- 25 -
HWE07150
GB
(2) Sample control wiring (Different refrigerant group operation)
(1) Cautions
1) Do not connect together the terminal blocks (TB5) of in-
door units connected to different outdoor units.
2) Three or more MA remote controllers cannot be set for
indoor units in the same group. If there are three or more
indoor units, ensure there are no more than two MA re-
mote controllers. Disconnecting the relay connector for
wiring the MA remote controller in the indoor unit allows
for the indoor unit to be set to the same state as when the
MA remote controller has been removed.
(2) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2
[AWG16] or larger)
L1+L2, L3+L4 200m [656ft]
2) Transmission line for centralized control
Same as [4] (1).
3) MA remote controller wiring
Maximum overall line length (0.3 to 1.25mm
2
)
[AWG22~16]
m1+m2+m3 200m [656ft]
(3) Wiring method and address setting
1) Indoor/outdoor transmission cable
Connect terminals M1 and M2 of the terminal block (TB3)
for the indoor-outdoor transmission cable of the outdoor
unit (OC, OS) and terminals A and B of the terminal block
(TB5) for the indoor-outdoor transmission cable of each
indoor unit (IC). (Non-polarized two-wire)
* Only use shielded cables.
[Shielded cable connection]
Same as [4] (1).
2) Transmission cable for centralized control
Same as [4] (1).
3) MA remote controller wiring
* In the case of different refrigerant group operation, be
sure to set the MA remote controller of one of the indoor
units as the sub remote controller.
Same as [4] (1).
[In the case of operation with two remote controllers]
Same as [4] (1).
[In the case of indoor group operation]
In the case of group operation of indoor units, connect to-
gether the terminal 1 and 2 pairs of the terminal blocks
(TB15) of both indoor units. (Non-polarize two-wire)
* Set the main/sub selection setting of the remote con-
troller of one of the indoor units to the sub remote con-
troller.
Set the indoor unit that has the most functions within
the same group as the main unit.
4) Switch Setting
Refer to Chapter 3-[2]-(1) "Address Setting". (page 19)
CN41 as it is
CN41 as it is
Group
MA(body)
Sub
m1
m2
m3
MA(body)
Main
L1
L2
OC
TB7
M1M2
M1M2
S
TB3
TB5
A
A1 B2
A1 B2
L3
B
1 2
S
TB15
IC
51
CN41 as it is
OS
TB7
M1M2
M1M2
S
TB3
52
OC
TB7
M1M2
A B
S
TB3
53
01
TB5
M1M2
CN41 as it is
L4
OS
TB7
M1M2S
TB3
54
M1M2
1 2
S
TB15
IC
03
Содержание City Multi PFAV-P500VMH-E
Страница 1: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 37: ... 28 ...
Страница 39: ... 30 ...
Страница 48: ... 39 HWE07150 GB IV Indoor Unit Structure 1 External View 41 2 Control Box 42 3 Board 43 4 Fan 44 ...
Страница 49: ... 40 ...
Страница 50: ... IV Indoor Unit Structure 41 HWE07150 GB IV Indoor Unit Structure 1 External View PFAV P500VMH E ...
Страница 55: ... 46 ...
Страница 59: ... 50 ...
Страница 61: ... 52 ...
Страница 65: ... 56 ...
Страница 66: ... 57 HWE07150 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 59 2 Principal Parts and Functions 60 ...
Страница 67: ... 58 ...
Страница 73: ... 64 ...
Страница 75: ... 66 ...
Страница 95: ... 86 ...
Страница 107: ... 98 ...
Страница 195: ... X Troubleshooting 186 HWE07150 GB ...
Страница 196: ... 187 HWE07150 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 189 ...
Страница 197: ... 188 ...
Страница 242: ......