52
CHAPTER 11
TRANSMISSION TIME
This section describes the transmission cycle time and transmission delay time of AnyWire Bitty.
11.1
Transmission Cycle Time
The transmission cycle time is the time required for a bridge module and all the slave modules to update I/O data.
11.1.1
Transmission cycle time of the NZ2AW1C1BY
The transmission cycle time of the NZ2AW1C1BY is listed in the table below.
11.1.2
Effects of the double check system
(1) Input
Unless the same data is received twice successively on the NZ2AW1C1BY side, the input area data is not
updated. Therefore, a minimum of one-transmission cycle time and a maximum of two-transmission cycle time
are required as the data response time.
Therefore, when a signal is shorter than two-transmission cycle time, the input data may not be captured
depending on the timing.
To ensure the response, provide an input signal that is longer than two-transmission cycle time.
(2) Output
As the double check is performed on the slave module side, the time required is the same as that for input,
namely a minimum of one-transmission cycle time and a maximum of two-transmission cycle time.
Number of occupied stations
Transmission cycle time
1 station occupied
3.2ms
2 stations occupied
5.5ms
3 stations occupied
10.2ms
4 stations occupied
10.2ms
Minimum data
response time
Input data change
Input data change
Input data update
Input data update
Maximum data
response time
Sampling timing
Sampling timing
Sampling timing
Minimum one-transmission cycle time
Maximum two-transmission cycle time
Sampling timing
Sampling timing
Содержание CC-Link-AnyWire Bitty Bridge
Страница 1: ...CC Link AnyWire Bitty Bridge Module User s Manual NZ2AW1C1BY ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 14: ...12 Memo ...
Страница 24: ...22 2 4 External Dimensions Unit mm 15 4 3 85 141 5 DIN rail 3 8 2 5 66 69 40 100 51 ...
Страница 53: ...51 CHAPTER 10 CC LINK I O RESPONSE TIME 10 Memo ...
Страница 73: ......