58
*1
Check the short circuit, reverse connection, disconnection, terminating resistor, FG connection, total length, and
distance between stations.
YES
YES
NO
Is the RDY LED on?
Is the station number setting
switch correctly configured?
YES
Is the transmission speed setting correct?
The applicable module is in failure
(transmission speed setting switch).
Power on the module again.
Power on the module again.
The applicable module is in failure
(station number setting switch).
Correctly configure the station number.
NO
NO
Correctly configure the
transmission speed setting.
NO
Properly wire the communication cable.
Correctly configure the station number.
Completed
Power on the module again.
Is the communication
cable properly wired?
*1
YES
Is the station number setting
switch correctly configured?
YES
NO
1
2
3