background image

9

TWG TECHNICAL SPECIFICATIONS

Model

TWG

80

TWG

100

TWG

125

TWG

150

TWG

175

Capacity

kcal/h

80.000

100.000

125.000

150.000

175.000

kW

93

116

145

174

203

Width

A

mm

707

707

707

757

757

Width

H

mm

757

757

757

807

807

Height

H1

mm

933

933

933

983

983

Height

L

mm

1299

1299

1539

1544

1744

Length

L1

mm

742

742

982

987

1187

Foot record

E

mm

200

200

200

200

200

Chimney Diameter

H2

mm

547

547

547

597

597

Chimney Height

F

DN

65

65

65

65

65

Hot Water Flow / Return

lt

118

118

145

160

191

(PN 16)

kg

360

370

425

460

510

Water Volume

S

inch

1 1/4”

1 1/4”

1 1/4”

1 1/4”

1 1/4”

Dry Weight

S1

inch

1/2”

1/2”

1/2”

1/2”

1/2”

Safety Departure / Return

C

inch

1”

1”

1”

1”

1”

Condensing Expense

mbar

0.5

1.2

1.3

2.2

2.5

Back Pressure

bar

4

4

4

4

4

TLG TECHNICAL SPECIFICATIONS

Model

TLG

1500

TLG

1750

TLG

2000

TLG

2500

TLG

3000

TLG

3500

Capacity

kcal/h 1.500.000 1.750.000 2.000.000 2.500.000 3.000.000 3.500.000

kW

1740

2030

2320

2900

3480

4060

Width

A

mm

1654

1654

1654

1648

1782

1880

Width

H

mm

1674

1674

1674

1688

1802

1900

Height

H1

mm

1855

1855

1855

1971

1985

2083

Height

L

mm

3054

3354

3754

4060

5085

4612

Length

L1

mm

2484

2784

3184

3474

4515

3986

Foot record

E

mm

500

500

500

500

500

500

Chimney Diameter

H2

mm

1264

1264

1264

1279

1361

1510

Chimney Height

F

DN

150

150

150

200

200

200

Hot Water Flow / Return

lt

2088

2363

2731

2714

2731

2580

(PN 16)

kg

3450

3855

4430

4945

6555

6900

Water Volume

S

inch

2 1/2”

2 1/2”

2 1/2”

2 1/2”

2 1/2”

2 1/2”

Dry Weight

S1

inch

1”

1”

1”

1”

1”

1”

Safety Departure / Return

C

inch

1”

1”

1”

1”

1”

1”

Condensing Expense

mbar

5.8

6.2

6.7

6.5

6.8

7

Back Pressure

bar

4

4

4

4

4

4

Содержание TLG 100

Страница 1: ...Heating Boiler User Guide...

Страница 2: ...www facebook com ekinendustriyel www youtube com ekinendustriyel www linkedin com company ekinendustriyel www soundcloud com ekinendustriyel www twitter com ekinendustriyel www spotify com ekin endus...

Страница 3: ...stioning of the status quo and our desire to outperform ourselves New Generation Engineering With our engineering approach that focuses on the process not the problem we do not just specialize in a pr...

Страница 4: ...te Valves Actuators Check Valves and Strainers Thermoplastic Valves Boilers Steam Generators Solar Collectors Chillers Cooling Towers Gasketed Plate Heat Exchangers Brazed Heat Exchangers Shell Tube H...

Страница 5: ...1 Precautions 3 Product General Specifications 7 Shipping And Installation 13 First Run And Considerations Before First Run 20 Boiler Water Specifications 21 General Maintenance 21 Detection And Fixi...

Страница 6: ...te of the period for such repairs Device repair duration shall not exceed 20 business days This duration shall start from the date of notification to the service station and in the event of the absenc...

Страница 7: ...outside the scope of warranty In case of wrong connection while installing electricity connection of the device any related failures shall be outside the scope of warranty Failure to comply with techn...

Страница 8: ...r problems originated from boilers installed in living quarters In installations with closed expansion tank make sure to use automatic safety valve suitable for boiler operating pressure Our company c...

Страница 9: ...e explosion of the boiler In this case please check the circulation pump working immediately close burner and wait for cooling in natural way then contact to authorized service To prevent any accident...

Страница 10: ...er does not work again related burner authorized service must be called If you feel or smell gas or if there is a gas leak Stay calm Extinguish any burning fires Open doors and windows Close valves of...

Страница 11: ...nical support we remind you to prepare the following information for providing better service to you Located on the aluminum sheet label on the device 1 Year of manufacture and serial number of the de...

Страница 12: ...1 2 1 2 1 2 1 2 Back Pressure mbar 1 2 1 3 1 5 2 2 2 3 2 5 Standard Operating Pressure bar 4 4 4 4 4 4 Ekin End striyel MG series gas fueled heating boilers are manufactured with three pass Known as...

Страница 13: ...1 2 1 2 1 1 1 Back Pressure mbar 2 8 3 3 8 5 2 5 2 5 7 Standard Operating Pressure bar 4 4 4 4 4 4 TLG TECHNICAL SPECIFICATIONS Model TLG 600 TLG 700 TLG 800 TLG 900 TLG 1000 TLG 1250 Capacity kcal h...

Страница 14: ...2 5 Back Pressure bar 4 4 4 4 4 TLG TECHNICAL SPECIFICATIONS Model TLG 1500 TLG 1750 TLG 2000 TLG 2500 TLG 3000 TLG 3500 Capacity kcal h 1 500 000 1 750 000 2 000 000 2 500 000 3 000 000 3 500 000 kW...

Страница 15: ...se mbar 3 3 3 2 8 2 5 3 Back Pressure bar 4 4 4 4 4 TWG TECHNICAL SPECIFICATIONS Model TWG 450 TWG 500 TWG 600 TWG 700 TWG 800 TWG 1000 Capacity kcal h 450 000 500 000 600 000 700 000 800 000 1 000 00...

Страница 16: ...2289 Height L mm 2720 2920 3515 3915 3915 4219 Length L1 mm 2194 2394 2994 3394 3394 3698 Foot record E mm 500 500 500 500 500 500 Chimney Diameter H2 mm 1460 1460 1585 1585 1643 1670 Chimney Height...

Страница 17: ...635 2687 Height L mm 5245 5251 5345 5747 6721 Length L1 mm 4724 4730 4826 5226 6200 Foot record E mm 500 500 500 600 600 Chimney Diameter H2 mm 1776 1884 1884 1966 2014 Chimney Height F DN 200 200 200...

Страница 18: ...panies From the point of safety of you and your environment never install the device in daily life sections kitchen bathroom hallway etc open spaces and balconies places where explosive and easily fla...

Страница 19: ...elbow is required it is crucial to use round and wide angle elbows and not to use more than two elbows Steel chimney connection must be manufactured and assembled in a way to disassemble from boiler...

Страница 20: ...PIPING FEEDING WATER OUTLET DISCHARGE VALVE CUT OFF VALVE TEMPERATURE PROBE DISCHARGING PIPE DIRT SEPERATOR AIR RELIEF COCK SAFETY VALVE CIRCULATION PUMP CHECKVALVE THREE WAY VALVE MANOMETER THERMOME...

Страница 21: ...ry Fed Operation Time Mod 1 20 35 mA Mod 2 8 10 mA Available Battery Type 5 hours Rechargeable Battery Rechargeable Battery NiMh 9V Battery Charging Method Constant Current and Constant Voltage Batter...

Страница 22: ...g down when there is temperature difference between boiler water temperature and adjusted thermostat temperature as much as burner first stage difference temperature the burner is activated at first l...

Страница 23: ...ry After adjusting system with stages above adjust thermostat temperature with up arrow button When you turn off the device with device On Off button the system will start to work in this configuratio...

Страница 24: ...ch burner second stage adjustment menu press Selectbutton five times and you will see the following screen 2 Hold the up arrow button the indicator will display off on screenwhen you select 98 3 Wait...

Страница 25: ...pass valve Air must be taken from air intake valves and air relief cocks in the installation Circulation pump should not be run during air intake Ekin End striyel is not responsible for the burner on...

Страница 26: ...ck the following considerations Monitor operations of boiler fittings thermostat thermometer hydrometer manometer all the time do the necessary controls replace it if necessary By putting thin mineral...

Страница 27: ...external temperature is 12 C and lower When external air temperature is between 12 15 C heating system should be operated in limited mode If external air temperature is 15 C and higher heater should...

Страница 28: ...e missing water It is required to use with appropriate safety valve Closed expansion tanks can only be used in liquid and gas fueled heating systems provided automatic control mechanical combustion Fu...

Страница 29: ...mbly Scheme 1 Gas filter 2 Test nipple 3 Push tap and manometer 4 Compensator 5 Global gas valve 6 Gas entry line 7 Mutliblock gas valve Filter Regulator Minimum gas processor Safety gas valve operati...

Страница 30: ...laced with an appropriate pump Make your burner checked by authorized service Water accumulation or leakage in smoke chest Condensation of water vapor in flue gas Failure in operating boiler in low te...

Страница 31: ...there is AC energy input to the system Temperature warning is flashing on the screen Overheating in boiler Boiler temperature increases over 95 degrees Lower the temperature The burner cannot be activ...

Страница 32: ...27 CERTIFICATES...

Страница 33: ......

Страница 34: ...ICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERVICE SERV...

Страница 35: ......

Страница 36: ...4EK N Dudullu Organize Sanayi B lgesi Des Sanayi Sitesi 107 Sk B14 Blok No 2 mraniye stanbul Turkey Phone 90 216 232 2412 Fax 90 216 660 13 08 info ekinendustriyel com www ekinendustriyel com Is tma S...

Отзывы: