APPENDICES
A
Appendix
1 EM
C
and Low Volt
ag
e
Direc
tives
Appendix
1.
1 Requirem
ent
s f
o
r
com
p
lianc
e wit
h t
he E
M
C
Direct
ive
(2) Cables
(a) CC-Link dedicated cable
Use the AD75CK cable clamp (Mitsubishi) to shield the cable connected to the CC-Link module located close
to the exit of the control panel or each CC-Link station, and ground the shielded part of the CC-Link dedicated
cable to the control panel within 30cm from the module or station.
The Ver.1.10-compatible CC-Link dedicated cable is a shielded cable. Strip a part of the jacket of the cable as
shown below and ground the exposed shield to the ground as much as possible.
Use the specified Ver.1.10-compatible CC-Link dedicated cable.
Use the FG terminals of the CC-Link module and CC-Link stations as shown below to connect to the FG line
inside the control panel.
For the CC-Link dedicated cable, attach a ferrite core having the attenuation characteristics equivalent to that
of ZCAT3035-1330 made by TDK Corporation as close to the CC-Link side terminal block of this product as
possible. Use a ferrite core with two turns of wire as shown below.
(b) AnyWire Bitty cable
For the AnyWire Bitty cable, attach a ferrite core having the attenuation characteristics equivalent to that of
ZCAT3035-1330 made by TDK Corporation as close to the AnyWire Bitty side terminal block of this product as
possible. Use a ferrite core with two turns of wire as shown below.
(c) Power cable for the 24VDC power supply terminal
Use a CE-marked DC power supply. The DC power supply must be placed together with the module in the
same control panel, and the power cable connected to the power terminal of this product should be 30cm or
shorter.
CC-Link Ver.1.10 compatible cable
Shield
Terminating
resistor
Terminating
resistor
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
(Blue)
(White)
(Yellow)
(Blue)
(White)
(Yellow)
(Blue)
(White)
(Yellow)
(Blue)
(White)
(Yellow)
CC-Link Ver.1.10
compatible cable
CC-Link Ver.1.10
compatible cable
DA
DB
DG
SLD
FG
Master module
Remote module
Local module
Содержание CC-Link-AnyWire Bitty Bridge
Страница 1: ...CC Link AnyWire Bitty Bridge Module User s Manual NZ2AW1C1BY ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 14: ...12 Memo ...
Страница 24: ...22 2 4 External Dimensions Unit mm 15 4 3 85 141 5 DIN rail 3 8 2 5 66 69 40 100 51 ...
Страница 53: ...51 CHAPTER 10 CC LINK I O RESPONSE TIME 10 Memo ...
Страница 73: ......