X
Troubleshooting ]
- 182 -
HWE07150
GB
3. Leak spot: In the case of extension pipe for indoor unit (Heating season)
(1) Run all the indoor units in heating test run mode.
1) To run the indoor unit in test run mode, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON.
2) Change the setting of the remote controller for all the indoor units to the heating mode.
3) Check that all the indoor units are performing a heating operation.
(2) Stop all the indoor units, and stop the compressor.
1) To stop all the indoor units and the compressors, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON.
2) Check that all the indoor units are stopped.
(3) Close the service valves (BV1 and BV2).
(4) Collect the refrigerant that remains inside the indoor unit. Do not discharge refrigerant into air into the atmosphere
when it is collected.
(5) Repair the leak.
(6) After repairing the leak, perform evacuation of the extension pipe for the indoor unit, and open the service valves
(BV1 and BV2) to adjust refrigerant.
4. Leak spot: In the case of outdoor unit (Heating season)
1) Collect the refrigerant in the entire system (outdoor unit, extended pipe and indoor unit).Do not discharge refrigerant into the
atmosphere when it is collected.
2) Repair the leak.
3) After repairing the leak, replace the dryer with the new one, and perform evacuation of the entire system, and calculate the
standard amount of refrigerant to be added (for outdoor unit, extended pipe and indoor unit), and charge the refrigerant.
Refer to "
IX
[4] 3. "(page 90)
If the indoor or outdoor units need to be turned off for repairing leaks during Step 1) above, turn off the power approximately
1 hour after the units came to a stop.
If the power is turned off in less than 15 minutes, LEV2a and LEV2b may close, trapping high-pressure refrigerant in the out-
door unit heat exchanger and creating a highly dangerous situation.
Содержание City Multi PFAV-P500VMH-E
Страница 1: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 37: ... 28 ...
Страница 39: ... 30 ...
Страница 48: ... 39 HWE07150 GB IV Indoor Unit Structure 1 External View 41 2 Control Box 42 3 Board 43 4 Fan 44 ...
Страница 49: ... 40 ...
Страница 50: ... IV Indoor Unit Structure 41 HWE07150 GB IV Indoor Unit Structure 1 External View PFAV P500VMH E ...
Страница 55: ... 46 ...
Страница 59: ... 50 ...
Страница 61: ... 52 ...
Страница 65: ... 56 ...
Страница 66: ... 57 HWE07150 GB VII Refrigerant Circuit 1 Refrigerant Circuit Diagram 59 2 Principal Parts and Functions 60 ...
Страница 67: ... 58 ...
Страница 73: ... 64 ...
Страница 75: ... 66 ...
Страница 95: ... 86 ...
Страница 107: ... 98 ...
Страница 195: ... X Troubleshooting 186 HWE07150 GB ...
Страница 196: ... 187 HWE07150 GB XI LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 189 ...
Страница 197: ... 188 ...
Страница 242: ......