CHAPTER 6 MEMORY MAPS
6
6.
4 Er
ror
R
e
set
6.4
Error Reset
Remote station READY is turned on after the reset by supplying the power.
Error status flag is set (turns on) when an error occurs. Error status flag is reset (turns off) by turning on Error reset
request flag from off, provided that the error cause has been eliminated.
Remote station READY is reset (turns off) when an error has occurred. Remote station READY remains reset (remains
off) until Error reset request flag is turned off.
The remote device values for Remote station READY, Error status flag, and Error reset request flag at each occupied
station setting are shown in the table below.
n: Address assigned to the master station in the station number setting
Name
Number of occupied stations
1 station occupied
2 stations occupied
3 stations occupied
4 stations occupied
Remote station READY
RX(n+1)A
RX(n+3)A
RX(n+5)A
RX(n+7)A
Error status flag
RX(n+1)B
RX(n+3)B
RX(n+5)B
RX(n+7)B
Error reset request flag
RY(n+1)A
RY(n+3)A
RY(n+5)A
RY(n+7)A
Error status flag
An error occurred
Error reset request flag
Remote station READY
ON
ON
OFF
OFF
OFF
ON
The flag is turned on
using the user's program
after the error cause is
removed.
Содержание CC-Link-AnyWire Bitty Bridge
Страница 1: ...CC Link AnyWire Bitty Bridge Module User s Manual NZ2AW1C1BY ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 14: ...12 Memo ...
Страница 24: ...22 2 4 External Dimensions Unit mm 15 4 3 85 141 5 DIN rail 3 8 2 5 66 69 40 100 51 ...
Страница 53: ...51 CHAPTER 10 CC LINK I O RESPONSE TIME 10 Memo ...
Страница 73: ......