The transmission line work is performed while the power is on, the transmitted data will collide, and the wave shape will be
changed.
2) The transmission is sent and received repeatedly due to noise.
3) Decrease of transmission line voltage/signal by exceeding acceptable range of transmission wiring.
Farthest:200m [656ft] or less
Remote controller wiring:12m [39ft] or less
4) The transmission line voltage/signal is decreased due to erroneous sizing of transmission line.
Wire diameter: 1.25mm
2
[AWG16] or more
4. Check method and remedy
1) When an error occurs during commissioning, turn off the power sources for the outdoor unit, indoor unit, and LOSSNAY for 5
or more minutes, and then turn them on again.
When they return to normal operation, the cause of the error is the transmission line work performed with the power on.
If an error occurs again, check the cause 2).
2) Check 3) and 4) above.
If the cause is found, correct it.
If no cause is found, check 3).
3) Check transmission wave shape/ noise on trans-mission line by following "
X
[3] Investigation of Transmission Wave Shape/
Noise".(page 159)
Noise is the most possible cause of the error "6608".
6608
Содержание City Multi PFAV-P500VMH-E
Страница 1: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 37: ... 28 ...
Страница 39: ... 30 ...
Страница 48: ... 39 HWE07150 GB IV Indoor Unit Structure 1 External View 41 2 Control Box 42 3 Board 43 4 Fan 44 ...
Страница 49: ... 40 ...
Страница 50: ... IV Indoor Unit Structure 41 HWE07150 GB IV Indoor Unit Structure 1 External View PFAV P500VMH E ...
Страница 55: ... 46 ...
Страница 59: ... 50 ...
Страница 61: ... 52 ...
Страница 65: ... 56 ...
Страница 66: ... 57 HWE07150 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 59 2 Principal Parts and Functions 60 ...
Страница 67: ... 58 ...
Страница 73: ... 64 ...
Страница 75: ... 66 ...
Страница 95: ... 86 ...
Страница 107: ... 98 ...
Страница 195: ... X Troubleshooting 186 HWE07150 GB ...
Страница 196: ... 187 HWE07150 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 189 ...
Страница 197: ... 188 ...
Страница 242: ......